  9. Kidde KIR-PHD Assembly instructions

Kidde KIR-PHD Assembly instructions

Other Kidde Smoke Alarm manuals

Kidde TRUSENSE SMOKE 3050-VDS10 User manual

Kidde

Kidde TRUSENSE SMOKE 3050-VDS10 User manual

Kidde PE910 User manual

Kidde

Kidde PE910 User manual

Kidde FIREX KF3 User manual

Kidde

Kidde FIREX KF3 User manual

Kidde P9040 User manual

Kidde

Kidde P9040 User manual

Kidde P3010CU User manual

Kidde

Kidde P3010CU User manual

Kidde 0910UK User manual

Kidde

Kidde 0910UK User manual

Kidde PI2010 User manual

Kidde

Kidde PI2010 User manual

Kidde KN-SMFM-i User manual

Kidde

Kidde KN-SMFM-i User manual

Kidde Signature Series Assembly instructions

Kidde

Kidde Signature Series Assembly instructions

Kidde P9050 User manual

Kidde

Kidde P9050 User manual

Kidde i9010UK User manual

Kidde

Kidde i9010UK User manual

Kidde TRUSENSE COMBO User manual

Kidde

Kidde TRUSENSE COMBO User manual

Kidde P12040 User manual

Kidde

Kidde P12040 User manual

Kidde Stratos-HSSD 2 User manual

Kidde

Kidde Stratos-HSSD 2 User manual

Kidde P3010K-CA User manual

Kidde

Kidde P3010K-CA User manual

Kidde 4899 User manual

Kidde

Kidde 4899 User manual

Kidde PE9 User manual

Kidde

Kidde PE9 User manual

Kidde 10Y29 User manual

Kidde

Kidde 10Y29 User manual

Kidde VM-1 User manual

Kidde

Kidde VM-1 User manual

Kidde FIRE SENTRY 0914 User manual

Kidde

Kidde FIRE SENTRY 0914 User manual

Kidde TRUSENSE SMOKE 3050-VAS10 User manual

Kidde

Kidde TRUSENSE SMOKE 3050-VAS10 User manual

Kidde P4010ACSAQ-WF User manual

Kidde

Kidde P4010ACSAQ-WF User manual

Kidde PI 2000 User manual

Kidde

Kidde PI 2000 User manual

Kidde TRUSENSE SMOKE 2050-DS10 User manual

Kidde

Kidde TRUSENSE SMOKE 2050-DS10 User manual

Popular Smoke Alarm manuals by other brands

Dyna-Glo DGY784BDP installation instructions

Dyna-Glo

Dyna-Glo DGY784BDP installation instructions

NOXE LUMENS Installation and user guide

NOXE

NOXE LUMENS Installation and user guide

Develco SMAZB-141 installation manual

Develco

Develco SMAZB-141 installation manual

Honeywell 5800COMBO Installation and setup guide

Honeywell

Honeywell 5800COMBO Installation and setup guide

Gentex 7109CS installation instructions

Gentex

Gentex 7109CS installation instructions

FireAngel Thermoptek ST-622 user manual

FireAngel

FireAngel Thermoptek ST-622 user manual

teko Astra-42A user guide

teko

teko Astra-42A user guide

ELRO FS8110 instruction manual

ELRO

ELRO FS8110 instruction manual

Heiman SMOKI NS-626PHS user manual

Heiman

Heiman SMOKI NS-626PHS user manual

Siemens PE-11C installation instructions

Siemens

Siemens PE-11C installation instructions

Resolution Products RE612 CryptiX quick start guide

Resolution Products

Resolution Products RE612 CryptiX quick start guide

First Alert PC900V user manual

First Alert

First Alert PC900V user manual

Eminent EM6590 E-Domotica user manual

Eminent

Eminent EM6590 E-Domotica user manual

Ei Electronics Ei Ei168RC user manual

Ei Electronics

Ei Electronics Ei Ei168RC user manual

Carrier Kidde Quell Q301 user manual

Carrier

Carrier Kidde Quell Q301 user manual

Family Gard FG225 user manual

Family Gard

Family Gard FG225 user manual

Regin SDD-S65 instruction manual

Regin

Regin SDD-S65 instruction manual

LST ÜMS-55000-841 Specification sheet

LST

LST ÜMS-55000-841 Specification sheet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

