Hubbel TRIPLE H User manual

WARNINGS
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
• Disconnect power before installing or servicing.
•The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
•Protect all wiring connections with approved insulators rated 600V. 150ºC.
•Line voltage must be 120V – 277V to match fixture voltage requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
•Upon receipt of this fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held accountable.
TRIPLE H™
High Ambient High Output High Efficacy Highbay/Lowbay
Triple TM

INSTALLING HOOK/LOOP MOUNT (See Figure 1, 2, & 3):
NOTE: Cord and Hook/Loop ordered as CxHLPx
(Plug optional and ordered separately)
1. Insert end of Power Cord (A) through Hook/Loop (B). Supply cord is to be rated for a minimum of 90OC 16/3 SEOW-A/STOOW.
2. Insert end of Power Cord through the Cord Grip/Gotcha-ring (D),Rubber Bushing (E) and Washer (F). Note that the Rubber
Bushing is placed between the Cord Grip and Washer. Part of the cord jacket should extend through Bushing (E) and Washer
(F).
3. Insert the Power Cord through the Yoke Assy Crossmember (C) and into the Wiring Box ¾ Conduit hole, allowing the Washer
(F), Bushing (E) to “seat” inside. The Cord Grip (D) remains in place at the Hook/Loop.
4. Apply Teflon tape to the male (external) conduit thread of the Hook (A).
5. Thread the Hook (A) into the ¾” NPT Conduit Box (C). Use a wrench over the hex shape on the hook casting to tighten it in
place.
CAUTION: Do not twist the hook by using a screwdriver blade – too much force could break the hook.
6. Connect cord wires to the fixture AC Power Input Jumper Cord Ass’y, already factory installed into J-box, with approved wire
nuts. See wiring diagram for reference (page 3 and figure 6). Wires and wire nuts can now be pushed back into the
fixture/driver housing. Ensure grounding wires within wiring Box are secure.
7. Close out Wiring Box (G) using Cover, Cover Gasket, and Screws provided in hardware kit.
8. Mount wired Yoke Assembly (H) onto fixture rails using 5/16” Screw (J) provided in hardware kit into each pair of Slide Nut (K)
already inserted into the rail. Position the mounted Yoke Ass’y according to the centering illustration on page 10. Fine tuning
of the final Yoke Ass’y position on the rail may be required to achieve final balance and alignment.
9. Tighten the Yoke Ass’y mounting screws to torque noted in Fig. 3.
10. Tighten Set Screw (F) to secure hook from loosening.
11. Secure Closure Backet (M) with Screw (N) provided.
12. Install lens option onto each Lightbar, see Figure 9. If wireguard was ordered, lenses will ship installed on fixture.
13. Complete electrical connection by installing AC Input Jumper Cord connector into AC Panel as shown in Figure 3.
INSTALLATION INSTRUCTIONS
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision A
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
FIGURE 1
FIGURA 1
FIGURE 3
FIGURA 3
FIGURE 2
FIGURA 2
PAGE 1
WIRING BOX
3/4" OUTLETS
(G)
5/16 MNTG SCREW (J)
INTO RAIL SLIDE NUT (K)
TORQUE: 120 IN-LB
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated
600V, 150OC.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held
accountable.
INSTALLING HOOK/LOOP MOUNT (See Figure 1, 2, & 3):
NOTE: Cord and Hook/Loop ordered as CxHLPx
(Plug optional and ordered separately)
1. Insert end of Power Cord (A) through Hook/Loop (B). Supply cord
is to be rated for a minimum of 90OC 16/3 SEOW-A/STOOW.
2. Insert end of Power Cord through the Cord Grip/Gotcha-ring (D),
Rubber Bushing (E) and Washer (F). Note that the Rubber
Bushing is placed between the Cord Grip and Washer. Part of
the cord jacket should extend through Bushing (E) and Washer
(F).
3. Insert the Power Cord through the Yoke Assy Crossmember (C)
and into the Wiring Box ¾ Conduit hole, allowing the Washer (F),
Bushing (E) to “seat” inside. The Cord Grip (D) remains in place
at the Hook/Loop.
4. Apply Teflon tape to the male (external) conduit thread of the
Hook (A).
5. Thread the Hook (A) into the ¾” NPT Conduit Box (C). Use a
wrench over the hex shape on the hook casting to tighten it in
place.
CAUTION: Do not twist the hook by using a screwdriver blade –
too much force could break the hook.
6. Connect cord wires to the fixture AC Power Input Jumper Cord
Ass’y, already factory installed into J-box, with approved wire
nuts. See wiring diagram for reference (page 3 and figure 6).
Wires and wire nuts can now be pushed back into the
fixture/driver housing. Ensure grounding wires within wiring Box
are secure.
7. Close out Wiring Box (G) using Cover, Cover Gasket, and Screws
provided in hardware kit.
8. Mount wired Yoke Assembly (H) onto fixture rails using 5/16”
Screw (J) provided in hardware kit into each pair of Slide Nut (K)
already inserted into the rail. Position the mounted Yoke Ass’y
according to the centering illustration on page 10. Fine tuning of
the final Yoke Ass’y position on the rail may be required to
achieve final balance and alignment.
9. Tighten the Yoke Ass’y mounting screws to torque noted in Fig. 3.
10. Tighten Set Screw (F) to secure hook from loosening.
11. Secure Closure Backet (M) with Screw (N) provided.
12. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
13. Complete electrical connection by installing AC Input Jumper
Cord connector into AC Panel as shown in Figure 3.
CLOSURE
BRACKET (M)
RETAINING
SCREW (N)
AFTER WIRING
ASSEMBLE YOKE
TO FIXTURE USING
RAIL MOUNTING
HARDWARE KIT
- SEE FIG. 3
D
E
F
A
B
YOKE
CROSSMEMBER
C
COMPLETE
YOKE ASS'Y
(H)
(CORDSETS
NOT SHOWN)
FIGURE 1a.
FIGURA 1a.
PLUG
(OPTION AL)
CORD
ROUTE INTO
J-BOX WIRE TO
AC INPUT JUMPER
L
M
N
Hubbell Lighting, Inc.
Doc. No. 93062486
A subsidiary of Hubbell Incorporated
Revision A
701 Millennium Drive • Greenville, SC 29607 Pho
ne (864) 678-1000
Industrial Lighting
®
FIGURE 1
FIGURA 1
FIGURE 3
FIGURA 3
FIGURE 2
FIGURA 2
PAGE 1
WIRING BOX
3/4" OUTLETS
(G)
5/16 MNTG SCREW (J)
INTO RAIL SLIDE NUT (K)
TORQUE: 120 IN-LB
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated
600V, 150OC.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held
accountable.
