Huanyu HYM1L Series Owner's manual

- 1 -
HYM1L Series
Earth Leakage Circuit Breaker
Installation and Operation
Instruction
Before installing and using the product,
please read the instruction carefully and
well keep it for future reference.
Product Certificate
This product has passed the inspection and meets the
requirements of GB/T 14048.2, and therefore is allowed to
leave the factory.
Inspector:
Date of inspection: See the product or
packaging.
Huanyu Group Zhejiang High-tech Co., Ltd.
Inspection
09

- 1 -
I. Purpose and Scope of Application
The HYM1L Series Earth Leakage Circuit Breaker (hereinafter referred to as
“earth leakage circuit breaker”) is one of the new earth leakage circuit
breakers designed and developed by our company with international
advanced technology. This series of products is suitable for the circuits with
AC 50 Hz, rated isolation voltage of 800 V, rated working voltage of 400 V,
and rated current up to 630 A and below, which can provide indirect contact
protection for people with fatal electric shock, and can also be used to
prevent major fire hazard caused by grounding fault current caused by
equipment insulation damage. It can be used to protect the overload, short
circuit and undervoltage of the line, and can also be used for infrequent
transfer of lines. Furthermore, this series adds the A-type residual current
(with DC component) protection function.
The earth leakage circuit breaker is characterized by small size (equal to that
of the corresponding molded case circuit breaker), high breaking current,
short flashover and adjustable residual current operating time. It can be
equipped with alarm contact, shunt trip, undervoltage release, auxiliary
contact, handle rotation operating mechanism, electric operating mechanism
and other accessories, and can adopt the wiring in front of the plate, behind
the plate and of the plug-in type, which is an ideal product for users.
The product complies with GB/T 14048.2.
II. Normal Working Conditions
1. The altitude of the installation location shall not exceed 2,000 m.
2. The ambient air temperature shall be -5°C ~ +40°C. The average
temperature within 24 hours shall not exceed +35°C.
3. The relative atmospheric humidity shall not exceed 50% when the
ambient air temperature is +40°C. The average maximum relative
humidity of the wettest month is 90%, and the average minimum
temperature of that month is +20°C.
4. Installation category: III.
5. Contamination grade: Grade 3.
6. The installation place shall have no significant shaking and impact
vibration.
7. The magnetic field near the installation site shall not exceed 5 times of
the geomagnetic field in any direction.
8. The earth leakage circuit breaker shall generally be installed vertically.
The "1, 3, 5 and N1" terminals of the circuit breaker are connected to
the power supply, and the "2, 4, 6 and N2" terminals are connected to
the load, which cannot be reversed. If special reverse connection is
required, please indicate when ordering.

- 2 -
III. Model Description
Type of neutral pole of 4-pole circuit breaker Note 2
Release mode and accessory code (see
Table 1)
Number of poles
Note 1
Classification of operation characteristics when residual current
contains DC component: No code for default Type AC, and Code
A for Type A residual current protection device
Rated ultimate short
-circuit breaking capacity level
(Type M: M; Type L: L)
Shell frame level rated current (A)
No code for the non
-delay type, and Code Y for the delay type
Code B for alarm without tripping
With earth leakage (residual current) protection function
Design number
Molded
Case Circuit Breaker
Enterprise code
Note: (1) 2P is denoted by 2; 3P is denoted by 3; and 3P+N and 4P are
denoted by 4.
(2) The type of neutral pole (N pole) of the 4-pole circuit breaker is divided
into:
Type A: The N pole is not equipped with an overcurrent tripping element and
is normally on, and is not closed/opened with the other three poles (Code:
A).
Type B: The N pole is not equipped with an overcurrent tripping element, and
is closed/opened with the other three poles (Code: B).
Where the Type A 4-pole circuit breaker is 3P+N type.
Where the shell frame level rated current of Inm=400 A and 630 A is not
followed by L or M, and the outline dimensions and technical parameters are
the same as those of Type M.
Installation on
the left side
Installation on
the right side
Handle
Alarm contact
Auxiliary contact
Shunt trip
Undervoltage release
Lead direction

