HP RP36000/3 User manual

Can you meet your power
protection needs?
Power protection in your data center has always been
a critical requirement to maintain system uptime and
keep a dynamic business running. Today, the
increased densities in data centers drive the need for
uninterruptible power with increased power density,
power efficiency and flexibility. The HP RP36000/3
Uninterruptible Power System provides all three.
This pre-racked uninterruptible power system (UPS)
provides 36 kilowatts (kW) of power or 24 kW with
N+1 redundancy. Housed in a single HP 10000 G2
Series 42U rack, the system can be expanded to 60
kW with N+1 simply by installing up to three additional
RP12000/3 UPS Modules. Digital Signal Processing
(DSP), UPS paralleling and new Online On Demand
hybrid technology answer the call for increased density,
redundancy, efficiency and flexibility.
Online On Demand combines the efficiency of a
line-interactive UPS, up to 97 percent, with the stability
of a double conversion online UPS when power
fluctuates beyond acceptable limits. Hot-swappable
batteries and electronics modules and an automatic
bypass reduce downtime for maintenance.
Key features and benefits
The new HP RP36000/3 Uninterruptible Power Systems
are designed to provide high power output with industry-
leading efficiency for mission-critical enterprise solutions
and data centers.
Performance
• Supports up to 60000 volt-amperes (VA)/60000
watts in a single 42U rack
• Offers unity power factor, which means volt
amperage out equals wattage output
• Delivers industry-leading 97 percent efficiency, even
at output loads as low as 40 percent, with Online
On Demand hybrid technology
• Uses UPS paralleling for redundancy and expansion
• Delivers extra long battery life with Enhanced Battery
Management (EBM)
• Extends battery run time with optional Extended
Runtime Modules (ERMs)
• Enables longer run time with Digital Signal Processing
technology (DSP)
HP 3 Phase Parallel Uninterruptible
Power Systems
Data sheet
Efficiency, modularity and redundancy give HP 3 Phase
Parallel Uninterruptible Power Systems the ability to grow
with your data center needs, with lower energy costs and
cooling needs than conventional large uninterruptible
power systems.

Management
• Includes UPS Management Module for remote
configuration and graceful shutdown of critical
servers without the need for a dedicated
management server
• Includes hot-swappable electronics and batteries
• Is backed by a limited three-year warranty and HP
pre-failure warranty on the batteries
Redundancy
• Offers N+1 redundancy with UPS paralleling
technology
• Allows up to six UPS modules to work together to
increase load capacity and N+1 fault tolerance
• In the event of a failure, the load shifts to remaining
modules to provide 100 percent UPS protection
Options
• Allows you to attach up to four 3U Extended Runtime
Modules to each UPS for increased run time in the
event of a power failure
• Supports output modules with dual L15-30 receptacles
that can be connected to each UPS module for a total
of 12 L15-30 connections
• Fully compatible with the HP Power Distribution Rack
to provide power and scalability to rows of equipment
Ideal environments
Large data centers
The HP 3 Phase Parallel UPS can provide you with
additional power protection for multiple racks of critical
equipment in the event of a power outage, with better
efficiency than many site-level UPS systems.
Small to midsize data centers
When hundreds of kilowatts of power are not necessary,
the HP 3 Phase Parallel Uninterruptible Power System
provides power protection for an entire row of racks. Its
unique modular design allows your system to grow
with demand. Hot-swappable electronics and batteries
reduce downtime.
Collocation facilities
The HP 3 Phase Parallel UPS can provide power
protection to one or more racks and can be managed by
administrators separately from the collocation facilities.
Recommended options
RP12000/3 UPS Module AF436 (NA) and AF437 (INTL)
Based on the R12000/3, this UPS is specially designed
to attach directly to the bus bar in the RP36000/3,
allowing it to expand to 60 kW with N+1 redundancy.
HP Power Distribution Rack
The HP Power Distribution Rack (PDR) improves power
management in the data center by moving power
distribution to the row level. Decentralizing power improves
cable management, decreases diagnostic time for
problems, and saves installation costs by reducing the
size and number of long power feeds required to reach
from large wall-mounted distribution units. Capable of
high amperage inputs, the HP PDR can power several
high-density racks with shorter cable runs than
conventional site-level power distribution systems. Fully
redundant inputs and outputs provide dependable
power while protecting valuable IT equipment. Individual
branch circuit monitoring and redundant management
modules provide the status and power consumption of
each attached rack.
HP Power Distribution Units AF504A, AF503A,
AF508A and AF507A
The monitored vertical rack-mount power distribution
units (PDUs) units can connect directly to the optional
UPS output modules and provide three-phase monitored
power, as well as full-rack power utility ranging from
8.6 kilovolt-amperes (kVA) up to 22 kVA. Available
PDUs include full-rack models with 39 receptacles or
with 78 receptacles.
HP 3 Phase Modular Power Distribution Units AF512A
and AF513A
These high-output, 8.6 kVA (North America/Japan) and
11 kVA (International) Modular PDUs have a unique
modular architecture designed specifically for data center
customers who want to increase power distribution and
space efficiencies in the rack. Modular PDUs consist of
two building blocks: the Control Unit (core) and the
optional Extension Bars (sticks). The Control Unit is
1U/0U, and the optional Extension Bars mount directly
to the frame of the rack in multiple locations.
2

