Hochiki S772 Technical manual

Version 1.00 |March 2021 |MAN-1420HA
16 Channel IO Panel Module
(S772) Information Guide

CONTENTS
Contents 2
Compliance 4
Underwriters Laboratories (UL) 4
FCC 4
Installation 4
Introduction 5
Technical Support 5
Return Material Authorization (RMA) 5
Warranty Service 6
Advanced Replacements 6
Overview 7
Use Case Examples 7
Package Contents 8
Installation 9
Before You Begin 10
Setting the Address 10
Placement 10
Wiring 13
Inputs 13
Outputs 14
Restrictions 15
Testing the Installation 16
Configuration 17
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 2
Contents

Panel Module Properties 17
Channel Properties 18
For channels set as Outputs 18
For channels set as Inputs 20
ULCompliance Limitations 21
Specifications 22
Electrical 22
Operating Environment 22
Physical Specifications 22
Index 23
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 3
Contents

COMPLIANCE
Underwriters Laboratories (UL)
Fire Alarm Subassembly
Hochiki America Corporation
FCC
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part
15 of the FCCRules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the Installation Manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense. Any
changes or modifications not expressly approved by Hochiki America Corporation could void the user's authority
to operate this equipment under the rules and regulations of the FCC.
Operation is subject to the following two conditions:
(1)This device may not cause harmful interference, and
(2) This device must accept any interference received, including interference that may cause undesired
operation.
Installation
Install this product in accordance with NFPA 13, NFPA 72, NFPA 70, and NEC 70 and all local codes.
All field wiring should be installed using fire rated cables according to the NFPA 72. Riser conductors shall be
installed in accordance with the survivability from attack by fire requirements in National Fire Alarm Code, NFPA
72, Section 12.3. Riser conductors shall employ either a 2 hour rated cable system, or meet requirements
approved by the AHJ.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 4
Compliance

INTRODUCTION
Technical Support
For technical support, contact Hochiki America at 800.845.6692 or technicalsupport@hochiki.com. Hochiki
technical support is available Monday through Friday, 7:00AM to 5:00PM, PST.
Prior to contacting technical support, have the following information available:
nProduct part number
nPurchase order or order number
nProduct serial number
nCurrent function of the product
nExpected function of the product
nInstallation of the product
Return Material Authorization (RMA)
Contact Technical Support to obtain an RMAfor any product to be returned. Returns will not be accepted
without an accompanying RMA number. An RMA number is assigned when:
lTech Support acknowledges a possible product failure.
lA product was damaged during shipping
lAn incorrect product was shipped
lAn order was placed using an incorrect part number *
lAn order was placed using an incorrect part quantity *
lAn order is no longer required *
* Restocking fees may apply.
All returned products are tested to confirm operating failures experienced in the field. If the product is found to be
functional, contractors must absorb expenses for return shipping, as well as the cost and shipping of the
advanced replacement product.
Prominently display the RMA number on all packages sent for return.
Ship all return products to:
Attention: RMA # _____________
Hochiki America
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 5
Introduction

7051 Village Park Drive, Suite 100
Buena Park, CA90621
Warranty Service
Technical Support can replace or repair a defective product when the original purchase is within the warranty
period defined in the sales contract. Check your contract for more information, or contact your sales
representative about your specific warranty period.
Advanced Replacements
Products that fail to operate in the field can be replaced quickly using the advanced replacement process. The
advanced replacement process is available to all contractors who maintain an acceptable line of credit.
Initiate the advanced replacement process by requesting an RMA number from a Tech Support representative.
Advanced replacements can be shipped to your location when the product is covered under warranty and when
a replacement product is in stock.
lAdvanced replacements can be expedited at the request of the contractor. Shipping costs associated with this
process are the responsibility of the contractor.
lProducts returned using the advanced replacement process must be received within 30 days of the RMA issue date.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 6
Introduction

OVERVIEW
16 Channel I/OPanel Module (S772)
The 16 Channel I/O Interface enhances the versatility of the alarm system by providing additional input and
output capabilities to the FireNET L@titude Fire Alarm ControlPanel. Inputs and outputs can be selected for up
to 16 individual channels. All inputs and outputs are configured in the same way as devices connected to
addressable loops of the panel. The 16 Channel I/O Interface can be configured to contribute or act upon cause
and effect logic.
Use Case Examples
The 16 Channel I/OInterface can be used to interface the L@titude panel to a NAC extender or Voice
Evacuation system, by providing
linputs to the L@titude panel for dry contact closures such as General Trouble, AC Power Trouble, or Battery Trouble
from these devices.
loutputs from the panel to control various NAC or Voice Evacuation outputs.
The 16 Channel I/OInterface can be used to interface the L@titude panel to a secondary panel or releasing
panel, by providing
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 7
Overview

linputs to the L@titude panel for dry contact closures such as Fire, Supervisory, and Trouble from these panels, and
various stages of release from the releasing panel.
loutputs from the panel to activate NAC outputs on these panels.
IMPORTANT! Refer to the Wiring section for restrictions when using and wiring the 16 Channel I/O Panel Module.
Package Contents
l(1) Installation sheet
l(1) Wiring Terminal Labels
l(1) S772 16 Channel I/O Interface
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 8
Overview