- 3 -
Table 1 Release mode and accessory code
HYM1L-125
HYM1L-250
HYM1L-400 HYM1L-630
3-pole,
4-pole
Type A
4-pole
Type B
3-pole,
4-pole
Type A
4-pole
Type B
3-pole,
4-pole
Type A
4-pole
Type B
208, 308▲Alarm contact
210, 310▲Shunt trip
220, 320▲Auxiliary contact
230, 330▲Undervoltage
release
240, 340 Shunt trip
Auxiliary contact —
—
—
250, 350
Shunt trip
Undervoltage
release
—
—
—
260, 360
2 sets of auxiliary
contacts
— — —
—
270, 370
Auxiliary contact
Undervoltage
release
— — —
—
218, 318
Shunt trip
Alarm contact
—
—
—
228, 328▲Auxiliary contact
Alarm contact
238, 338▲
Undervoltage
release
Alarm contact
— — — —
248, 348
Shunt trip
Auxiliary contact
Alarm contact
—
—
—
268, 368
2 sets of auxiliary
contacts
Alarm contact
— — —
—
278, 378
Auxiliary contact
Undervoltage
release
Alarm contact
— — — — —
Note: ①In the release mode and internal accessory code: The first digit 2
indicates electromagnetic
(instantaneous) release, and 3 indicates thermal-
electromagnetic (complex) release. The last
two digits indicate the internal accessory code, or 00 if there is no accessory.
②In HYM1L-400 and 630, the auxiliary contacts of
sizes 228, 328, 248 and 348 are a pair of
contacts (i.e. one normally-open contact and one normally-
closed contact), and the auxiliary
contacts of sizes 268 and 368 are three pairs of contacts (i.e. three normally-
open contacts
and three normally-closed co
ntacts). The configuration of other auxiliary contacts is shown in
Table 2.
③The auxiliary contacts of sizes 220, 320, 240 and 340 in HYM1L-
125 and 250 can be provided
with two pairs of contacts (i.e. two normally-open contacts and two normally-closed con
tacts),
which however, must be noted when ordering.
④
If the HYM1L series is equipped with earth leakage alarm unit module (that is, earth leakage
alarm without tripping), only the accessories of the specification with ▲ are provided.
Model
Release
mode and
internal
accessory
code
Accessory
name
Number of
poles and
N-
pole form

- 4 -
IV. Main Technical Parameters
1. See Tables 2, 3 and 4 for basic specifications and technical parameters
of the earth leakage circuit breaker.
Table 2 Basic specifications and technical parameters
Model
Rated
voltage
Un
(V)
Number
of poles
Rated
current
In (A)
Rated
ultimate
short-
circuit
breaking
capacity
Icu (kA)
Rated
operating
short-
circuit
breaking
capacity
Ics (kA)
Residual
current
operation
type
Rated
residual
operating
current
IΔn
(mA)
Rated
residual
non-
operating
current
IΔno
(mA)
Rated residual
short-circuit
making/breaking
capacity IΔm
(kA)
Flashover
distance
(mm)
HYM1L-
125L
230
2
16, 20
,
25,
32,
40, 50,
63, 80
,
100,
125
35 22
Type A
Type AC
50
100
200
300
500
1/2
IΔn
1/4
Icu
≤50
400 3
4
HYM1L-
125M
230
2
50 35
400
3
4
HYM1L-
250L
230
2
100,
125,
160,
180,
200,
225,
250
35 25
400 3
4
HYM1L-
250M
230 2 100,
125,
160,
180,
200,
225,
250
50 35
400 3
4
HYM1L-
400 400 3
4
225,
250,
315,
350,
400
50 35
100
300
500 ≤100
HYH1L-
630 400 3
4
400,
500,
630
50 35
300
500
1,000
Note: The adjustment of the three-gear residual operating current can be
selected by the user.
Table 3 Breaking time of the non-delay earth leakage circuit breaker
Residual current
IΔn
2IΔn
5IΔn
10IΔn
Maximum breaking time (S)
0.2
0.1
0.04
0.04