INSTALLING HOOK/LOOP MOUNT (See Figure 1, 2, & 3):
NOTE: Cord and Hook/Loop ordered as CxHLPx
(Plug optional and ordered separately)
1. Insert end of Power Cord (A) through Hook/Loop (B). Supply cord
is to be rated for a minimum of 90OC 16/3 SEOW-A/STOOW.
2. Insert end of Power Cord through the Cord Grip/Gotcha-ring (D),
Rubber Bushing (E) and Washer (F). Note that the Rubber
Bushing is placed between the Cord Grip and Washer. Part of
the cord jacket should extend through Bushing (E) and Washer
(F).
3. Insert the Power Cord through the Yoke Assy Crossmember (C)
and into the Wiring Box ¾ Conduit hole, allowing the Washer (F),
Bushing (E) to “seat” inside. The Cord Grip (D) remains in place
at the Hook/Loop.
4. Apply Teflon tape to the male (external) conduit thread of the
Hook (A).
5. Thread the Hook (A) into the ¾” NPT Conduit Box (C). Use a
wrench over the hex shape on the hook casting to tighten it in
place.
CAUTION: Do not twist the hook by using a screwdriver blade –
too much force could break the hook.
6. Connect cord wires to the fixture AC Power Input Jumper Cord
Ass’y, already factory installed into J-box, with approved wire
nuts. See wiring diagram for reference (page 3 and figure 6).
Wires and wire nuts can now be pushed back into the
fixture/driver housing. Ensure grounding wires within wiring Box
are secure.
7. Close out Wiring Box (G) using Cover, Cover Gasket, and Screws
provided in hardware kit.
8. Mount wired Yoke Assembly (H) onto fixture rails using 5/16”
Screw (J) provided in hardware kit into each pair of Slide Nut (K)
already inserted into the rail. Position the mounted Yoke Ass’y
according to the centering illustration on page 10. Fine tuning of
the final Yoke Ass’y position on the rail may be required to
achieve final balance and alignment.
9. Tighten the Yoke Ass’y mounting screws to torque noted in Fig. 3.
10. Tighten Set Screw (F) to secure hook from loosening.
11. Secure Closure Backet (M) with Screw (N) provided.
12. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
13. Complete electrical connection by installing AC Input Jumper
Cord connector into AC Panel as shown in Figure 3.
CLOSURE
BRACKET (M)
RETAINING
SCREW (N)
AFTER WIRING
ASSEMBLE YOKE
TO FIXTURE USING
RAIL MOUNTING
HARDWARE KIT
- SEE FIG. 3
D
E
F
A
B
YOKE
CROSSMEMBER
C
COMPLETE
YOKE ASS'Y
(H)
(CORDSETS
NOT SHOWN)
FIGURE 1a.
FIGURA 1a.
PLUG
(OPTION AL)
CORD
ROUTE INTO
J-BOX WIRE TO
AC INPUT JUMPER
L
M
N
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision A
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
FIGURE 1
FIGURA 1
FIGURE 3
FIGURA 3
FIGURE 2
FIGURA 2
PAGE 1
WIRING BOX
3/4" OUTLETS
(G)
5/16 MNTG SCREW (J)
INTO RAIL SLIDE NUT (K)
TORQUE: 120 IN-LB
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated
600V, 150OC.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held
accountable.
INSTALLING HOOK/LOOP MOUNT (See Figure 1, 2, & 3):
NOTE: Cord and Hook/Loop ordered as CxHLPx
(Plug optional and ordered separately)
1. Insert end of Power Cord (A) through Hook/Loop (B). Supply cord
is to be rated for a minimum of 90OC 16/3 SEOW-A/STOOW.
2. Insert end of Power Cord through the Cord Grip/Gotcha-ring (D),
Rubber Bushing (E) and Washer (F). Note that the Rubber
Bushing is placed between the Cord Grip and Washer. Part of
the cord jacket should extend through Bushing (E) and Washer
(F).
3. Insert the Power Cord through the Yoke Assy Crossmember (C)
and into the Wiring Box ¾ Conduit hole, allowing the Washer (F),
Bushing (E) to “seat” inside. The Cord Grip (D) remains in place
at the Hook/Loop.
4. Apply Teflon tape to the male (external) conduit thread of the
Hook (A).
5. Thread the Hook (A) into the ¾” NPT Conduit Box (C). Use a
wrench over the hex shape on the hook casting to tighten it in
place.
CAUTION: Do not twist the hook by using a screwdriver blade –
too much force could break the hook.
6. Connect cord wires to the fixture AC Power Input Jumper Cord
Ass’y, already factory installed into J-box, with approved wire
nuts. See wiring diagram for reference (page 3 and figure 6).
Wires and wire nuts can now be pushed back into the
fixture/driver housing. Ensure grounding wires within wiring Box
are secure.
7. Close out Wiring Box (G) using Cover, Cover Gasket, and Screws
provided in hardware kit.
8. Mount wired Yoke Assembly (H) onto fixture rails using 5/16”
Screw (J) provided in hardware kit into each pair of Slide Nut (K)
already inserted into the rail. Position the mounted Yoke Ass’y
according to the centering illustration on page 10. Fine tuning of
the final Yoke Ass’y position on the rail may be required to
achieve final balance and alignment.
9. Tighten the Yoke Ass’y mounting screws to torque noted in Fig. 3.
10. Tighten Set Screw (F) to secure hook from loosening.
11. Secure Closure Backet (M) with Screw (N) provided.
12. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
13. Complete electrical connection by installing AC Input Jumper
Cord connector into AC Panel as shown in Figure 3.
CLOSURE
BRACKET (M)
RETAINING
SCREW (N)
AFTER WIRING
ASSEMBLE YOKE
TO FIXTURE USING
RAIL MOUNTING
HARDWARE KIT
- SEE FIG. 3
D
E
F
A
B
YOKE
CROSSMEMBER
C
COMPLETE
YOKE ASS'Y
(H)
(CORDSETS
NOT SHOWN)
FIGURE 1a.
FIGURA 1a.