General characteristics
Power rating (non-redundant)
Power rating N+1
Efficiency
Heat dissipation
Cooling
Altitude before derating
Input characteristics
Input connection
Input voltage
Voltage range
Frequency range
Input current distortion
Input power factor
Inrush current
Input requirements
Bypass source
Generator compatibility
Output characteristics
Output connection
Rated output voltage
Output configuration
Output frequency (nominal)
Frequency regulation
Load power factor range
Total output voltage distortion
Battery characteristics
Battery type
Battery run time (internal)
Battery string voltage
Battery test
Battery recharge profile
Battery cut-off voltage
Battery low condition
Extended battery capability
36 kW / 36 kVA
24 kW / 24 kVA
>97%
<1113 W / 3800 BTU/hr. at 100% rated load
Fan-cooled, temperature microprocessor monitored; front air entry, rear exhaust
1000 meters (3300 ft. ASL)
Hard-wired from facility power
208 VAC and 400 VAC models
208V model: 180 to 265 VAC (N.A.)
400V model: 311 to 519 VAC (Intl.)
50 or 60 Hz, ±5 Hz (auto-sensing)
<5% with IT loads (PFC power supplies)
>.99 with IT loads (PFC power supplies)
Load dependent
Hard-wired, three-phase, wye (5 wire, 4 pole)
Same as input (single-feed)
Fast sync slew rate for generator synchronization
Hard-wired from power bus bar or uses optional output modules
208V model: 180 to 255 VAC, Ph to Ph
400V model: 180 to 240 VAC, Ph to N
Three-phase, wye. Three-phase Delta can be provided by optional
output modules
50 or 60 Hz auto-detection on startup
0.1 Hz free-running
Lagging: 0.7
Leading: 0.9
<3% with IT loads (PFC power supplies)
<5% with non-linear or non-PFC power supplies
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
>5 minutes at 100% load
240 VDC
Automatic battery test standard
Manual battery test from front display
Enhanced Battery Management three-stage charging technology
Variable from 1.67 VPC at <5 min. run time to 1.75 VPC at >90 min. run time
Announced with alarm
Yes, add up to four additional 3U battery enclosures per RP12000/3
UPS Module
12 kW / 12 kVA
60 kW / 60 kVA maximum configuration
>97%
<371 W / 1266 BTU/hr. at 100% rated load
Fan-cooled, temperature microprocessor monitored; front air entry, rear exhaust
1000 meters (3300 ft. ASL)
Connects to power bus bar
208 VAC and 400 VAC models
208V model: 180 to 265 VAC (N.A.)
400V model: 311 to 519 VAC (Intl.)
50 or 60 Hz, ±5 Hz (auto-sensing)
<5% with IT loads (PFC power supplies)
>.99 with IT loads (PFC power supplies)
Load dependent
Hard-wired, three-phase, wye (5 wire, 4 pole)
Same as input (single-feed)
Fast sync slew rate for generator synchronization
Hard-wired from power bus bar or uses optional output modules
208V model: 180 to 255 VAC, Ph to Ph
400V model: 180 to 240 VAC, Ph to N
Three-phase, wye. Three-phase Delta can be provided by optional
output modules
50 or 60 Hz auto-detection on startup
0.1 Hz free-running
Lagging: 0.7
Leading: 0.9
<3% with IT loads (PFC power supplies)
<5% with non-linear or non-PFC power supplies
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
>5 minutes at 100% load
240 VDC
Automatic battery test standard
Manual battery test from front display
Enhanced Battery Management three-stage charging technology
Variable from 1.67 VPC at <5 min. run time to 1.75 VPC at >90 min. run time
Announced with alarm
Yes, add up to four additional 3U battery enclosures per RP12000/3
UPS Module
RP36000/3 (base unit) RP12000/3 (optional UPS expansion module)
Technical specifications
3

