Hochiki FireNET Plus User manual

FireNETPlusWiringInstruction1V1.01
FireNET Plus Wiring Instructions
This manual provides wiring instructions for the 1 loop and 2 loop version of the FireNET
Plus panels, which supports our finest Hochiki’s DCP protocol.
Note: Refer to wiring diagrams for specific part numbers and descriptions of all fire control
panels covered in this manual. The operation of this product is intended for indoor use only.
Table of Contents
1. Front Panel View ......................................................................................................2
2. Wiring Gauge............................................................................................................2
3. Reference Documents..............................................................................................2
4. Terminal Connection.................................................................................................2
5. Model Description.....................................................................................................3
6. Power Supply Circuit ................................................................................................3
7. Battery Circuit...........................................................................................................4
8. Ground Fault.............................................................................................................5
9. Power Output Circuits...............................................................................................5
10. Limited Energy Circuit ...........................................................................................5
11. Supervised Circuits ...............................................................................................5
12. SLC Circuits ..........................................................................................................5
13. NAC Circuits..........................................................................................................6
1. Maximum Current Ratings.....................................................................................6
2. Single and Dual Circuit Synchronization................................................................6
14. Communication Circuits.........................................................................................7
15. Relay Circuits........................................................................................................8
16. Auxiliary Voltage Circuits.......................................................................................8
Version 1.01
11 March 2015
PN# 1700-10842

FireNETPlusWiringInstruction2V1.01
1. Front Panel View
The figure below is the front panel view of the FireNET Plus Panel:
1
24
3
?
Figure1
2. Wiring Gauge
Use 18 to 14AWG wiring for all field terminations except for AC terminal block. Use
14AWG only for line, neutral and ground of the AC terminations.
3. Reference Documents
For additional information on installing and operating the FireNET Plus Panel, refer to
the following documents:
FireNET Plus Installation and Operating Manual, 1700-10840, Version 1.04
Operating Instruction, 1700-10850, Version 0.3
Inner Door Label, 1700-04520, Version 1.04
4. Terminal Connection
The figure below illustrates the terminal connections of the FireNET Plus Panel:

FireNETPlusWiringInstruction3V1.01
Earth Ground
TELCO 1
TELCO 2
24V OUT
24VDC
AUX 24V
24VDC RELAYS
SLC 1 ZERO-OHM
RESISTOR
S2026
SLC 2 ZERO-OHM
RESISTOR
S2026
NETWORK
OUT
NETWORK
IN
COMMS
RS485
NAC 1
10K EOL RESISTOR
S2030
NAC 2
10K EOL RESISTOR
S2030
Figure2
5. Model Description
The following are the details of the various FireNET Plus Models:
FNP-1127 – 1 SLC Loop, Not Expandable
FNP-1127D – 1 SLC Loop with Integrated DACT, Not Expandable
FNP-1127E – 1 SLC Loop Expandable to 2 SLC Loops and Networkable
FNP-1127DE – 1 SLC Loop with Integrated DACT, Expandable to 2 SLC Loops
and Networkable
6. Power Supply Circuit
Following table is the electrical specification for the Power Supply Circuit:
Line Connection
Terminals Description Voltage Current
LAC Line 115 VAC @ 50/60 Hz 2.1 A max
230 VAC @ 50/60 Hz 1.1 A max
NAC Neutral
G
Earth Ground

FireNETPlusWiringInstruction4V1.01
Power Supply
Parameter Description
Rating 115 VAC @ 250 VA
230 VAC @ 250 VA
AC Input Fuse 3 A, 250 VAC, Slow-Blow, 5 x 20 mm
Input (Supervised) 115 VAC 50/60 Hz or
230 VAC 50/60 Hz
Transfer Voltage 115 VAC transfer @ 75 VAC
230 VAC transfer @ 160 VAC
7. Battery Circuit
Following table is the electrical specification for the Battery Circuit:
Parameter Description
Standby-Battery Type Two 12 VDC, 50 AH, Sealed Lead Acid (SLA), batteries
Standby-Battery Charging Two standby batteries wired in series
Charge Current Fast charge: 1.25 A
Trickle charge: 1.25 A (voltage limited)
Output Current 0 - 4 Amps
Standby-Operating Time 24 Hours
Battery Charge Voltage 27.6 VDC
Fire Control Panel Current Draw
From Battery While In Mains Fail,
Standby And Not in Alarm
D.P. - TBD mA with buzzer sounding
Maximum Current Draw
of FACP, In Alarm
D.P. - TBD mA (Current does not include loads from NACs, Solenoid, Remote
Annunciators, Ancillary Boards and Auxiliary equipment)
Maximum Current Draw
From Batteries
4 Amps