PLUG
(OPTION AL)
CORD
ROUTE INTO
J-BOX WIRE TO
AC INPUT JUMPER
L
M
N

INSTALLING PENDANT MOUNT (See Figure 1, 3, 4, 5, & 6):
1. Install Locknut (Q) onto Pendent threads to the end of the threads.
2. Apply Teflon tape to the male (external) conduit thread of the Pendent (P).
3. Insert wiring from Pendent mounting conduit (P) into Wiring Box (G) of the Yoke Ass’y (H). Conduit end passes through the
Yoke Assy Crossmember (C) and into the Wiring Box ¾ Conduit hole.
4. Carefully thread the Yoke Ass’y onto the Pendent conduit (P) via Wiring Box. Use a wrench over the hex shape on the hook
casting to tighten it in place.
CAUTION: Do not twist the hook by using a screwdriver blade – too much force could break the hook.
5. Connect cord wires to the fixture AC Power Input Jumper Cord Ass’y, already factory installed into J-box, with approved wire
nuts. See wiring diagram for reference (page 3). Wires and wire nuts can now be pushed back into the fixture/driver housing.
Ensure grounding wires within wiring Box are secure.
6. Close out Wiring Box (G) using Cover, Cover Gasket, and Screws provided in hardware kit.
7. Mount the fixture onto the Pendent mounted Yoke Assembly (H) via each rail using 5/16” Screw (J) provided in hardware kit
into each pair of Slide Nut (K) already inserted into the rail. Position the mounted Yoke Ass’y according to the centering
illustration on page 10. Fine tuning of the final Yoke Ass’y position on the rail may be required to achieve final balance and
alignment.
8. Tighten the Yoke Ass’y mounting screws to torque noted in Fig. 3.
9. Install lens option onto each Lightbar, see Figure 9. If wireguard was ordered, lenses will ship installed on fixture.
10. Complete electrical connection by installing AC Input Jumper Cord connector into AC Panel as shown in Figure 5.
INSTALLATION INSTRUCTIONS
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision A
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
FIGURE 5
FIGURA 5
FIGURE 6
FIGURA 6
PAGE 2
WIRING
BOX
COVER
#8-32 SCREWS
LOCKNUT (Q)
YOKE ASSEMBLY (H)
3/4" CONDUIT
INLET INTO J-BOX
SEAL WITH RTV
AFTER INSTALL
PENDANT
3/4" RIGID CONDUIT
(P)
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated 600V.
150
O
C.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held accountable.
INSTALLING PENDANT MOUNT (See Figure 1, 3, 4, 5, & 6):
1. Install Locknut (Q) onto Pendent threads to the end of the threads.
2. Apply Teflon tape to the male (external) conduit thread of the
Pendent (P).
3. Insert wiring from Pendent mounting conduit (P) into Wiring Box
(G) of the Yoke Ass’y (H). Conduit end passes through the Yoke
Assy Crossmember (C) and into the Wiring Box ¾ Conduit hole.
4. Carefully thread the Yoke Ass’y onto the Pendent conduit (P) via
Wiring Box. Use a wrench over the hex shape on the hook casting
to tighten it in place.
CAUTION: Do not twist the hook by using a screwdriver blade –
too much force could break the hook.
5. Connect cord wires to the fixture AC Power Input Jumper Cord
Ass’y, already factory installed into J-box, with approved wire nuts.
See wiring diagram for reference (page 3). Wires and wire nuts can
now be pushed back into the fixture/driver housing. Ensure
grounding wires within wiring Box are secure.
6. Close out Wiring Box (G) using Cover, Cover Gasket, and Screws
provided in hardware kit.
7. Mount the fixture onto the Pendent mounted Yoke Assembly (H)
via each rail using 5/16” Screw (J) provided in hardware kit into
each pair of Slide Nut (K) already inserted into the rail. Position the
mounted Yoke Ass’y according to the centering illustration on page
10. Fine tuning of the final Yoke Ass’y position on the rail may be
required to achieve final balance and alignment.
8. Tighten the Yoke Ass’y mounting screws to torque noted in Fig. 3.
9. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
10. Complete electrical connection by installing AC Input Jumper Cord
connector into AC Panel as shown in Figure 5.
FIGURE 4
FIGURA 4
J-BOX
SEALING
GASKET
AC INPUT POWER CORD
FROM WIRING J-BOX
CONNECTED TO DRIVER
MODULE.
FACTORY WIRED
AC INPUT CORD
FROM J-BOX - CONNECT
TO AC INPUT PANEL
ON DRIVER MODULE
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision A
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
FIGURE 5
FIGURA 5
FIGURE 6
FIGURA 6
PAGE 2
WIRING
BOX
COVER
#8-32 SCREWS
LOCKNUT (Q)
YOKE ASSEMBLY (H)
3/4" CONDUIT
INLET INTO J-BOX
SEAL WITH RTV
AFTER INSTALL
PENDANT
3/4" RIGID CONDUIT
(P)
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated 600V.
150
O
C.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held accountable.
INSTALLING PENDANT MOUNT (See Figure 1, 3, 4, 5, & 6):
1. Install Locknut (Q) onto Pendent threads to the end of the threads.
2. Apply Teflon tape to the male (external) conduit thread of the
Pendent (P).
3. Insert wiring from Pendent mounting conduit (P) into Wiring Box
(G) of the Yoke Ass’y (H). Conduit end passes through the Yoke
Assy Crossmember (C) and into the Wiring Box ¾ Conduit hole.
4. Carefully thread the Yoke Ass’y onto the Pendent conduit (P) via
Wiring Box. Use a wrench over the hex shape on the hook casting
to tighten it in place.
CAUTION: Do not twist the hook by using a screwdriver blade –
too much force could break the hook.
5. Connect cord wires to the fixture AC Power Input Jumper Cord
Ass’y, already factory installed into J-box, with approved wire nuts.
See wiring diagram for reference (page 3). Wires and wire nuts can
now be pushed back into the fixture/driver housing. Ensure
grounding wires within wiring Box are secure.
6. Close out Wiring Box (G) using Cover, Cover Gasket, and Screws
provided in hardware kit.
7. Mount the fixture onto the Pendent mounted Yoke Assembly (H)
via each rail using 5/16” Screw (J) provided in hardware kit into
each pair of Slide Nut (K) already inserted into the rail. Position the
mounted Yoke Ass’y according to the centering illustration on page
10. Fine tuning of the final Yoke Ass’y position on the rail may be
required to achieve final balance and alignment.
