Delivered
materials
Hose clamp, cable ties, snap spring, water detection cable (5 m), liquid leak detection
sensor modular, water pipe or pipe accessories, anchor baffle plate, connect plate,
check valve, combined hexagon head bolts, black self-tapping screw, cord end
terminals, OT terminals
Optional T/H sensors and cables outside cabinets, network cable for teamwork
Purchased
materials Mandatory
Refrige
rant
pipe
Refrigerant pipe components (including copper pipes, thermal
insulation foam, oil traps, and inverted traps) and pipe supports
Water
pipe
Water
supply
pipe
Rigid pipe (1/2-inch BSPT, outer screw thread, made of
PP-R or C-PVC), pagoda connector (BSPT, 1/2-inch,
outer thread connector), hose clamp, hose (for example,
Ethylene-Propylene-Diene Monomer (EPDM))
Drainpi
pe Rigid pipe (1/2 inch BSPT, outer screw thread, made of
PP-R or C-PVC), hose clamp, hose (inner diameter of
5/8-inch, for example EPDM), rigid pipe conversion
adapter (5/8-inch outer diameter converting to 1/2 inch
BSPP inner screw thread), thermal insulation foam
Cable Indoor unit power cable, outdoor unit power cable,
outdoor unit ON/OFF signal cable
2Material Preparations
1. Vacuum pump: Flow 2 L/s to 4 L/s, absolute vacuum level ≤ 60 Pa.
2. Pressure gauge and leather hose: Dedicated to R410A, pressure gauge measurement range
≥ 4.0 MPa, and the leather hose tolerance range ≥ 4.5 MPa.
3. Welding torch and welding rod: Silver copper welding rod (5% silver).
4. Nitrogen reducing valve: A reducing valve must be installed on the head of the nitrogen
cylinder, and the reducing valve range ≥ 4.0 MPa.
5. Dry nitrogen.
Special tools and materials
Refrigerant R410A
2.1
Do not use unqualified refrigerant. Huawei will not be liable for any equipment damage caused by
unqualified refrigerant.
Refrigerant from name brands such as DuPont, Daikin, and Honeywell are recommended. You
can verify the refrigerant authenticity in the following ways:
1. Dial the refrigerant manufacturer's hotline to confirm the refrigerant manufacturer authenticity.
2. Place the refrigerant tank indoors for 24 hours. Use a point thermometer to measure the outer
surface temperature of the refrigerant tank (figure 1), and connect a pressure gauge to the tank
to measure the internal pressure (figure 2). Find the saturation pressure corresponding to the
measured outer surface temperature from the table on the next page. If the deviation between
the saturation pressure and the measured internal pressure is greater than 0.2 MPa, the
refrigerant does not meet the requirements, and needs to be replaced.
1