FireNETPlusWiringInstruction5V1.01
8. Ground Fault
A ground fault indication occurs when 30K Ohms or less is detected between earth
ground and the following field terminals of the FireNET Plus Panel:
24V OUT
AUX 24V
NAC1 and NAC 2
SLC1 and SLC2
NET IN and NET OUT
COMMS
9. Power Output Circuits
Special Application outputs are provided on the NAC1 and NAC2 terminals of the
FireNET Plus Panel.
10. Limited Energy Circuit
All circuits are power limited except for AC input/output and the battery.
11. Supervised Circuits
All circuits of the FireNET Plus Panel are supervised except relay terminals for the
TROUBLE, FIRE, SUPERVISORY and the TELCO.
12. SLC Circuits
SLC circuits of the FireNET Plus Panel operates with Hochiki’s DCP-Protocol.
Terminals Description
SLC1 IN, SLC1 OUT
and SLC2 IN, SLC2 OUT
Signaling Line Circuits are Class A, Style 7, Class A, Style 6 or Class B,
Style 4.

FireNETPlusWiringInstruction6V1.01
13. NAC Circuits
Following table is the specification for the Notification Appliance Circuits (NAC1 and
NAC2):
Parameter Description
Fuse Self-resetting 1.6 A electronic
Regulated Continuous Current Continuous DC currents cannot exceed 1.6 A from NAC 1 and NAC with the
total DC current not to exceed 3.2 A.
Regulated Pulsed Current: Pulse DC currents cannot exceed 900 mA from NAC 1 and NAC with the total
DC current not to exceed 1.8 A.
Special Application 24 VDC @ 2.3 A continuous with the combined current of NAC 1 and NAC 2
not to exceed 3.1 A.
Supervision EOL Device, 0400-01023
Synchronization Synchronize the regulated output of NAC 1 and NAC 2 with authorized and
compatible synchronization modules from Gentex, Amseco, System Sensor or
Wheelock. Connect End-Of-Line-Device S2030 to the output of each
Synchronization Module installed.
The FireNET Plus Panel provides internal device synchronization
between the outputs of NAC 1 and NAC 2 when operating NAC devices
from Gentex, Amseco, System Sensor or Wheelock.
External synchronization modules must not be used on the NAC outputs when
operating in the special application mode.
NFPA Operation Type Class B, Style Y
1. MaximumCurrentRatings
The total sum of device loads in the NAC circuit must not exceed the maximum current
specified for the FireNET Plus Panel when operating in Continuous Regulated, Pulsed
Regulated, or Special Application mode.
Note: Reference NAC manufacturer datasheets for individual device loads and then
compare the total sum to the maximum current capability of the FireNET Plus Panel in
regulated or special application mode.
2. SingleandDualCircuitSynchronization
NAC channels 1 and 2 of the FireNET Plus Panel provides single and dual circuit
synchronization. Single circuit synchronization provides a synchronized output on one of
two NAC channels. Dual circuit synchronization provides a synchronized output on both
NAC channels.

FireNETPlusWiringInstruction7V1.01
14. Communication Circuits
Phone Line Terminal Connections:
Terminal Description
L1T TELCO Line 1 Tip
L1R TELCO Line 1 Ring
P1T TELCO Phone 1 Tip
P1R TELCO Phone 1 Ring
L2T TELCO Line 2 Tip
L2R TELCO Line 2 Ring
P2T TELCO Phone 2 Tip
P2R TELCO Phone 2 Ring
RS485 Serial Bus:
Terminal Rating
COMMS (+) (+) Data 3.3 VDC @ 30 mA max
COMMS (-) (-) Data
Network Terminals:
Terminal Rating
NET OUT (+) (+) Data 3.3 VDC @ 30 mA max
NET OUT (-) (-) Data
NET IN (+) (+) Data 3.3 VDC @ 30 mA max
NET IN (-) (-) Data

FireNETPlusWiringInstruction8V1.01
15. Relay Circuits
The following is the specification for the FireNET Plus Panel Relays:
Parameter Description
Operation Common: Operates for all of the signals relative to its type (such as alarm, trouble, supervisory).
Current 1A maximum, volt free change over contact
Voltage 30 VDC max
Power Factor 1.0 PF
16. Auxiliary Voltage Circuits
The following is the specification for the FireNET Plus Panel Auxiliary Voltage Circuits:
Terminal Description
24V OUT Regulated 24 VDC @ 360 mA max
AUX 24V Regulated 24 VDC @ 360 mA max
IfyouhaveanyquestionsregardingthismatterpleasecontactTechnicalSupport.
HochikiAmericaCorporation
TechnicalSupport
1‐800‐845‐6692
Table of contents
Other Hochiki Control Unit manuals
Popular Control Unit manuals by other brands

HAUTAU
HAUTAU FTA 3.1 Original instructions

Texas Instruments
Texas Instruments TMUXBQB-DYYEVM user guide

Philips
Philips LBB 2521/10 Installation and user instructions

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R RD78G4 user manual

Humandata
Humandata ACM-018 Series user manual

OKM
OKM 5410 Series Handling manual