8. Tighten the Yoke Ass’y mounting screws to torque noted in Fig. 3.
9. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
10. Complete electrical connection by installing AC Input Jumper Cord
connector into AC Panel as shown in Figure 5.
FIGURE 4
FIGURA 4
J-BOX
SEALING
GASKET
AC INPUT POWER CORD
FROM WIRING J-BOX
CONNECTED TO DRIVER
MODULE.
FACTORY WIRED
AC INPUT CORD
FROM J-BOX - CONNECT
TO AC INPUT PANEL
ON DRIVER MODULE

Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision A
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 3
FIGURE 7
FIGURA 7
FIGURE 9
FIGURA 9
5/16 MNTG SCREW (J)
INTO RAIL SLIDE NUT (K)
TORQUE: 120 IN-LB
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated
600V. 150
O
C.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held
accountable.
INSTALLING AIRCRAFT CABLE MOUNTING SYSTEM
(See Figure 7 and 8):
WARNING! NOTICE AIRCRAFT CABLE KIT TYPE SHIPPED
WITH YOUR ORDER:
2mm KIT FOR LOWBAY SERIES ONLY!
3mm KIT FOR HIGHBAY SERIES ONLY!
1. Install AC Mounting Bracket (R) onto each corner of the rail, inset
approximately 1-inch from the rail end. Using 5/16” Screw (J)
provided in the hardware kit, insert the screw through the bottom
hole of each backet and install into the Slide Nut (K) pre-installed
within the rail. Ensure the bracket when pre-tightened is vertically
oriented as shown in Figure 8.
2. Tighten AC Mounting Bracket Screw (J) to torque noted in Fig. 8,
while supporting the bracket orientation to prevent rotating during
the tightening sequence.
3. Insert each Snap Hook Eyelet of the Y-Cable Ass’y onto the AC
Mounting Bracket top holes on each end of the fixture so that the
cable spans across the lightbar as shown in Figure 7.
4. The Top Cable of the Aircraft System is lopped around a facility
structural member suitable to support the fixture load. The bare
cable end being inserted into the Top Cable Loop and then
proceeding into the Gripper. The Top Cable length should be
adjusted to desired length according to mounting height selected).
5. Repeat for other side of the fixture cable mounting.
6. Final adjustment of the Gripper Barrel position across the width of
the fixture will balance the fixt
ure, while Top Cable Length
adjustment will balance the fixture lengthwise. See Figure 7
illustration.
7. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
8. Complete electrical connection by installing AC Input Cord into
AC Panel as shown in Figure 10.
AIRCRAFT CABLE KIT
( 2mm KIT FOR LB, 3mm KIT FOR HB)
FIGURE 8
FIGURA 8
ACRYLIC LENS: SNAP INTO
LIGHTBAR GROOVE
AIRCRAFT
MNTG OPTION
BRACKET (R)
AIRCRAFT CABLE KIT
( 2mm KIT FOR LB, 3mm KIT FOR HB)
FIGURE 10
FIGURA 10
INSTALLING AIRCRAFT CABLE MOUNTING SYSTEM (See Figure 7 and 8):
WARNING! NOTICE AIRCRAFT CABLE KIT TYPE SHIPPED
WITH YOUR ORDER:
2mm KIT FOR LOWBAY SERIES ONLY!
3mm KIT FOR HIGHBAY SERIES ONLY!
1. Install AC Mounting Bracket (R) onto each corner of the rail, inset approximately 1-inch from the rail end. Using 5/16” Screw
(J) provided in the hardware kit, insert the screw through the bottom hole of each backet and install into the Slide Nut (K)
pre-installed within the rail. Ensure the bracket when pre-tightened is vertically oriented as shown in Figure 8.
2. Tighten AC Mounting Bracket Screw (J) to torque noted in Fig. 8, while supporting the bracket orientation to prevent rotating
during the tightening sequence.
3. Insert each Snap Hook Eyelet of the Y-Cable Ass’y onto the AC Mounting Bracket top holes on each end of the fixture so that
the cable spans across the lightbar as shown in Figure 7.
4. The Top Cable of the Aircraft System is lopped around a facility structural member suitable to support the fixture load. The
bare cable end being inserted into the Top Cable Loop and then proceeding into the Gripper. The Top Cable length should be
adjusted to desired length according to mounting height selected).
5. Repeat for other side of the fixture cable mounting.
6. Final adjustment of the Gripper Barrel position across the width of the fixture will balance the fixture, while Top Cable Length
adjustment will balance the fixture lengthwise. See Figure 7 illustration.
7. Install lens option onto each Lightbar, see Figure 9. If wireguard was ordered, lenses will ship installed on fixture.
8. Complete electrical connection by installing AC Input Cord into AC Panel as shown in Figure 10.
INSTALLATION INSTRUCTIONS
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision A
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 3
FIGURE 7
FIGURA 7
FIGURE 9
FIGURA 9
5/16 MNTG SCREW (J)
INTO RAIL SLIDE NUT (K)
TORQUE: 120 IN-LB
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated
600V. 150
O
C.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held
accountable.
INSTALLING AIRCRAFT CABLE MOUNTING SYSTEM
(See Figure 7 and 8):
WARNING! NOTICE AIRCRAFT CABLE KIT TYPE SHIPPED
WITH YOUR ORDER:
2mm KIT FOR LOWBAY SERIES ONLY!
3mm KIT FOR HIGHBAY SERIES ONLY!
1. Install AC Mounting Bracket (R) onto each corner of the rail, inset
approximately 1-inch from the rail end. Using 5/16” Screw (J)
provided in the hardware kit, insert the screw through the bottom
hole of each backet and install into the Slide Nut (K) pre-installed
within the rail. Ensure the bracket when pre-tightened is vertically
oriented as shown in Figure 8.
2. Tighten AC Mounting Bracket Screw (J) to torque noted in Fig. 8,
while supporting the bracket orientation to prevent rotating during
the tightening sequence.
3. Insert each Snap Hook Eyelet of the Y-Cable Ass’y onto the AC
Mounting Bracket top holes on each end of the fixture so that the
cable spans across the lightbar as shown in Figure 7.
4. The Top Cable of the Aircraft System is lopped around a facility
structural member suitable to support the fixture load. The bare
cable end being inserted into the Top Cable Loop and then
proceeding into the Gripper. The Top Cable length should be
adjusted to desired length according to mounting height selected).