- 5 -
Table 4 Breaking time of the delay earth leakage circuit breaker
(The limit non-operating time Δt is 0.1 s, 0.2 s, 0.5 s, and 1 s)
Note: tn is the delay setting value. Only two-gear delay is provided for Inm = 125 A
and 250 A, and three-gear delay is provided for Inm = 400 A and 630 A.
2. See Table 5 for the interruption characteristics of inverse time operation
of the earth leakage circuit breaker for power distribution.
Table 5 Interruption characteristics of the inverse time operation of
the earth leakage circuit breaker for the power distribution
Test current
name
Set current
multiple
Conventional time
Initial state
In≤63A
In>63A
Conventional
non-tripping
current
1.05In ≥lh ≥2h Cold state
Conventional
tripping current
1.30In <lh <2h Thermal state
3. See Table 6 for the interruption characteristics of inverse time operation
of the earth leakage circuit breaker for motor protection.
Table 6 Interruption characteristics of the inverse time operation of
the earth leakage circuit breaker for the motor protection
Test current
name
Set current multiple Conventional time Initial state
Conventional
non-tripping
current
l.0In ≥2h Cold state
Conventional
tripping current
1.2In <2h Thermal state
4. The instantaneous operation characteristic of the earth leakage circuit
breaker for power distribution is set to 10 In, and the instantaneous operation
characteristic of the earth leakage circuit breaker for motor protection is set
to 12 In, and the setting accuracy is ±20%.
5. See Table 7 for mechanical and electrical operation performance.
125, 250
125, 250, 400, 630
400, 630

- 6 -
Table 7 Number of operation cycles
Shell frame level
rated current Inm
(A)
Number of
operation cycles
per hour
Number of operation cycles
Energizing De-energizing Total times
125
120
1,500
8,500
10,000
250
120
1,000
7,000
8,000
400
60
1,000
4,000
5,000
630
60
1,000
4,000
5,000
6. Electric operating mechanism
When the electric operating mechanism is used for the earth leakage circuit
breaker, reliable closing and opening of the circuit breaker shall be ensured
at any voltage between 85% and 110% of the rated control power supply
voltage.
7. Shunt trip
When the power supply voltage is equal to any voltage between 70% and
110% of the rated control power supply voltage, the circuit breaker can be
reliably interrupted by operating the shunt trip.
8. Undervoltage release
When the power supply voltage drops to 70% ~ 35% of the rated power
supply voltage, the undervoltage release shall act to interrupt the earth
leakage circuit breaker. When the power supply voltage is lower than 35%
of the rated power supply voltage, the undervoltage release shall prevent the
earth leakage circuit breaker from closing. When the power supply voltage is
equal to or greater than 85% of the rated power supply voltage, reliable
closing of the earth leakage circuit breaker shall be ensured.
9. LB earth leakage alarm module (see Figure 1)
The HYM1LB Earth Leakage Circuit Breaker is plugged with LB earth
leakage alarm module on the right side of the circuit breaker. Terminals P1-
P2 of this module are externally connected with AC 400 V or AC 230 V power
supply. When earth leakage occurs in the main circuit of the earth leakage
circuit breaker and IΔ ≥ IΔn, the earth leakage circuit breaker does not trip,
the relay in the alarm module acts, and the terminals S1, S2 and S3 are
internally connected with relay contacts to send out alarm signals.
Figure 1 Wiring diagram of the LB earth leakage alarm module
Where S2-S3 are normally-closed contacts and S1-S2 are normally-open
contacts:
A. When I∆<I∆n, the earth leakage indicator light is not on, and S2-S3 is
closed and S1-S2 is open.
LB earth
leakage
alarm
module
Contact
capacity