INSTALLATION
This section provides instructions for connecting cables, mounting, and testing the 16 Channel I/OPanel Module
for installation.
qUsing Loop Explorer 2, add the panel module to the existing configuration and configure it as required for the
system. For detailed information on the configuration settings, refer to the Configuration section.
qNotify the monitoring center and location security that the FireNET L@titude Fire Alarm ControlPanel will be
temporarily out of service.
qRemove the module from its packaging and check its contents.
qSet the address of the module as configured in Loop Explorer 2. Refer to Setting the Address for details.
qDetermine the slot (E or higher) where the panel module will be installed and place the provided sticker label on the
corresponding field terminals.
qConnect field wiring as shown in the Wiring section below.
qTransfer the new configuration from Loop Explorer 2 into the panel.
qWait for the "Sending configuration to panel" (in LE2) and "Saving configuration" (on the panel) steps to complete.
qRemove AC and battery power from the panel.
qRemove the black plastic cover.
qInstall the module into selected slot on the Main Back Board or an Extension Board of the panel.
qRestore AC and battery power.
qWait for the panel start-up process to complete. Refer to the FireNET L@titude Fire Alarm ControlPanel
Installation Manual (MAN-1431HA) for more information.
qTest communication from the panel via the LEDStatus Indicators
qResolve any troubles related to the new connections.
qActivate each circuit and verify that all connected devices function properly.
qReplace the black plastic cover.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 9
Installation

Install this product in accordance with NFPA 72, the National Electrical Code, and all local codes.
WARNING! The module must be installed by personnel familiar with electronic components. Electronic
components within the module are vulnerable to damage from electrostatic discharge. Ground straps must be worn by
installers before handling to prevent electrostatic discharge damage.
Before You Begin
The following item is not included with the FireNET L@titude Fire Alarm ControlPanel, but is required for the
installation:
lA Ground Strap is required for handling circuit boards.
Setting the Address
Panel modules should use addresses 1-8. Each panel module of the FireNET L@titude Fire Alarm
ControlPanel must contain a unique setting before being connected to the Main Back Board. The binary setting
of the DIP switch sets the specific address for the panel module. The numeric order of the address setting
between modules does not impact operation, but each panel module must be assigned a separate / unique
address.
The black portion of the DIP switch identifies the switch actuator.
Placement
To install modules on the FireNET L@titude Fire Alarm ControlPanel:
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 10
Installation

1. Disconnect AC power and standby batteries prior to performing the module installation.
2. Remove the retaining screw and plastic cover.
3. Remove the panel module from the protective packaging using adequate electrostatic protection.
4. Point the conductor side of the panel module toward the backplate.
5. Insert the notched end of the panel module in the metal guide notch of the backplate at an angle, as shown.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 11
Installation

The photo above is an example of panel module placement and may not be representative of the specific module
and slot placement described in this guide. Refer to the checklist above for details on placement.
6. Rotate the panel module until all conductors are securely inserted into connectors of the Main Back Board.
7. Replace the cover onto the Main Back Board.
8. Reconnect the batteries and restore ACpower.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 12
Installation

Wiring
Inputs
These inputs are intended for use as control signals from other life safety equipment. Inputs of this device are not
supervised, and cannot be used as initiating circuits for life safety applications within a UL listed system.
Inputs on the 16 Channel I/O Interface are intended to be activated by connecting the input to a 0V terminal
through volt-free contacts. Contacts must be suitably rated to handle 24VDC. The switch-current caused by
contact closure is limited to a maximum of 3mA.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 13
Installation

Outputs
These outputs are intended for use as control signals to other life safety equipment. Outputs of this device are not
supervised, and must not be connected to notification and/or releasing type appliances in a UL listed system.
IMPORTANT! When powering the 16 Channel I/O Panel Module from one of the AUX24V outputs of the panel, it is
recommended that external 100mA fuses be inserted at the AUX24V+terminal. Failure to use a fuse will prevent the
protection of the output and void the product warranty.
WARNING! Incorrectly connected diodes will damage 16 Channel I/O Panel Module outputs. Installers must
connect the cathode-band of the suppression diode to the positive terminal of the relay coil as shown to provide
protection.
Each output is rated up to 100mA, therefore a
100mA fuse must be used to provide protection.
Multiple channels may be protected with a single
100mA fuse if their combined currents will not
exceed 100mA.
This example shows 2 LEDs protected by a single
fuse. The combined current draw of these LEDs
will not exceed the 100mA fuse rating.
The relay is protected by a separate fuse because
its current draw would exceed 100mA if combined
with the LEDs.
Outputs are intended to be connected to a 24VDC load. Theother side of this load should be connected to a 24V
power source, such as the panel's AUX24V+ terminal.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 14
Installation

