Honeywell Home PROSiXSMOKEV Assembly instructions

PROSiXSMOKEV
Wireless Smoke/Heat Detector
Installation and Setup Guide
This is a multi-criteria wireless smoke
detector which employs advanced levels of
detection and discrimination. This reduces
common cooking nuisance alarms and
allows faster detection to different types of
fire conditions. It is intended for use with
Controls that support PROSiX™ series
devices.
To remove the mounting bracket, turn
the top of the detector 15 degrees
counterclockwise and separate the
mounting bracket and top cover.
PROSiXSMOKEV
Open
ENROLLMENT
Initiate enrollment on the Control Panel. When prompted, activate
the device by pulling the battery tab or, if already powered, press the
Test button to enroll. It enrolls into 2 zones: smoke detection into
one zone and heat detection into a second zone.
If the detector is not successfully enrolled during the enrollment
period, the LED turns off and the device powers down. Activate the
tamper or press the Test Button to restart the enrollment process.
NOTES: Enrollment time varies depending on the signal strength
between the device and the Control Panel.Once enrolled in a
system, the detector cannot be used with another system until it is
removed from the current one. See the Control Panel’s instructions
for details.
Enroll
PROGRAM
Consult the Control Panel’s instructions to program the device in the system. This detector reports the following signals to the
Control Panel:
•Smoke and Heat detection
-Smoke Alarm when smoke is detected
-Heat Alarm when temperature of 135° F (57° C) or greater
-Rate-of-Rise Alarm when temperature is >104° F (40° C) @ 15° F/minute (8.33° C/minute).
•Maintenance: Contaminated chamber that requires cleaning.
•End-of-Life
•Base Tamper: It sends a tamper signal to the control when the smoke head is removed from its base.
•Supervision: 200 second check-in compatible.
•Signal and battery Strength: Signal and battery strength information are sent with every communication to the panel.
NOTE: If programmed in the Control to operate in One-Go-All-Go mode, all smoke detectors programmed as One-Go-All-Go in the
system will sound on alarm.
TAMPER
When the detector is removed from its base, it sends a tamper signal to the Control. OPTIONAL: The detector can be made
tamper-proof to prevent unauthorized removal from its base. Break off the small pillar on the base as shown. This causes the
detector to latch to the base. From this point on, to remove the detector from its base, you must use a small screwdriver to release
the catch (push the catch towards the base) and twist the detector counter-clockwise. A screw can be added to prevent removal
from the base.
MOUNT
Refer to the Limitations of Fire Alarm Systems (P/N 800-15144) for
detailed information on detector spacing, placement zoning and
special applications. Copies of this document are available on
www.resideo.com.
NOTE: Before mounting the detector permanently, conduct a Walk
test (see control’s instructions) to verify adequate signal strength
and adjust the device location and orientation as necessary.
The detector can be mounted on the ceiling or on the wall (if local
ordinances permit). Select a location and mount using the included
mounting hardware.
Mount

Testing
The detector should be tested immediately after installation and at least once a year.
Recommended: Notify the Central Station that the smoke detector is undergoing tests, so they do not dispatch authorities.
After enrolling, verify adequate signal strength by conducting a sensor test (see the Control Panel’s instructions) with the device in its
intended mounting location. Adjust the device location and orientation as necessary.
Tests and testing methods:
There is no specific Test Mode that needs to be initiated to test smoke, heat, or Rate-of-Rise. These can be applied to the detector
at any time as a test.
•Test Button – When the Test Button is held down, the unit initiates a test on the smoke sensor, chamber, heat sensor, End-of-
Life, and battery. If all tests pass, it sounds a normal alarm and sends alarm signal to the Control. However, if one of these
tests fails, it sends a trouble signal to the Control and provides fail status on the yellow led and sounder. The Test Button is also
used to silence or Hush the detector. To Hush the detector, press and release the large Test Button. Only the detector that
initiated the alarm can be Hushed by the Test Button. Other detectors that sound with One-Go-All-Go must be silenced by the
Control by entering a disarm command. Depending on how much smoke is still in the chamber determines if the Hush feature
silences the detector and make it send an Alarm restore to the Control. If there is too much smoke still in the chamber, it does
not Hush nor send a restore to the Control Panel. When Hush is successful, the sounder comes back on after 10 minutes and a
restore signal is still not sent provided there is still enough smoke in the chamber to be considered an alarm. Once the smoke
level is below threshold in the chamber, Hush causes the sounder to remain off and the restore signal is sent. Entering a disarm
command to the Control also silences all detectors that are sounding without needing to Hush any smoke detector. See the
LED and Sounder Indication Chart on the next page.
•Smoke Entry Test (canned smoke*) – Can be done at any time. Once the chamber is clear, the sounder will stop, and it will
send a restore signal to the Control Panel.
•Direct Heat Test (hair dryer 12” or further from the detector)
•135° F fixed Heat Detection
•Rate-of-Rise >104° F (40° C) @ 15° F/minute (8.33° C/minute).
CAUTION: The detector alarms when 135° F is exceeded and restore when it falls below 135° F. However, the thermistor is
damaged at 195° F and the integrity of the detector itself is compromised and needs to be replaced.

