Homesafe F1 Res 44 User manual

F1 Res 44 Horizontal Side Wall
Details below are taken from data supplied by the head manufacturer.
Up to 4.9 x 6.1 metres coverage from 1 head
Temperature Range 68°C or 79°C Escutcheon F2
Installation Data
RRP
Thread K Maximum Maximum
40.00
$
Size Factor Pressure Ambient
Plus GST
mm
kPa
Temperature
38°C
66°C
Minimum Spacing of 4.3 Metres
Ceiling to
LPM
Pressure
Deflector
kPa
45.4 52
53 71
60.6 92
68.1 116
72 129
87.1 189
53 71
60.6 92
64.4 104
75.7 143
87.1 189
Features
1 Residential
2 Quick Response
3 3mm Glass bulb
4 Pressure Rated 1200 kPa
5 Tested to 3445 kPa
6 Tread Size 1/2" NPT
7 Minimum Density of 2.03 LPM per square metre
Listings & Approval
1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus)
2. NYC MEA 258-93-E
4.9 x 6.1
101 - 152mm
152 - 305mm
4.9 x 5.5
4.9 x 5.5
3.6 x 3.6
4.3 x 4.3
4.9 x 4.9
4.3 x 4.3
4.9 x 4.9
5.5 x 5.5
4.9 x 6.1
Sprinkler Length
62 mm
Max Spacing
15mm 63 1200
3.6 x 3.6
Product Description
The F1 Res Horizontal Sidewall sprinklers (Figs.1 and 2) are equally attractive when above ceiling piping
cannot is used.
The 3mm glass-bulb pendent sprinklers, with a K-Factor of 63, permit the efficient use of residential
water supplies for sprinkler coverage in residential fire protection design.
The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the
sensitive fire protection application needs of the latest residential market standards
(UL 1626 Standard effective 7/12/02).
Upon fire conditions, rising heat causes a sprinkler’s heat-sensitive glass-bulb to shatter, releasing the
waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire.
Call 07 824 8005 To Order

Figure 1 Figure 2
Application and Installation
Model F1 Res Sprinklers are used for Residential Fire Protection according to UL 1626 Standard*. Be sure
that orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest
published standards of the authority having jurisdiction.
.
Models F1 Res sprinklers are to be installed as shown. Model F1 and F2 Escutcheons, illustrated
herewith, are the only recessed escutcheons to be used with Model F1 Res sprinklers. Use of any other
recessed escutcheon will void all approvals and warranties. For installing Models F1 Res Recessed
SWC sprinklers use only the Model GFR1 sprinkler wrench.
Use of wrenches other than those specified may damage these sprinklers. Install F1 Res 44 HSW
with a ceiling to deflector distance of 102 - 305mm . Flow arrow on deflector must point away from near wall
and “Top” marking must face ceiling.
Note: DH56 and DH56 Recessed Sprinklers have orange bulb protectors to minimize bulb damage during
shipping, handling, and installation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER
SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION.
Removal of the protectors before this time may leave the bulb vulnerable to damage. Wrenches are
designed to install sprinklers when covers are in place.
REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THEPROTECTORS
Note: A leak tight ½" NPT (R1/2) sprinkler joint can be obtained with a torque of 8-18 ft-lbs (10.8-24.4
N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or
impairment of the sprinklers
Call 07 824 8005 To Order

Maintenance
Model F1 Res 44 Sprinklers should be inspected quarterly and the sprinkler system maintained in
accordance with NFPA 25, 13, 13D and 13R. Do not clean sprinklers with soap and water, ammonia or any
other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover
plate assembly which has been painted (other than factory applied) or damaged in any way.
A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated
sprinklers.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to
minimize the potential for damage to sprinklers that would cause improper operation or non-operation.
Model F1 Res 44Horizontal SidewallSprinkler
Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential horizontal
sidewall sprinklers engineered to provide a minimum design density (See above) over the listed coverage
area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable
installation standard. Where horizontal sidewall residential sprinklers are installed under sloped ceilings
having a pitch of up to [1:3] [2:3], the sprinklers shall be listed for such use. Sprinkler frame and deflector
shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon-
coated Belleville spring washer and top-loaded extruded cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of 68 C or 79 C. Sprinklers shall have a nominal K-factor of 63.
Standard finish: Bronze Chrome-plated or White Polyester.
Residential horizontal sidewall sprinklers shall be ReliableModel F1 Res 44, SIN R3531(Bulletin 135).
Model F1 Res 44 Recessed Horizontal Sidewall Sprinkler
Use description for the Model F1 Res 44 horizontal sidewall sprinkler with the following modifications:
Replace “horizontal sidewall sprinkler” with “recessed horizontal sprinkler.” Add: Recessed escutcheon
assembly shall be a steel, two-piece escutcheon with 13mm adjustment (Model F2). Standard finish shall be
[brass][bright chrome] [white painted]
Residential recessed horizontal sidewall sprinklers shall be Reliable Model F1 Res 44/F2, SIN
R3531 (Bulletin 135)..
Call 07 824 8005 To Order
Table of contents
Popular Irrigation System manuals by other brands

Task Force Tips
Task Force Tips MASTERSTREAM 1000 Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Tyco
Tyco LFII Series Design guide

Micro Rain
Micro Rain MR 32 INSTRUCTION MANUAL FOR OPERATION AND MAINTENANCE

Netafim
Netafim D-Net 8550 user manual

Victaulic
Victaulic VicFlex V32 Assembly instructions

Reliable
Reliable G VELO Pendent Bulletin