5. Repeat for other side of the fixture cable mounting.
6. Final adjustment of the Gripper Barrel position across the width of
the fixture will balance the fixture, while Top Cable Length
adjustment will balance the fixture lengthwise. See Figure 7
illustration.
7. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
8. Complete electrical connection by installing AC Input Cord into
AC Panel as shown in Figure 10.
AIRCRAFT CABLE KIT
( 2mm KIT FOR LB, 3mm KIT FOR HB)
FIGURE 8
FIGURA 8
ACRYLIC LENS: SNAP INTO
LIGHTBAR GROOVE
AIRCRAFT
MNTG OPTION
BRACKET (R)
AIRCRAFT CABLE KIT
( 2mm KIT FOR LB, 3mm KIT FOR HB)
FIGURE 10
FIGURA 10
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision A
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 3
FIGURE 7
FIGURA 7
FIGURE 9
FIGURA 9
5/16 MNTG SCREW (J)
INTO RAIL SLIDE NUT (K)
TORQUE: 120 IN-LB
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated
600V. 150
O
C.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held
accountable.
INSTALLING AIRCRAFT CABLE MOUNTING SYSTEM
(See Figure 7 and 8):
WARNING! NOTICE AIRCRAFT CABLE KIT TYPE SHIPPED
WITH YOUR ORDER:
2mm KIT FOR LOWBAY SERIES ONLY!
3mm KIT FOR HIGHBAY SERIES ONLY!
1. Install AC Mounting Bracket (R) onto each corner of the rail, inset
approximately 1-inch from the rail end. Using 5/16” Screw (J)
provided in the hardware kit, insert the screw through the bottom
hole of each backet and install into the Slide Nut (K) pre-installed
within the rail. Ensure the bracket when pre-tightened is vertically
oriented as shown in Figure 8.
2. Tighten AC Mounting Bracket Screw (J) to torque noted in Fig. 8,
while supporting the bracket orientation to prevent rotating during
the tightening sequence.
3. Insert each Snap Hook Eyelet of the Y-Cable Ass’y onto the AC
Mounting Bracket top holes on each end of the fixture so that the
cable spans across the lightbar as shown in Figure 7.
4. The Top Cable of the Aircraft System is lopped around a facility
structural member suitable to support the fixture load. The bare
cable end being inserted into the Top Cable Loop and then
proceeding into the Gripper. The Top Cable length should be
adjusted to desired length according to mounting height selected).
5. Repeat for other side of the fixture cable mounting.
6. Final adjustment of the Gripper Barrel position across the width of
the fixture will balance the fixture, while Top Cable Length
adjustment will balance the fixture lengthwise. See Figure 7
illustration.
7. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
8. Complete electrical connection by installing AC Input Cord into
AC Panel as shown in Figure 10.
AIRCRAFT CABLE KIT
( 2mm KIT FOR LB, 3mm KIT FOR HB)
FIGURE 8
FIGURA 8
ACRYLIC LENS: SNAP INTO
LIGHTBAR GROOVE
AIRCRAFT
MNTG OPTION
BRACKET (R)
AIRCRAFT CABLE KIT
( 2mm KIT FOR LB, 3mm KIT FOR HB)
FIGURE 10
FIGURA 10

Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision A
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 3
FIGURE 7
FIGURA 7
FIGURE 9
FIGURA 9
5/16 MNTG SCREW (J)
INTO RAIL SLIDE NUT (K)
TORQUE: 120 IN-LB
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
SEE WARNINGS ON CARTON
WARNINGS:
Observe all precautions usually followed when dealing with high
voltage equipment when installing or servicing this light fixture.
Disconnect power before installing or servicing.
The product must be installed in accordance with the applicable
installation code by a person familiar with the construction and
operation of the product and the hazards involved.
Protect all wiring connections with approved insulators rated
600V. 150
O
C.
Line voltage must be 120V – 277V to match Fixture voltage
requirement.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
Upon receipt of this Fixture, thoroughly inspect it for any damage.
If any is found, the carrier should be notified and held
accountable.
INSTALLING AIRCRAFT CABLE MOUNTING SYSTEM
(See Figure 7 and 8):
WARNING! NOTICE AIRCRAFT CABLE KIT TYPE SHIPPED
WITH YOUR ORDER:
2mm KIT FOR LOWBAY SERIES ONLY!
3mm KIT FOR HIGHBAY SERIES ONLY!
1. Install AC Mounting Bracket (R) onto each corner of the rail, inset
approximately 1-inch from the rail end. Using 5/16” Screw (J)
provided in the hardware kit, insert the screw through the bottom
hole of each backet and install into the Slide Nut (K) pre-installed
within the rail. Ensure the bracket when pre-tightened is vertically
oriented as shown in Figure 8.
2. Tighten AC Mounting Bracket Screw (J) to torque noted in Fig. 8,
while supporting the bracket orientation to prevent rotating during
the tightening sequence.
3. Insert each Snap Hook Eyelet of the Y-Cable Ass’y onto the AC
Mounting Bracket top holes on each end of the fixture so that the
cable spans across the lightbar as shown in Figure 7.
4. The Top Cable of the Aircraft System is lopped around a facility
structural member suitable to support the fixture load. The bare
cable end being inserted into the Top Cable Loop and then
proceeding into the Gripper. The Top Cable length should be
adjusted to desired length according to mounting height selected).
5. Repeat for other side of the fixture cable mounting.
6. Final adjustment of the Gripper Barrel position across the width of
the fixture will balance the fixture, while Top Cable Length
adjustment will balance the fixture lengthwise. See Figure 7
illustration.
7. Install lens option onto each Lightbar, see Figure 9. If wireguard
was ordered, lenses will ship installed on fixture.
8. Complete electrical connection by installing AC Input Cord into
AC Panel as shown in Figure 10.
AIRCRAFT CABLE KIT
( 2mm KIT FOR LB, 3mm KIT FOR HB)
FIGURE 8
FIGURA 8
ACRYLIC LENS: SNAP INTO
LIGHTBAR GROOVE
AIRCRAFT
MNTG OPTION
BRACKET (R)
AIRCRAFT CABLE KIT
( 2mm KIT FOR LB, 3mm KIT FOR HB)
FIGURE 10
FIGURA 10
Hubbell Lighting, Inc.