To learn more, visit www.hp.com/products/ups
4AA1-5885ENW, November 2007
© 2007 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change
without notice. The only warranties for HP products and services are set forth in the express warranty statements
accompanying such products and services. Nothing herein should be construed as constituting an additional
warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.
HP Financial Services
HP Financial Services provides innovative financing
and financial asset management programs to help you
cost-effectively acquire, manage and ultimately retire
your HP solutions. For more information, contact your
local HP representative, or visit
www.hp.com/go/hpfinancialservices.
For more information
For more information about HP power distribution
products, contact your local HP representative or visit
www.hp.com/products/ups
Physical characteristics
Dimensions (HxDxW) UPS
Total chassis weight without
batteries or electronics
Total chassis weight with batteries
or electronics
EBM weight
Communications and user interface
Software compatibility
Control panel LCD
Multi-language
Configuration changes
REPO port
Warranty and serviceability
Warranty (parts/labor/onsite)
Serviceability features
CarePacks
Certifications
Safety
EMI
Surge protection
Hazardous materials (RoHS)
78.7 x 39.7 x 24 in.
2000 x 1015 x 597 mm
(HP 10000 G2 42U Rack)
653 lb. (296 kg)
1274 lb. (578 kg)
170 lb. (77 kg)
UPS ships with HP UPS Management Module
Two lines by 20 characters
Four menu-driven interface buttons
Four status-at-a-glance LEDs
1 per UPS Module
English standard
User-capable, firmware autoconfigures
Yes
3-year/1-year/1-year (Power bus bar is 3-year parts only)
Hot-swappable batteries
Hot-swappable electronics module
Automated internal maintenance bypass
Autoconfigure firmware
Flash firmware upgradeable
Installation CarePacks available for additional RP12000/3 UPS Modules
208V model: UL1778, cUL
400V model: CE
208V model: FCC Part15 Class A
400V model: EN62040-2 Class A
ANSI C62.41, Cat B-3
EU Directive 2002/95/EC Category 3 (4 of 5)
10.3 (6U) x 17.4 x 26.0 in.
267 x 442 x 660 mm
100 lb. (46 kg)
307 lb. (140 kg)
170 lb. (77 kg)
UPS ships with HP UPS Management Module
Two lines by 20 characters
Four menu-driven interface buttons
Four status-at-a-glance LEDs
1 per UPS Module
English standard
User-capable, firmware autoconfigures
Yes
3-year/1-year/1-year (Power bus bar is 3-year parts only)
Hot-swappable batteries
Hot-swappable electronics module
Automated internal maintenance bypass
Autoconfigure firmware
Flash firmware upgradeable
Installation CarePacks available for additional RP12000/3 UPS Modules
208V model: UL1778, cUL
400V model: CE
208V model: FCC Part15 Class A
400V model: EN62040-2 Class A
ANSI C62.41, Cat B-3
EU Directive 2002/95/EC Category 3 (4 of 5)
RP36000/3 (base unit) RP12000/3 (optional UPS expansion module)
Technical specifications
(continued)
Other manuals for RP36000/3
1
This manual suits for next models
1
Table of contents
Other HP UPS manuals
Popular UPS manuals by other brands

Puls dimension
Puls dimension UC10.241 instruction manual

Socomec Sicon
Socomec Sicon DELPHYS MX elite operating manual

Emerson
Emerson Liebert NX user manual

Lenovo
Lenovo 5594-6KX Installation and user guide

Eaton
Eaton Ellipse PRO 650 FR Installation and user manual

Alpha Technologies
Alpha Technologies Novus 1800TP Installation and operator's manual

ONEAC
ONEAC ONE404AG-SE Operation, troubleshooting and reference guide

Tuncmatik
Tuncmatik NEWTECH ECO 6kVA user manual

Tech Novitas
Tech Novitas 6 user manual

Liebert
Liebert GXT3-5000RT230 user manual

Eaton
Eaton 93P User and installation guide

Avaya
Avaya RS9 Site operation, installation and operator's manual