Model F1 Res 44 Sprinklers should be inspected quarterly and the sprinkler system maintained in
accordance with NFPA 25, 13, 13D and 13R. Do not clean sprinklers with soap and water, ammonia or any
other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover
plate assembly which has been painted (other than factory applied) or damaged in any way.
A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated
sprinklers.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to
minimize the potential for damage to sprinklers that would cause improper operation or non-operation.
Model F1 Res 44Horizontal SidewallSprinkler
Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential horizontal
sidewall sprinklers engineered to provide a minimum design density (See above) over the listed coverage
area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable
installation standard. Where horizontal sidewall residential sprinklers are installed under sloped ceilings
having a pitch of up to [1:3] [2:3], the sprinklers shall be listed for such use. Sprinkler frame and deflector
shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-
coated Belleville spring washer and top-loaded extruded cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of 68 C or 79 C. Sprinklers shall have a nominal K-factor of 63.
Standard finish: Bronze Chrome-plated or White Polyester.
Residential horizontal sidewall sprinklers shall be ReliableModel F1 Res 44, SIN R3531(Bulletin 135).
Model F1 Res 44 Recessed Horizontal Sidewall Sprinkler
Use description for the Model F1 Res 44 horizontal sidewall sprinkler with the following modifications:
Replace “horizontal sidewall sprinkler” with “recessed horizontal sprinkler.” Add: Recessed escutcheon
assembly shall be a steel, two-piece escutcheon with 13mm adjustment (Model F2). Standard finish shall be
[brass][bright chrome] [white painted]
Residential recessed horizontal sidewall sprinklers shall be Reliable Model F1 Res 44/F2, SIN
R3531 (Bulletin 135)..