A subsidiary of Hubbell Incorporated
701 Millennium Drive • Greenville, SC 29607
Industrial Lighting
®
PAGE 4
HHH WIRING DIAGRAMS
GROUND
GREEN
LINE
(HOT) BLACK
BLACK
WHITE
RED
R
E
D
W
H
T
B
L
K
FUSING
WIHUBB OPTION
(ETO ONLY)
FUSING
SINGLE FUSE
OPTION
DOUBLE FUSE
OPTION
OCCUPANCY SENSOR
(OCS) OPTION
R
E
D
W
H
T
B
L
K
SURGE
SUPPRESSOR
CONTROL SENSOR (WST)
(ETO ONLY)
WIRELESS CONTROL DEVICE
(WIS) OPTION
WHITE
BLACK
DC INPUT
PANEL CONNECTOR
LIGHTBAR
+
-
+
-
DC OUTPUT
PANEL CONNECTOR
FROM DRIVER MDL
INTERCONNECT CORDSET ASSY'S
90° HEAD BOTH ENDS - MALE PINS ON
DRIVER OUTPUT, FEMALE END TOWARDS LIGHTBAR)
DRVR
RED
BLUE
RED
BLUE
BRWN
BLUE
BRWN
BLUE
R
E
D
W
H
T
B
L
K
GREEN
BLACK
WHITE
Doc. No. 93062486
Revision A
Phone (864) 678-1000
HHH MODULAR LOWBAY LOW OUTPUT ASSEMBLY
WIRING DIAGRAM "LOWBAY TWIN"
HHH-xK-LB-LO
WIRING DIAGRAMS
INSTALLATION INSTRUCTIONS
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision C
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 1
SEE TABLE
BELOW
FIGURE 11
FIGURA 11
HHH (MODULAR HIGHBAY) - LOOSE DIMMING LEADS WIRING TO HOUSE SUPPLY
Item Service/ReplPartNr
(incl.packaging)
LightEngines
15‐inchLEDboards5K 93075032
26‐inchLEDboard5K 93075033
15‐inchLEDboards4K 93075034
26‐inchLEDboard4K 93075035
Drivers
95WD ri ve r120‐277V 93075036
50WD ri ve r 93075037
95WD ri ve r347‐480V 93075038
Lenses
15‐Inchdiffuse 93075043
26‐inchdiffus e 93075044
15‐inchmedium93075045
26‐inchmedium 93075046
15‐inchn a rrow 93075047
26‐inchn a rrow 93075048
15‐inchwide93075049
26‐inchwide 93075050
WireGuard
15‐inchfl at 93075051
26‐inchfl at 93075052
15‐inchRound 93075054
26‐inchRound 93075055
15‐inchfl at 93077270
26‐inchfl at 93077271
15‐inchRound 93077272
26‐inchRound 93077273
HHH REPLACEMENT PARTS
DimmingConnection
ColorCodeMatri x
HouseSupplyLeadColors Positive(+) Negative(‐)
Violet(positive+) Violet ‐
Gray(negative‐)‐Gray
Violet(positive+) Brown ‐
Gray(negative‐)‐Blue
FixtureDimmingCable
LeadColors
Alternate
Default
DIMMING CONNECTIONS BY COLOR CODE
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision C
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 1
SEE TABLE
BELOW
FIGURE 11
FIGURA 11
HHH (MODULAR HIGHBAY) - LOOSE DIMMING LEADS WIRING TO HOUSE SUPPLY
Item Service/ReplPartNr
(incl.packaging)
LightEngines
15‐inchLEDboards5K 93075032
26‐inchLEDboard5K 93075033
15‐inchLEDboards4K 93075034
26‐inchLEDboard4K 93075035
Drivers
95WD ri ve r120‐277V 93075036
50WD ri ve r 93075037
95WD ri ve r347‐480V 93075038
Lenses
15‐Inchdiffuse 93075043
26‐inchdiffuse 93075044
15‐inchmedium93075045
26‐inchmedium 93075046
15‐inchn a rrow 93075047
26‐inchn a rrow 93075048
15‐inchwide93075049
26‐inchwide 93075050
WireGuard
15‐inchflat 93075051
26‐inchflat 93075052
15‐inchRound 93075054
26‐inchRound 93075055
15‐inchflat 93077270
26‐inchflat 93077271
15‐inchRound 93077272
26‐inchRound 93077273
HHH REPLACEMENT PARTS
DimmingConnection
ColorCodeMatrix
HouseSupplyLeadColors Positive(+) Negative(‐)
Violet(positive+) Violet ‐
Gray(negative‐)‐Gray
Violet(positive+) Brown ‐
Gray(negative‐)‐Blue
FixtureDimmingCable
LeadColors
Alternate
Default
DIMMING CONNECTIONS BY COLOR CODE
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision C
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 1
SEE TABLE
BELOW
FIGURE 11
FIGURA 11
HHH (MODULAR HIGHBAY) - LOOSE DIMMING LEADS WIRING TO HOUSE SUPPLY
Item Service/ReplPartNr
(incl.packaging)
LightEngines
15‐inchLEDboards5K 93075032
26‐inchLEDboard5K 93075033
15‐inchLEDboards4K 93075034
26‐inchLEDboard4K 93075035
Drivers
95WD ri ve r120‐277V 93075036
50WD ri ve r 93075037
95WD ri ve r347‐480V 93075038
Lenses
15‐Inchdiffuse 93075043
26‐inchdiffus e 93075044
15‐inchmedium93075045
26‐inchmedium 93075046
15‐inchn a rrow 93075047
26‐inchn a rrow 93075048
15‐inchwide93075049
26‐inchwide 93075050
WireGuard
15‐inchfl at 93075051
26‐inchfl at 93075052
15‐inchRound 93075054
26‐inchRound 93075055
15‐inchfl at 93077270
26‐inchfl at 93077271
15‐inchRound 93077272
26‐inchRound 93077273
HHH REPLACEMENT PARTS
DimmingConnection
ColorCodeMatri x
HouseSupplyLeadColors Positive(+) Negative(‐)
Violet(positive+) Violet ‐
Gray(negative‐)‐Gray
Violet(positive+) Brown ‐
Gray(negative‐)‐Blue
FixtureDimmingCable
LeadColors
Alternate
Default
DIMMING CONNECTIONS BY COLOR CODE
