TROUBLESHOOTING GUIDE
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Symptom Possible Cause Action
Display does not
turn on. Thermostat is not powered. Check for 24 Vac between C and R terminals; if missing 24 Vac:
— Check if the circuit breaker is tripped; if so, reset the circuit
breaker.
— Check if the system fuse is blown; if so, replace the fuse.
— Check if the power switch on the HVAC equipment is in the Off
position; if so, set to the On position.
— Check wiring between the thermostat and HVAC equipment;
replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Thermostat microprocessor
is locked up. Remove the thermostat from the wallplate for two minutes. After
two minutes, replace the thermostat on the wallplate.
Temperature
display is incorrect. Room temperature display
has been reconfigured. Enter Installer Setup mode number 37 and reconfigure the display.
Thermostat is configured for
°F or °C display. Enter Installer Setup mode number 14 and reconfigure the display.
Bad thermostat location. Relocate the thermostat.
Temperature
settings will not
change. (Example:
The upper or lower
temperature limits were
reached.
Check the temperature setpoints:
• Heating limits are 40°F to 90°F (4.5°C to 32°C).
• Cooling limits are 45°F to 99°F (7°C to 37°C).
Cannot set the
heating higher or
the cooling lower.)
The setpoint temperature
range stops were
configured.
Check Installer Setup mode numbers 34 and 35 and reconfigure
the setpoint stops.
Heating does not
turn on. No power to the thermostat. Check for 24 Vac between C and R terminals; if missing 24 Vac:
— Check if the circuit breaker is tripped; if so, reset the circuit
breaker.
— Check if the system fuse is blown; if so, replace the fuse.
— Check if the system switch at the equipment is in the Off
position; if so, set to the On position.
— Check wiring between thermostat and HVAC equipment;
replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
— Check connection to D terminal.
Heating does not
turn on. Thermostat minimum off
time is activated. Wait up to five minutes for the system to respond.
System selection is not set
to Heat. Set system selection to Heat.
Cooling does not
turn on. No power to the thermostat. Check for 24 Vac between C and R terminals; if missing 24 Vac:
— Check if the circuit breaker is tripped; if so, reset the circuit
breaker.
— Check if the system fuse is blown; if so, replace the fuse.
— Check if the system switch at the equipment is in the Off
position; if so, set to the On position.
— Check wiring between thermostat and HVAC equipment;
replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
— Check connection to D terminal.
Thermostat minimum off
time is activated. • Wait up to five minutes for the system to respond.
• Enter Installer Setup mode number 33. Reconfigure minimum
off time (if required).
System selection is not set
to Cool. Set system selection to Cool.