VisionPRO TM 8000 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu.
Installer Setup
Number Installer Setup Name Notes
0120 Date (Year Upper) 2001 - 2178 available
0130 Date (Year Lower) 2001 - 2178 available
0140 Date (Month)
0150 Date (Day)
0160 Schedule Options
0170 System Type Selection
Settings
Select first two digits of current calendar year (2005, etc)
Select last two digits of current calendar year (05 for year
2005, etc)
Select number that represents current calendar month
Select number that represents current calendar date
0--nonprogrammable
4--7-day programmable
1--1 heattl cool conventional (factory setting)
2--single-stage heat pump (no auxiliary heat)
3--heat only conventional (no fan) Also for 750mV.
4--heat only conventional (with fan)
5--heat only (power to open and power to close zone
valves or normally-open zone valves)
6--cool only conventional
7--2 heat/1 cool heat pump (with auxiliary heat)
8--2 heatt2 cool multistage conventional
9--2 heattl cool multistage conventional
10--1 heat/2 cool multistage conventional
11--2 heatt2cool heat pump (no auxiliary heat)
12--3 heat/2cool heat pump (with auxiliary heat)
0--gas or oil furnace equipment controls fan in heating
(factory setting)
l--electric furnace--thermostat controls fan in heating
Available options and
defaults vary by
thermostat. System
selection automatically
modifies some default
Cycles per hour (cph) for
1st Stage Compressor
Cycles per hour (cph) for
2nd Stage Compressor
Cycles per hour (cph) for
1st Stage Conventional
Heat
settings and/or hides
other installer Setup
options.
0180 Fan Control in Heating Only shown if
conventional system is
selected. If heat pump is
chosen, fan defaults to
electric.
0190 Changeover Valve--O/B Only shown if heat pump
Terminal Energized in system is chosen.
Heating or Cooling
(Heat Pumps Only)
0200 Backup Heat Source Only shown if 2 heat/
(Auxiliary Heat) 1 cool or 3 heat/2 cool
heat pump is chosen
0210 External Fuel Fossil Only shown if fossil fuel is
Fuel Kit chosen as backup heat
source.
0220
0230 Only shown if two stages
of cool are selected.
0240 Not shown if system
selection is heat pump.
0--changeover valve--O/B terminal is energized in
cooling (factory setting)
1--changeover valve--OIB terminal is energized in
heating
0--heat pump backup heat source is electric (factory
setting)
l--heat pump backup heat source is fossil fuel
0--no external fossil fuel kit is controlling heat pump
backup heat. This thermostat controls the dual fuel. Must
install outdoor sensor and set Installer Setup Number
0340 to number 2.
1--external fossil fuel kit is controlling heat pump backup
heat
3--cph recommended for compressors (factory setting)
1, 2, 4, 5, 6--other cycle rate settings
3--cph recommended for compressors (factory setting)
1, 2, 4, 5, 6--other cycle rate settings
1-- 1 cph used for steam and gravity
3--3 cph used for hot water system and high efficiency
(90% or better) furnaces
5--5 cph used for standard fossil fuel forced air (less than
80% efficient) systems (factory setting)
9--9 cph used for electric furnaces
2, 4, 6, 7, 8, 10, 11, 12--other cycle rate settings
1--1 cph used for steam and gravity
3--3 cph for hot water systems and high efficiency (90%
or better) furnaces
5--5 cph for standard fossil fuel forced air (less than 90%
efficient) systems (factory setting)
9--9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems
2, 4, 6, 7, 8, 10, 11, 12--other cycle rate settings
Cycles per hour (cph) for
2nd Stage Heat (Aux
Heat for 2H/1C Heat
Pumps)
Selection in this stage
changes default cph for
2nd stage heat.
Only shown if two stages
of heat are selected.
0250
68-0280 16