LEDS AND SOUNDER
The PROSIXSMOKEV has one green LED and a separate bi-color (red and yellow) LED with an
85dB sounder.Refer to the following table below for operation of these features.
LED AND SOUNDER INDICATION CHART
Normal Operation
Action
Green LED
Red LED
Yellow LED
Sounder
Reaction
Power Up
Pull Battery Tab
1 Flash 1 Flash 1 Flash Off
Enrollment into System Program into
Control
Rapid flashing up
to 30 seconds, Then
on 3 seconds
Off Off
Single Chirp Install into System
Delete from System
Delete from
Control
Rapid flashing for 5
seconds
Off Off Off
Uninstall from system
Processing Control
Queries
Slow flashing Off Off Off
Tamper
Remove from base
Slow flash for
10 minutes
Off Off Off
Standby - Normal
1 flash every
60 seconds
Off Off Off
Sensing Smoke / Heat
Smoke / Fire
Condition
Off
Rapid
flashing
Off Temporal 3 Evacuate Premises
One-Go-All-Go
Fire / CO Alarm
from Control
Off Off Off
Fire Temporal 3 /
CO Temporal 4
Evacuate Premises
Alarm Hush
Action
Green LED
Red LED
Yellow LED
Sounder
Reaction
Silence Sounding Alarm
Press & Release
Button Off
1 flash every
8 seconds Off Off for 10 mins
Silence Low Battery
Press & Release
Button Off Off Off for 12 hours
Beep once per
hour for 12 hours Replace both batteries
Silence Faulty Sensor
(only possible once)
Press & Release
Button Off Off
2 flashes every
48 seconds Off for 12 hours Replace unit
Silence End of Life (up to
30 days)
Press & Release
Button Off Off Off for 72 hours Off for 72 hours Replace unit
Self-Diagnostics
Action
Green LED
Red LED
Yellow LED
Sounder
Reaction
Low Battery
Automatic every
16 minutes
Off Off
1 flash every
48 seconds
1 beep with 1
flash Replace both batteries
Faulty Smoke Sensor
Automatic every
16 seconds
Off Off
2 flashes every
48 seconds
2 beeps with 2
flashes
Replace unit
Faulty Heat Sensor
Automatic every
second
Off Off
2 flashes every
48 seconds
2 beeps with 2
flashes Replace unit
End of Life
Automatic every 4
hours
Off Off
3 flashes every
48 seconds
3 beeps with 3
flashes
Replace unit
Maintenance
Automatic every
16 seconds
Off Off
4 flashes every
48 seconds Off
Clean unit; see Cleaning
section
Test Button
Action
Green LED
Red LED
Yellow LED
Sounder
Reaction
Detector Status Good –
Normal Alarm
Press & Hold
Button
Off
Rapid
flashing
Off
Tempo
ral 3 Release button
Low Battery
Press & Hold
Button Off Off
1 flash then
rapid flashing
1 beep then
Temporal 3 Replace both batteries
Faulty Sensor
Press & Hold
Button
Off Off
2 flashes then
rapid flashing
2 beeps only Replace unit
End of Life
Press & Hold
Button Off Off
3 flashes then
rapid flashing
3 beeps then
Temporal 3 Replace unit
Maintenance
Press & Hold
Button
Off Off
4 flashes then
rapid flashing
4 beeps then
Temporal 3
Clean unit; see Cleaning
section
Alarm Memory
Action
Green LED
Red LED
Yellow LED
Sounder
Reaction
24 Hour Memory After Alarm Off
2 flashes every
48 seconds for
24 hours Off Off Press & Hold Button for
Long Term Memory
Long Term Memory
Press & Hold
Button
Off
Rapid
flashing
Off Rapid chirping
Memory is reset after
releasing the test button
CLEANING
Recommended: To prevent unwanted alarms, notify the Central Station
that the smoke detector system is undergoing maintenance before
cleaning the detector.
To clean the detector, carefully vacuum the side vents all the way around,
then, wipe them with a clean damp cloth and dry thoroughly.
Do NOT attempt to take the detector apart. This could result in damaging
the unit.
Cleaning
BATTERY REPLACEMENT
•Twist the front cover counterclockwise
15 degrees and separate it from the mounting
bracket.
•Remove both batteries and wait 10 seconds,
then insert two new recommended batteries:
-Panasonic CR123A
-Resideo 466
NOTE: Do not mix old and new batteries,
battery types or manufacturers.
•Reattach to the detector to the mounting plate.
Replace Batteries
BATTERY CAUTION: Risk of fire, explosion and burns. Do not recharge, disassemble,
heat above 212° F (100° C) or incinerate. Dispose of used batteries properly. Keep away
from children.
PROSiX/SiX™ Series transmitters draw quick bursts of current during transmission, then sit idle with very nominal current draw. Most batteries are
not designed for this type of use, therefore, only batteries listed as compatible should be used if the expected battery life is to be attained. Each
transmitter’s Installation Instructions has listed compatible battery manufacturers and their part numbers. When other non-approved batteries are
used, the quick bursts of current draw kill the battery cells prematurely causing them to go low in a matter of months and can also cause
unpredictable results. Other low-quality batteries have not been UL tested and pose a safety hazard if used.