lAll output terminals are internally pulled-up to the panel's 24V power source through high impedance.
lWhen active, output terminals are pulled down to the panel's 0V through low impedance.
lOutputs should never be pulled below 0V or above 24 VDC by external circuitry.
lIndividual channel loads must not exceed 100 mA. Output terminals are not protected from overcurrent conditions.
Exceeding their current rating can cause permanent damage to the panel module.
lChannels 1-8 must be limited to 400 mA combined.
lChannels 9-16 must be limited to 400 mA combined.
Refer to the FireNET L@titude Fire Alarm ControlPanel Installation Manual (MAN-1431HA) for detailed
information on connecting field wiring and wiring terminal locations.
Restrictions
Inputs are intended for use as control signals from other life safety equipment. Inputs of this device are not
supervised, and therefore cannot be used directly as initiating circuits for life safety applications within a UL listed
system. Outputs are intended for use as control signals to other life safety equipment. Outputs of this device are
not supervised, and cannot be directly connected to notification or releasing-type appliances in a UL listed
system.
In a ULlisted system, the 16 Channel I/O Panel Module:
lmust be wired in conduit (or equivalently protected against mechanical injury) and within 20 feet of equipment being
interfaced.
lmust not be used to control the release of extinguishants.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 15
Installation

Testing the Installation
1. Confirm communication from the panel via the LEDstatus indicators.LED indicators provide diagnostic information
to identify communication.
2. Resolve any troubles related to the new connections.
3. Activate each circuit and verify that all connected devices function properly.
LED Label Name Color Description
LED 1 Heartbeat Red Flashes every 2 seconds when theboard is operating.
LED 2 Rx Comms Green Flashes every 2 - 3 seconds when the module is receiving data from the
panel.
LED 3 Tx Comms Green Flashes every 2 - 3 seconds when the module is transmitting data to the
panel.
LED 4 Trouble Yellow Flashes every 2 seconds when one or more outputs have a trouble
condition.
LED 5 Input Active LED Red Flashes every 2 seconds when one or more inputs are active.
LED 6 Output Active LED Red Flashes every 2 seconds when one or more outputs are active (low).
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 16
Installation

CONFIGURATION
The 16 Channel I/OPanel Module can be configured via LE2 or the Panel GUI. Set each channel to be an input
or output.
NOTE The panel module must be added to the configuration via Loop Explorer 2 or an Autolearn on the panel.
Panel Module Properties
Set each of the 16 channels to be either an input or an output for each 16 Channel I/OPanel Module installed in
the FireNET L@titude Fire Alarm ControlPanel.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 17
Configuration

Channel Properties
For channels set as Outputs
1. Select the desired Output Options. This selection will activate the circuit when the selected event(s) occur.
2. Set whether the output will be Silenceable. Each channel is configurable in reaction to the Alarm Silence button on
the front panel. Check the box if the channel should return to normal standby when Alarm Silence is active. If this
box is checked, the Second Delay field is displayed.
3. Each output circuit is normally floating, but is pulled-low (to 0V) when activated. Selecting Output Invert will set the
circuit to normally be pulled-low (to 0V), but become floating when activated.
4. Ignore Global Delays. This setting controls the delay of the activation of the output. If unchecked, it will activate
based on the Global Delay settings in the Panel Settings. If checked, it will activate based on the settings in the
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 18
Configuration

First Delay and Second Delay fields. Second Delay is only visible if the output is silenceable. For ULcompliance,
both delays must be set to 0.
NOTE If checked,
- the initial activation of the output will be delayed based on the settings in the First Delay field.
- if the output is silenceable, subsequent re-sounding of the output will be delayed based on the settings in the Second
Delay field.
5. Enter a Duration to select how long an output will be active. If set to 0, it will remain active until the system is reset.
For ULcompliance, this field must be set to 0.
6. Set the Location Text, up to 80 characters.
7. Use the Map to Zone field to set the zone number for the circuit. Allowable values are 0-2000.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 19
Configuration

For channels set as Inputs
1. Choose an Input Action.
2. Input Action Message is automatically set based on the selected Input Action. If desired, a custom Input Action
Message can be entered.
3. Check the Output Delay Bypass box if activation of this circuit should immediately activate its associated outputs,
even if those outputs have configured delays. For ULcompliance, this field must be checked.
4. Set the Input Delay in seconds, up to 180 seconds. Input activation will prevent the panel's response for specified
time period when the input is activated. No activation will occur if the input state is reset to normal before time period
expires. For ULcompliance, this field must be set to 0.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 |March 2021 |MAN-1420HA
Page 20
Configuration
Table of contents
Other Hochiki Control Unit manuals
Popular Control Unit manuals by other brands

Visual Productions
Visual Productions IoCore2 user manual

Honeywell
Honeywell 7800 SERIES Installation

Apollo
Apollo ApolloPress APL77V10711 Installation, operation, maintenance guide

NI
NI GPIB-410 user manual

Thermasol
Thermasol WHSP10S installation manual

Comunello
Comunello CU-24V-2M Installation and user manual