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision C
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 1
SEE TABLE
BELOW
FIGURE 11
FIGURA 11
HHH (MODULAR HIGHBAY) - LOOSE DIMMING LEADS WIRING TO HOUSE SUPPLY
Item Service/ReplPartNr
(incl.packaging)
LightEngines
15‐inchLEDboards5K 93075032
26‐inchLEDboard5K 93075033
15‐inchLEDboards4K 93075034
26‐inchLEDboard4K 93075035
Drivers
95WD ri ve r120‐277V 93075036
50WD ri ve r 93075037
95WD ri ve r347‐480V 93075038
Lenses
15‐Inchdiffuse 93075043
26‐inchdiffus e 93075044
15‐inchmedium93075045
26‐inchmedium 93075046
15‐inchn a rrow 93075047
26‐inchn a rrow 93075048
15‐inchwide93075049
26‐inchwide 93075050
WireGuard
15‐inchfl at 93075051
26‐inchfl at 93075052
15‐inchRound 93075054
26‐inchRound 93075055
15‐inchfl at 93077270
26‐inchfl at 93077271
15‐inchRound 93077272
26‐inchRound 93077273
HHH REPLACEMENT PARTS
DimmingConnection
ColorCodeMatri x
HouseSupplyLeadColors Positive(+) Negative(‐)
Violet(positive+) Violet ‐
Gray(negative‐)‐Gray
Violet(positive+) Brown ‐
Gray(negative‐)‐Blue
FixtureDimmingCable
LeadColors
Alternate
Default
DIMMING CONNECTIONS BY COLOR CODE
HHH (MODULAR HIGHBAY)
INSTALLATION INSTRUCTIONS
Hubbell Lighting, Inc. Doc. No. 93062486
A subsidiary of Hubbell Incorporated Revision C
701 Millennium Drive • Greenville, SC 29607 Phone (864) 678-1000
Industrial Lighting
®
PAGE 1
SEE TABLE
BELOW
FIGURE 11
FIGURA 11
HHH (MODULAR HIGHBAY) - LOOSE DIMMING LEADS WIRING TO HOUSE SUPPLY
Item Service/ReplPartNr
(incl.packaging)
LightEngines
15‐inchLEDboards5K 93075032
26‐inchLEDboard5K 93075033
15‐inchLEDboards4K 93075034
26‐inchLEDboard4K 93075035
Drivers
95WD ri ve r120‐277V 93075036
50WD ri ve r 93075037
95WD ri ve r347‐480V 93075038
Lenses
15‐Inchdiffuse 93075043
26‐inchdiffuse 93075044
15‐inchmedium93075045
26‐inchmedium 93075046
15‐inchn a rrow 93075047
26‐inchn a rrow 93075048
15‐inchwide93075049
26‐inchwide 93075050
WireGuard
15‐inchflat 93075051
26‐inchflat 93075052
15‐inchRound 93075054
26‐inchRound 93075055
15‐inchflat 93077270
26‐inchflat 93077271
15‐inchRound 93077272
26‐inchRound 93077273
HHH REPLACEMENT PARTS
DimmingConnection
ColorCodeMatrix
HouseSupplyLeadColors Positive(+) Negative(‐)
Violet(positive+) Violet ‐
Gray(negative‐)‐Gray
Violet(positive+) Brown ‐
Gray(negative‐)‐Blue
FixtureDimmingCable
LeadColors
Alternate
Default
DIMMING CONNECTIONS BY COLOR CODE

WIRING DIAGRAMS
Hubbell Lighting, Inc.
A subsidiary of Hubbell Incorporated
701 Millennium Drive • Greenville, SC 29607
Industrial Lighting
®
PAGE 6
HHH WIRING DIAGRAMS
Doc. No. 93062486
Revision A
Phone (864) 678-1000
GROUND
GREEN
LINE
(HOT) BLACK
COMMON
(NEUTRAL) WHITE
BLACK
WHITE
RED
FUSING
FUSING
SINGLE FUSE
OPTION
DOUBLE FUSE
OPTION
SURGE
SUPPRESSOR
HHH MODULAR LOWBAY HIGH OUTPUT ASSEMBLY
WIRING DIAGRAM "LOWBAY QUAD"
HHH-xK-LB-HO
WIHUBB OPTION
(ETO ONLY)
OCCUPANCY SENSOR
(OCS) OPTION
CONTROL SENSOR (WST)
(ETO ONLY)
WIRELESS CONTROL DEVICE
(WIS) OPTION
+
-
+
-
+
-
DC INPUT
PANEL CONNECTOR
LIGHTBAR
DC OUTPUT
PANEL CONNECTOR
FROM DRIVER MDL
INTERCONNECT CORDSET ASSY
90° HEAD BOTH ENDS - MALE PINS ON
DRIVER OUTPUT, FEMALE END TOWARDS LIGHTBAR)
WHITE
BLACK
DRVR
DRVR
BRWN
BLUE
BRWN
BLUE
BRWN
BLUE
BRWN
BLUE
RED
BLUE
RED
BLUE
RED
BLUE
RED
BLUE
WHITE
BLACK
WHITE
BLACK
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K
GREEN
BLACK
WHIT E
Hubbell Lighting, Inc.
A subsidiary of Hubbell Incorporated
701 Millennium Drive • Greenville, SC 29607
Industrial Lighting
®
PAGE 5
HHH WIRING DIAGRAMS
Doc. No. 93062486
Revision A
Phone (864) 678-1000
GROUND
GREEN
LINE
(HOT) BLACK
COMMON
(NEUTRAL) WHITE
BLACK
WHITE
RED
R
E
D
W
H
T
B
L
K
FUSING
FUSING
SINGLE FUSE
OPTION
DOUBLE FUSE
OPTION
SURGE
SUPPRESSOR GREEN
BLACK
WHITE
HHH MODULAR LOWBAY MEDIUM OUTPUT ASSEMBLY
WIRING DIAGRAM "LOWBAY TRIO"
HHH-xK-LB-MO
WIHUBB OPTION
(ETO ONLY)
OCCUPANCY SENSOR
(OCS) OPTION
CONTROL SENSOR (WST)
(ETO ONLY)
WIRELESS CONTROL DEVICE
(WIS) OPTION
+
-
+
-
+
-
DC INPUT
PANEL CONNECTOR
LIGHTBAR
DC OUTPUT
PANEL CONNECTOR
FROM DRIVER MDL
INTERCONNECT CORDSET ASSY'S
90° HEAD BOTH ENDS - MALE PINS ON
DRIVER OUTPUT, FEMALE END TOWARDS LIGHTBAR)
WHITE
BLACK
DRVR
DRVR
BRWN
BLUE
BRWN
BLUE
BRWN
BLUE
RED
BLUE
RED
BLUE
RED
BLUE
WHITE
BLACK
WHITE
BLACK
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K

WIRING DIAGRAMS
Hubbell Lighting, Inc.