- 7 -
B. When I∆≥ I∆n, the earth leakage indicator light is on, and S2-S3 is open
and S1-S2 is closed.
C. Under the condition that the earth leakage indicator light is on:
(1) If I∆<I∆n, the alarm state can be released by pressing the "Reset"
button, then the earth leakage indicator light will go out, the alarm state
will be released, and the module will return to the "A" state.
(2) If after the "Reset" button is pressed, the earth leakage indicator will go
out, and it will light up immediately after the "Reset" button is released,
which indicates that when I∆≥ I∆n, the alarm state is not released, and
that the module will remain in the "B" state all the time and will not return
to the "A" state until I∆<I∆n.
Attention: The HYM1LB Earth Leakage Circuit Breaker will not trip due
to earth leakage fault even if it is not connected to the auxiliary power
supply Us. Whether S2-S3 and S1-S2 are closed in each working state
can be detected by a multimeter.
10. See Table 8 and Table 9 for the cross-section area of connecting
conductor of earth leakage circuit breaker.
Table 8 Cross-section area of the connecting conductor of the main
circuit
Rated current 16
20 25 32 40
50 63 80 100 125 160
180
200
225
250 315
350 400
Cross-section
area S of
conductor
(mm2)
2.5 4 6 10 16 25 35 50 70 95 120 185 240
Table 9 Cross-section area of the connecting conductor of the main
circuit
Rated current In (A)
500
630
Copper conductor
Pcs
2
2
Cross-section area
(mm2) 150 185
Copper busbar
Pcs
2
2
Cross-section area
(mm
2
)
30×5 40×5
V. Structure and Principle of Operation
1. This series of earth leakage circuit breakers are electronic circuit
breakers, which are mainly composed of zero-sequence current
transformers, electronically controlled earth leakage trips and circuit
breakers with overload and short-circuit protection. All parts are installed
in a pair of molded cases.

- 8 -
2. When an earth leakage or an electric shock occurs in the protected
circuit, as long as the earth leakage current reaches the set earth
leakage operating current value, the output signal of the secondary
winding of the zero-sequence current transformer will trigger the
thyristor to conduct, and the earth leakage trip will be energized and
pulled in, so that the earth leakage breaker will be tripped, thus cutting
off the power supply to protect against earth leakage and electric shock.
See Figure 2 for the principle of operation.
3. When the protected circuit is overloaded or short-circuited, the thermal-
magnetic trip completes the delay or instantaneous tripping to make the
earth leakage circuit breaker operate, thus cutting off the power supply
to protect against overload or short-circuit.
Figure 2 Principle of operation
VI. Outline and Installation Dimensions (see Figure 3 and Table 10)
Table 10 Outline and installation dimensions
Model Number
of poles
Outline dimensions (max) nm
Installation dimensions (mm)
A
B
C
D
a
b
φd
HYM1L-125L
2
62
150
75
94
—
129
4.5
3
92
150
75
94
30
129
4.5
4
122
150
75
94
60
129
4.5
HYM1L-125M
2
62
150
92
110
—
129
4.5
3
92
150
92
110
30
129
4.5
4
122
150
92
110
60
129
4.5
HYM1L-250L
2
75
165
72
94
—
127
4.5
3
107
165
72
94
35
127
4.5
4
142
165
72
94
70
127
4.5
HYM1L-250M
2
75
165
90
110
—
127
4.5
3 107 165 90 110 35 127 4.5
4
142
165
90
110
70
127
4.5
HYM1L-400
3
150
257
106.5
146.5
44
194
7
4
198
257
106.5
146.5
94
194
7
HYM1L-630
3
210
280
115.5
155
70
243
7
4
280
280
115.5
155
140
243
7
Test resistor
Test button
Circuit breaker
Electronically
controlled
earth leakage trip
Zero sequence
current
transformer
Load
Test resistor
Test button
Circuit breaker
Electronically
controlled
earth leakage
trip
Zero sequence
current
transformer
Motor