© 2017 United Technologies Corporation 1 / 2 P/N 3102533-EN • REV 001 • ISS 15AUG17
KIR-PHD Intelligent
Multisensor Photo-Heat
Detector Installation Sheet
Description
The model KIR-PHD Intelligent Multisensor Photo-Heat Detector is an
intelligent device that contains a photoelectric smoke sensor and a
rate-of-rise heat sensor with a fixed temperature setting. The detector
analyzes the data from both sensing devices and determines whether
an alarm should be initiated. Can be operated as a single detector
using smoke or heat to initiate an alarm.
LED indicator. The LED indicator (see Figure 2) displays the following
states:
•Normal: Green LED indicator flashes, no action.
•Alarm/active: Red LED indicator flashes, evacuate the area.
Installation
Notes
•This detector does not operate without electrical power. As fires
frequently cause power interruption, discuss further safeguards
with the local fire protection specialist.
•This detector does not sense fires in areas where smoke or heat
cannot reach the detector. Smoke or heat from fires in walls, roofs,
or on the opposite side of closed doors may not reach the detector.
•Photoelectric detectors have a wide range of sensing capabilities,
and are best suited for detecting slow, smoldering fires. The heat
sensor in this device provides a source of supplemental
information. The heat sensor by itself does not provide life safety
protection.
•To ensure proper operation, store the detector within the
recommended ranges. Allow the detector to stabilize to room
temperature before applying power.
•The dust cover (supplied) must remain on the detector during
installation and be removed prior to commissioning and service.
The dust cover is not a substitute for removing the detector during
new construction or heavy remodeling.
•Do not use smoke detectors with detector guards unless the
combination has been evaluated and found suitable.
•In Canada, install according to the CAN/ULC-S524 Standard for
the Installation of Fire Alarm Systems, the CSA C22.1 Canadian
Electrical Code, and the local authority having jurisdiction.
•Upon completion of the original installation and following any
modifications or additions to the system, perform a calibrated
sensitivity test per NFPA code. The Kidde Intelligent devices can
perform this test at the panel which can then generate a system
sensitivity report.
To install the device:
1. Install and wire the base, as described on the installation sheet
supplied with the base.
2. Set the detector address. Refer to the panel technical reference
manual for a list of valid addresses. Use a screwdriver to adjust
the two rotary switches on the back of the detector.
(See Figure 1) Set the left rotary switch (0 through 12) for the 10s
and 100s digit and the right rotary switch for the 0 through 9 digit.
3. Attach the detector to the base by rotating the detector clockwise
until it snaps into the locked position.
Figure 1: Setting detector address (address 52 shown)
(1) Insert a screwdriver here to set the address
Figure 2: KIR-PHD features
2
(1) Self-locking tab
(2) LED indicator
Testing
Before testing, notify the proper authorities that the fire alarm system is
undergoing maintenance and will be temporarily out of service.
Test each sensor in the detector.
Caution: Heat damage. Excessive heat may damage the detector
outer cover. Do not apply excessive heat when using a hair dryer.
When using a Testifire detector tester, you must install a Testifire
Adapter Assembly.
Make sure the Testifire Adapter Assembly (model
SIGA2-TSTSPACER) is installed in the Testifire detector tester before
testing. Refer to the Testifire Adapter Assembly Installation Sheet (P/N
3101942-ML) for further details.
0
23456
8
9
0
1
2
3
456 7 8901
11
11
2
TENS ONES
(1)
2 / 2 P/N 3102533-EN • REV 001 • ISS 15AUG17
To perform an initial installation test:
1. Remove the detector from its base and verify that the proper
detector address, trouble signals, and messages are reported.
2. For KIR-PHD detectors placed in the air ducts, verify that the
airflow is within specifications. See “Specifications” below.
3. If wired for Class A operation, verify that the detector continues to
operate first with SLC_IN disconnected, reconnect SLC_IN and
then with SLC_OUT disconnected. (Refer to the installation sheet
for the base.)
4. Place a momentary ground fault on the SLC circuit to verify
operation of the ground fault detection circuitry.
5. Run a system detector sensitivity report on all detectors and verify
that readings fall within acceptable limits.
6. Perform a sensor function test, as described below.
To perform sensor function tests:
1. If desired, use the fire alarm control panel to put the detector or
zone into a service group for testing. (Refer to the panel technical
reference manual for instructions.)
2. Activate the smoke sensor using No Climb Products model Smoke
Centurion/M8, FireTech Smoke or Smoke Sabre smoke aerosol
spray, a smoke generator, or the Testifire detector tester per the
manufacturer’s instructions.
3. Activate the heat sensor using a hair dryer (maintaining a distance
of three inches) or using a Testifire detector tester per the
manufacturer’s instructions.
Maintenance
To ensure proper operation, plan maintenance (regular or selected) of
the detector in accordance with the AHJ and all applicable governing
laws, codes, or standards. Refer to CAN/ULC-S536 Standard for the
Inspection and Testing of Fire Alarm Systems and NFPA 72 National
Fire Alarm and Signaling Code.
Refer to Application Bulletin P/N 3102483-EN for additional information
and cleaning instructions.
Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Normal operating current
Alarm
51 µA
68 µA
Vibration level
10 to 35 Hz, with an amplitude of
0.01 in.
Rate-of-rise
15°F/min (9°C/min)
Air velocity [1]
0 to 4,000 ft./min (0 to 20.32 m/s)
Maximum spacing
for Heat Detectors
50 ft. (15.2 m) centers
Wall mount distance from
ceiling
12 in. (305 mm) max.
Compatible bases
Standard
Relay
Isolator
Audible
KI-SB, KI-SB4
KI-RB, KI-RB4
KI-IB, KI-IB4
KI-ABST, KI-ABDT, KI-ABLT
Compatible detector testers [2]
Testifire 1000, Testifire 2000
Operating environment
Temperature
Relative humidity
32 to 100°F (0 to 38°C)
0 to 93% noncondensing
Storage temperature
−4 to 140°F (−20 to 60°C)
Environmental compensation
Automatic
[1] For duct installation, use a K-DMP duct detector mounting plate and
install per P/N 3102482-EN.
[2] Requires the SIGA2-TSTSPACER Testifire adapter assembly.
Regulatory information
North American
standards
CAN/ULC-S529, CAN/ULC-S530, UL 268,
UL 268A, UL 521
UL/ULC smoke
sensitivity range
0.53 to 3.94 %/ft. (1.7 to 12.35 %/m) obscuration
UL/ULC fixed-
temperature alarm
rating
135°F (57.2°C)
UL/ULC Actual
alarm point
129 to 141°F (53.9 to 60.6°C)
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Industry Canada
compliance
This Class A digital apparatus complies with
Canadian ICES-003.
Contact information
For contact information, see www.kiddelifesafety.com.