General
Description
The TYCO Model ESFR-17 Upright
Sprinklers are “Early Suppression,
Fast Response Sprinklers” having a
nominal K-factor of 16.8 (Figure 1).
They are suppression mode sprinklers
that are especially advantageous as a
means of eliminating in-rack sprinklers
when protecting high-piled storage.
Model ESFR-17 Sprinklers are
primarily used for ceiling-only sprin-
kler protection of (but not limited to)
the following storage applications:
• Most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics.
• Cartoned, expanded plastics.
• Some storage arrangements of rub-
ber tires and roll paper.
For more specic criteria, refer to
Table 1 in this data sheet as well as
the applicable design standard.
The Model ESFR-17 Upright Sprin-
klers provide the system designer with
an upright option to the traditional
pendent ESFR Sprinklers. With a K-
factor of 16.8, Model ESFR-17 Sprin-
klers provide system designers with
hydraulic and sprinkler placement
options not presently available to
traditional ESFR Sprinklers having
a K-factor of 14.0. In particular, the
Model ESFR-17 Upright Sprinklers are
designed to operate at substantially
lower-end head pressures compared
to ESFR Sprinklers with 14.0 K-fac-
tors. This feature offers exibility when
sizing system piping and positioning
the system piping with respect to the
ceiling.
Applications for the TYCO ESFR
Sprinklers are expanding beyond cur-
rently recognized installation stan-
dards. For information on research re
tests that may be acceptable to an au-
thority having jurisdiction, contact the
Technical Services department.
NOTICE
The Model ESFR-17 Upright Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the ap-
plicable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction (e.g., FM Global). Failure to
do so may impair the performance of
these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
In all cases, the appropriate NFPA or
FM installation standard must be ref-
erenced to ensure applicability and
to obtain complete installation guide-
lines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.
Sprinkler
Identification
Number (SIN)
TY7126
Technical
Data
Approvals
FM Approved
CE Certied Certicate of Conformity
1725-CPD-H0012
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 inch NPT
ISO 7-R3/4
Discharge Coefficient
K = 16.8 GPM/psi1/2
(241,9 LPM/bar1/2)
Temperature Ratings
165°F (74°C)
214°F (101°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Deector. . . . . . . . . . . . . . . . . . . . . Copper
Compression Screw. . . . . . . . . . .Stainless
Steel
Hook. . . . . . . . . . . . . . . . . . . . . . . . . Monel
Strut . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Link Assembly . . . . . . . . . . . Solder, Nickel
Button. . . . . . . . . . . . . . . . . . . . . . . . Brass
Sealing Assembly. . . . . . . . . . . . Beryllium
Nickel w/TEFLON
Ejection Spring. . . . . . . . . . . . . . . . Inconel
Deector Nut . . . . . . . . . . . . . . . . . . Brass
Page 1 of 4 SEPTEMBER 2012 TFP316
Model ESFR-17
Early Suppression, Fast Response Upright Sprinklers
16.8 K-factor
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cau-
tions with respect to handling
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can
permanently damage a sprin-
kler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.