- 9 -
Figure 3 Outline and installation dimensions
VII. Use and Maintenance
1. Fix the earth leakage circuit breaker vertically (please use a Phillips
screwdriver to prevent damage to the housing). The appearance of the
earth leakage circuit breaker is in good condition, and no-load operation
works normally. The rated values of the earth leakage circuit breaker
and its accessories shall be consistent with the working conditions of the
installation site. As the earth leakage circuit breaker is equipped with
electronic circuit board, it is forbidden to measure the phase-to-phase
insulation resistance between the outgoing line terminals of the earth
leakage circuit breaker to avoid damaging electronic elements. If the
insulation test is carried out, it’s required to
a) Use a 500 V megger;
b) Measure the insulation resistance between terminals 1-2, 3-4 and
5-6 when the earth leakage circuit breaker is switched off;
c) Measure the insulation resistance between the terminals of the
main circuit and the shell (covered with metal foil) when the earth
leakage circuit breaker is closed;
d) The measured insulation resistance shall not be less than 1.5 MΩ.
2. The incoming line of the power supply must be directly above the earth
leakage circuit breaker, that is, the side marked with "1, 3, 5, N", and the
load conductors (including the neutral wires) must pass through the
earth leakage circuit breaker, and the load neutral wires must be
insulated from the ground.
3. The handle of the earth leakage circuit breaker can be in three positions:
"Closed", "Open" and "Tripped". When the handle is in the trip position,
it shall be pulled in the "Open" direction to make the circuit breaker trip
again, and then the "Closing" operation can be carried out.
Flash barrier
Flash barrier
Flash barrier

- 10 -
4. If the earth leakage circuit breaker is opened due to the failure of the
protected line, the reason shall be found out, and the closing operation
can only be carried out after troubleshooting.
5. Various characteristics of the earth leakage circuit breaker and its
accessories are set by our company according to the order requirements,
and cannot be adjusted freely during use.
6. As required by the user, the rated residual operating current IΔn and
earth leakage operating time shall be set (HYM1L non-delay earth
leakage operating time is not adjustable, while HYM1LY earth leakage
operating time is adjustable).
7. According to Chapter II "Normal Working Conditions" of this instruction
and the above articles of this chapter, the circuit breaker can be closed
and put into operation. During the operation of the circuit breaker, the
testing device shall be operated at least once a month to confirm that
the earth leakage protection function of the circuit breaker is normal.
VIII. Attention
1. The earth leakage circuit breaker cannot protect human body from
electric shock caused by contact with two load lines at the same time,
and therefore users shall pay attention to the electricity safety.
2. Do not test the device by means of short circuit between phase wires
and the ground, so as not to affect the service life of the device.
IX. Ordering Information
When ordering, users must indicate:
1. Name and model of the earth leakage circuit breaker
2. Rated current (A)
3. Rated residual operating current (mA)
4. Quantity
5. Special specifications will be discussed separately
Example of ordering: Product model name: HYM1L-125L/4300A earth
leakage circuit breaker, with rated current of 125 A, rated residual operating
current of 100/300/500 mA, non-delay type, and 100 sets.
Company Commitment
On the premise that users abide by the use and storage conditions and that
the product seals are intact, if the product is damaged or cannot be used
normally due to manufacturing quality problems within 18 months from the
production date of the product, our company will be responsible for the
repairing or replacement free of charge. If the warranty period expires, users
shall pay for the repair. However, if the damage is caused by the following
circumstances, the fees for repair still shall be charged even within the
warranty period:

Address: Wenzhou Bridge Industrial
Zone, Yueqing City, Zhejiang
Province
Service hotline: 400-887-5757
Switchboard: 0577-62889999
Fax: 0577-62885588
Website: www.huyu.com.cn
(1) Misuse, self-modification, improper maintenance, etc.
(2) Use beyond the standard specification requirements.
(3) Falling, damage during transportation, etc. after purchase.
(4) Earthquake, fire, lightning strike, abnormal voltage, other natural
disasters and secondary disasters, etc.
In case of any questions, please contact the dealer or our customer service
department.
Dear customers:
To protect our environment, please recycle the product or its components
when the product is scrapped. For materials that cannot be recycled, please
handle them properly. Thank you very much for your cooperation and
support.
This manual suits for next models
4
Table of contents
Other Huanyu Circuit Breaker manuals
Popular Circuit Breaker manuals by other brands

Eaton
Eaton HI21-P5-125/160 Instruction leaflet

Siemens
Siemens 3VM12 - ED Series operating instructions

ABB
ABB SACE Emax 2 Installation, operation and maintenance instructions for the installer and the user

ABB
ABB SACE Emax 2 user manual

hager
hager CDC740H quick start guide

Eaton
Eaton Power Defense PDC Series Instruction leaflet