A subsidiary of Hubbell Incorporated
701 Millennium Drive • Greenville, SC 29607
Industrial Lighting
®
PAGE 7
HHH WIRING DIAGRAMS
Doc. No. 93062486
Revision A
Phone (864) 678-1000
GROUND
GREEN
LINE
(HOT) BLACK
COMMON
(NEUTRAL) WHITE
BLACK
WHITE
RED
FUSING
FUSING
SINGLE FUSE
OPTION
DOUBLE FUSE
OPTION
SURGE
SUPPRESSOR
HHH MODULAR HIGHBAY LOW OUTPUT ASSEMBLY
WIRING DIAGRAM "HIGHBAY TWIN"
HHH-xK-HB-LO
WIHUBB OPTION
(ETO ONLY)
OCCUPANCY SENSOR
(OCS) OPTION
CONTROL SENSOR (WST)
(ETO ONLY)
WIRELESS CONTROL DEVICE
(WIS) OPTION
+
-
+
-
DC INPUT
PANEL CONNECTOR
LIGHTBAR
DC OUTPUT
PANEL CONNECTOR
FROM DRIVER MDL
INTERCONNECT CORDSET ASSY
90° HEAD BOTH ENDS - MALE PINS ON
DRIVER OUTPUT, FEMALE END TOWARDS LIGHTBAR)
WHITE
BLACK
DRVR
DRVR
BRWN
BLUE
BRWN
BLUE
RED
BLUE
RED
BLUE
WHITE BLACK
WHITE
BLACK
WHITE
BLACK
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K
GREEN
BLACK
WHITE
Hubbell Lighting, Inc.
A subsidiary of Hubbell Incorporated
701 Millennium Drive • Greenville, SC 29607
Industrial Lighting
®
PAGE 8
HHH WIRING DIAGRAMS
Doc. No. 93062486
Revision A
Phone (864) 678-1000
GROUND
GREEN
LINE
(HOT) BLACK
COMMON
(NEUTRAL) WHITE
BLACK
WHITE
RED
FUSING
FUSING
SINGLE FUSE
OPTION
DOUBLE FUSE
OPTION
SURGE
SUPPRESSOR
HHH MODULAR HIGHBAY MEDIUM OUTPUT ASSEMBLY
WIRING DIAGRAM "HIGHBAY TRIO"
HHH-xK-HB-MO
WIHUBB OPTION
(ETO ONLY)
OCCUPANCY SENSOR
(OCS) OPTION
CONTROL SENSOR (WST)
(ETO ONLY)
WIRELESS CONTROL DEVICE
(WIS) OPTION
+
-
+
-
+
-
DC INPUT
PANEL CONNECTOR
LIGHTBAR
DC OUTPUT
PANEL CONNECTOR
FROM DRIVER MDL
INTERCONNECT CORDSET ASSY
90° HEAD BOTH ENDS - MALE PINS ON
DRIVER OUTPUT, FEMALE END TOWARDS LIGHTBAR)
DRVR
DRVR
DRVR
BRWN
BLUE
BRWN
BLUE
BRWN
BLUE
RED
BLUE
RED
BLUE
RED
BLUE
WHITE BLACK
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K
GREEN
BLACK
WHITE

WIRING DIAGRAMS
Hubbell Lighting, Inc.
A subsidiary of Hubbell Incorporated
701 Millennium Drive • Greenville, SC 29607
Industrial Lighting
®
PAGE 9
Doc. No. 93062486
Revision A
Phone (864) 678-1000
WHITE
HHH-xK-LB-LO & HHH-xK-HB-LO UNITS
CENTERED ON RAIL
NOMINAL YOKE INSTALL POSITION BY FIXTURE TYPE:
Final installation position may vary to balance fixture in positiom
HHH-xK-LB-MO & HHH-xK-HB-MO UNITS
POSITIONED AS SHOWN OVER FIRST LIGHTBAR
HHH-xK-LB-HO & HHH-xK-HB-HO UNITS
CENTERED ON RAIL
7.2
6.4 10.1
HIL_0137_HHH_INST
Hubbell Lighting, Inc.
A subsidiary of Hubbell Incorporated
701 Millennium Drive • Greenville, SC 29607
Industrial Lighting
®
PAGE 9
HHH WIRING DIAGRAMS
Doc. No. 93062486
Revision A
Phone (864) 678-1000
GROUND
GREEN
LINE
(HOT) BLACK
COMMON
(NEUTRAL) WHITE
BLACK
WHITE
RED
FUSING
FUSING
SINGLE FUSE
OPTION
DOUBLE FUSE
OPTION
SURGE
SUPPRESSOR
HHH MODULAR HIGHBAY HIGH OUTPUT ASSEMBLY
WIRING DIAGRAM "HIGHBAY QUAD"
HHH-xK-HB-HO
WIHUBB OPTION
(ETO ONLY)
OCCUPANCY SENSOR
(OCS) OPTION
CONTROL SENSOR (WST)
(ETO ONLY)
WIRELESS CONTROL DEVICE
(WIS) OPTION
+
-
+
-
+
-
+
-
DC INPUT
PANEL CONNECTOR
LIGHTBAR
DC OUTPUT
PANEL CONNECTOR
FROM DRIVER MDL
INTERCONNECT CORDSET ASSY
90° HEAD BOTH ENDS - MALE PINS ON
DRIVER OUTPUT, FEMALE END TOWARDS LIGHTBAR)
WHITE BLACK
DRVR
DRVR
DRVR
DRVR
BRWN
BLUE
BRWN
BLUE
BRWN
BLUE
BRWN
BLUE
RED
BLUE
RED
BLUE
RED
BLUE
RED
BLUE
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K
R
E
D
W
H
T
B
L
K
GREEN
BLACK
WHITE
Table of contents
Popular Work Light manuals by other brands

Milwaukee
Milwaukee M18 RADIUS COMPACT SITE LIGHT WITH FLOOD... Operator's manual

TOOLCRAFT
TOOLCRAFT 2481635 operating instructions

TECH LIGHT
TECH LIGHT SL-2858 user manual

Normfest
Normfest SL 550 operating instructions

SpeedTech Lights
SpeedTech Lights W-DCC20 instruction manual

Philips
Philips Xitanium Xitanium Brochure & specs