
บริษัท เอดีดี เฟอร์เนส จํากัด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวีวัฒนา กรุงเทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์: 02-888-3258
SPECIFICATIONS • INSTALLATION
4. For gases with specific gravities other than 0.64,
multiply the burner cfh by the proper conversion factor:
5. Use the corrected capacity in cf/h when determining
the gas valve size in Fig.1.
6. Determine the maximum pressure drop across the
valve and draw a horizontal line at this pressure inFig. 1.
7. Draw a vertical line in Fig. 1 at the capacity (cf/h)
previouslydetermined.Use the corrected capacityfora gas
with a specific gravity other than0.64.
8. Use the valve sizeat the intersectionof the horizontal
and vertical lines. If the intersection is between valve sizes,
use the next higher size to the right.
TO SIZE TWO IDENTICAL VALVES PIPED IN
SERIES
1. Find the cf/h for the type of gas used.
2. Consider both valves as one unit. Determine the total
maximum pressure drop across the unit.
3. Findthepressuredropacrossthefirstvalvebyassum-
ing it to be 45 percent of the total pressure drop.
4. Find the valve size from Fig.1.
5. The second valve will be the same size as the first
valve.
Installation
IMPORTANT: The V5055 Valve is designed to provide
control of gaseous fuel (natural and LP gas) flow in
applications in which there is minimal exposure to
water.V5055Valvesusedinmaritime,beverage,food
processing, outdoor and other installations in which
occasional exposure to water is experienced may be
subject to valve stem and spring corrosion. The pres-
ence of corrosion decreases the operating life of the
valve. V5055 Valves used in such installations should
be inspected at least annually and should have the
valve bonnets replaced if corrosion isnoted.
A V4055ValveActuator with a NEMA4 rating isalso
recommended for such installations. The water-tight
designof the NEMA 4 rated V4055 Actuator prevents
water from entering the V4055 valve stem and spring
chamber through the actuator. Under certain condi-
tions, some water may be retained by the external
upperportionof the valve body. The retained wateris
effectively excluded from the valve stem and spring
chamberby afunctionalsealthatisincorporatedinto
the NEMA 4 ratedactuator.
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced, flame safe-
guard control technician.
4. After installation is complete, check out product
operations as provided in these instructions.
CAUTION
1. Turnoff gas supplybefore starting installation.
2. Disconnect power supply for valve actuator
before beginning installation to prevent electri-
cal shock and equipmentdamage.
3. Besurethevalveisinstalledsothearrowonthe
valve points in the direction of gas flow. (Gas
pressure helps to close thevalve.)
LOCATION
Installthevalveinthegassupplylinedownstreamfrom
the pressure regulator. The valve and actuator may be
mountedinanypositionthatallowssufficientclearancefor
installation and for repair or replacement.
1. The valve position indicators should beeasily visible
with the valve and actuator in the final position.
2. Thefinalpositionofthevalveandactuatormustallow
for damper linkage, ifused.
IMPORTANT: Allow room for turning the valve body
(actuator not attached) onto the gas piping. Swing
dimensions,measuredfromthecenterofthepipeare:
3/4 through 1-1/2 in. valves: 4 in. (101.6 mm).
2 through 3 in. valves: 5 in. (127.0 mm).
4 in. valves: 7 in. (177.8 mm).
MOUNTING (Figs. 4 through 6)
WARNING
If flow is not in the direction of the arrow on the
valve body, the valve may not shut off.