FEDERAL COMMUNICATIONS COMMISSION (FCC) & INDUSTRY CANADA (IC) STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or
modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested and found to comply with the limits for a Class B digital device, as defined by FCC Rules Part 15.105. The Class B Digital Device
statement can be viewed at:
https://customer.resideo.com/en-US/support/residential/codes-and-standards/FCC15105/Pages/default.aspx
FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules, and Industry Canada’s license-exempt RSSs. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC et exempt de licence RSS d’Industrie Canada. Son fonctionnement est soumis aux conditions suivantes:
(1) Cet appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris les interférences causant une réception
indésirable.
RF EXPOSURE WARNING – The antenna(s) used for this device must be installed to provide a separation distance of at least 7.8 inches (20 cm) from all persons and
must not be co-located or operating in conjunction with any other antenna or transmitter except in accordance with FCC multi-transmitter product procedures.
Mise en Garde Exposition aux Frequences Radio: L'antenne (s) utilisée pour cet émetteur doit être installée à une distance de séparation d'au moins 7,8 pouces (20
cm) de toutes les personnes.
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED, FOR DETAILS REGARDING
LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
Responsible Party / Issuer of Supplier’s Declaration of Conformity: Ademco Inc., a subsidiary of Resideo Technologies, Inc., 2 Corporate Center
Drive., Melville, NY 11747, Ph: 516-577-2000
The product should not be disposed of with other household waste. Check for the nearest authorized collection centers or authorized recyclers. The
correct disposal of end-of-life equipment will help prevent potential negative consequences for the environment and human health.
Any attempt to reverse-engineer this device by decoding proprietary protocols, de-compiling firmware, or any similar actions is strictly prohibited.
SUPPORT & WARRANTY INFORMATION
For the latest documentation and support, please go to:
www.resideo.com
For the latest warranty information, please go to:
www.security.honeywellhome.com/warranty
The Honeywell Home Trademark is used under license from Honeywell International Inc.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
2020 Resideo Technologies, Inc.
www.resideo.com
Ê800-25553BbŠ
800-25553B5/19Rev B
SPECIFICATIONS:
Smoke Detection: ..................................................................Photoelectric
Heat Detection: ......................................................................135° F (57° C) or greater +/- 5°F
Rate of Rise: ...........................................................................>104° F (40° C) @ 15° F/minute (8.33° C/minute).
dB Rating:................................................................................>85dBA (Minimum) at 9ft
Batteries: .............................................................................Two 3V Lithium; Panasonic CR123A, Resideo 466
RF Frequency: ........................................................................2.4GHz
Tamper:....................................................................................Base Tamper
Operating Temperature: .......................................................40° to 100° F / 4.4° to 37.7° C
Relative Humidity: ..................................................................15% to 95% max, non-condensing
Maximum Spacing: ........................................................50ft x 50ft (refer to National Fire Alarm Code Standard NFPA 72 for application requirements)
Dimensions: ...........................................................................4.5 in. Diameter x 1.7 in. Thick / 11.9 cm Diameter x 4.5 cm Thick
APPROVAL LISTINGS:
FCC / IC
ETL Listed – Conforms to UL 268 7th Edition
cETL Listed – Certified to UL268 & CAN/ULC S529
Other Standards:State of California requirement – free of substances that may cause cancer. Prop 65 US.
NFPA 72
NOTE: Smoke detectors are not to be used with detector guards unless the combination is evaluated and found suitable for that purpose.
This manual suits for next models
1
Other Honeywell Home Smoke Alarm manuals

Honeywell Home
Honeywell Home PROSiXCOMBO User manual

Honeywell Home
Honeywell Home R200S-1 User manual

Honeywell Home
Honeywell Home R200ST-N1 User manual

Honeywell Home
Honeywell Home resideo DFS8MS User manual

Honeywell Home
Honeywell Home R200H-N1 User manual

Honeywell Home
Honeywell Home R200S-3 User manual

Honeywell Home
Honeywell Home R200S-N1 User manual

Honeywell Home
Honeywell Home DFS8MS User manual

Honeywell Home
Honeywell Home R200S-N3 User manual