PAGE 206 December 2004 MAN0090-05
2SPECIFICATIONS
Table 1 –HE693THM166
Specification THM166 Specification THM166
Power Consumption 100mA @ 5VDC I/O Points
Required 16 %AI, 16 %I
Number of Channels 16 Input Impedance 20Mohms
Types Supported J, K, N, T, E, R, S, B, C, X Maximum Safe
Overload +/-35V
J: -210 to
+760°CT: -270 to
+400°CS: 0 to
+1768°CCommon Mode
Range +/-12V
K: -270 to
+1372°CE: -270 to
+1000°CB: 0 to
+1820°CCommon Mode
Rejection >100dB
A/D Conversion
Type Integrating
Input Range (Temp)
*X: -210 to
+1200°C
(+/-2°C
Maximum.)
(Reading not
guaranteed
below -200°C.)
N: -270 to
+1300°CR: 0 to
+1768°CC: 0 to
+2320°CA/D Conversion
Time 40 channels
per second
Resolution 0.5°C or 0.5°FOperating
Temperature 0 to 60°C (32
to 140°F)
Accuracy +/-0.5°C typical (J, K, N, T) Relative
Humidity
5% to 95%
non-
condensing
*NOTE: Model F and later support the Extended Range Type J (X).
3CONFIGURATION
To reach this screen, select I/O Configuration (F1), cursor over to the slot containing the module and select Other
(F8), and Foreign (F3).
Figure 3 -Foreign Module Configuration