Hubbell LX Series Manual

TROUBLE SHOOTING
•“EXIT” legend does not illuminate
• Check wiringconnections.
•Emergency circuit does not work
• Batteriesareshippedunchargedanddisconnected.Connectpowerpackleadsandchargebeforetesting.
• Makesurechargerboardisproperlyseated.
• Checkwiringconnections.
MAINTENANCE
SignsshouldbetestedandmaintainedinaccordancewithNationalElectricalCodeandNFPA101LifeSafetyCoderequirements.Itisrecommendedthatemergencyexitsignsbetestedfor30seconds
onceamonthandfor90minutesonceayear.
RECYCLING INFORMATION
Allthermoplasticpartsarerecyclable.
Allcartonscontainrecycledmaterials.
Pleaserecycleresponsibly.
NOTICE:
Emergency model exit signs contain rechargeable nickel-cadmium batteries which must be recycled or disposed of properly.
LX Series
Thermoplastic LED Exit Sign
Installation, Operation and Maintainance Instructions
Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com
Copyright©HubbellLighting,Inc.,AllRightsReserved•Specificationssubjecttochangewithoutnotice.•PrintedinU.S.A. 93028841B 6/10
IMPORTANT SAFEGUARDS
Whenusingelectricalequipment,basicsafetyprecautionsshouldalwaysbefollowedincludingthefollowing.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.Donotuseoutdoors.
2.Donotletpowersupplycordstouchhotsurfaces.
3.Donotmountneargasorelectricheaters.
4.Equipmentshouldbemountedinlocationsandatheightswhereitwillnotreadilybesubjecttotamperingby
unauthorizedpersonnel.
5.Theuseofaccessoryequipmentnotauthorizedbythemanufacturermaycauseanunsafecondition.
6.Donotusethisequipmentforotherthanitsintendedpurpose.
7.Servicingofthisequipmentshouldbeperformedbyqualifiedservicepersonnel.
8.Testcycling:theLifeSafetyCode(NFPA101)requirestestingofemergencyexitsignsonceamonthfora
minimumof30secondsandonceayearforaminimumof90minutes.
INSTALLER:
•SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS
•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT
WARNING–ThisproductcontainschemicalsknowntotheStateofCaliforniatocausecancer,birthdefectsand/orotherreproductiveharm.
Thoroughlywashhandsafterinstalling,handling,cleaning,orotherwisetouchingthisproduct.
93028961
OPERATION
“ACON”LEDisiluminatedwhenACpowerispresent.
NOTE:AllmodelsaresuppliedwithanACLockoutcircuit,whichpreventsthe“EXIT”legendfromilluminatingwhenthebatteryisconnectedandnoACpowerispresent.
NOTE:AllmodelsaresuppliedwithaLowVoltageDisconnectcircuit,whichpreventsdamagetothebatteryfromdeepdischargeduringprolongedemergencyoperation.
NOTE:Batteriesareoftenshippedinadischargedstate–thisisnormal.Thebatterywillrequirecharging.Allowseveralhoursofchargebeforetestingtheunit.
ModelsWithSPECTRON®Self-Testing/Self-DiagnosticCircuitry
ModelsequippedwiththeSpectronself-testing/self-diagnosticelectronicssystemprovide:
■Visual indication of AC power status ■Visual indication of self-diagnostic test cycle
—Visual indication of any unit malfunctions including—
■Battery fault ■Transfer Fault ■Charger fault ■Emergency Lamp fault
Spectron equipped units also include:
Brownoutprotection:unitwillautomaticallytransfertoemergencyoperationupondetectionoflowACpower(approximately80%ofnominalline).
TimeDelayRetransfer:uponreturnofnormalACpower,unitwillremainintheemergencymodeforanadditional15minutestoallowACpowertostabilize.
LED Status Indicator
AbicolorLED(green/red)isprovidedonthecontrolpanelofallmodelsequippedwiththeSpectron
option.
Red Status Indicator Code Description
OneblinkON/pause Batterynotconnected
TwoblinksON/pause Batteryfault
ThreeblinksON/pause Chargerfault
FourblinksON/pause Transfercircuitfault
FiveblinksON/pause EmergencyLampfault
Automatic Tests
Theunitwillautomaticallyinitiateaself-test/self-diagnosticcyclebased
onthefollowingtable:
Testing Period Duration of Test
Onceamonth 1minute
Onceevery6months Alternating:
30minutesor60minutes
Manual Tests
Usingtheunittestswitch,userscaninitiatedifferentdurationtestcycles
basedonthefollowingtable:
Initiating Action Test Cycle
Presstestswitchonce 1minute
Presstestswitchtwice 90minutes
Pressingthetestswitchatanytimeafteratestcyclehasbeguncancels
theremainderofthetestandreturnstheunittonormaloperation.
RedServiceAlertIndicator
Undernormaloperatingconditions,theredServiceAlertIndicatorwillremain“off”.Intheevent
theSpectroncontrollerdetectsamalfunction,theredServiceAlertIndicatorwillblinkata1Hz.
rate,basedonthefollowingtable:
GreenOperatingStatusIndicator
ThegreenOperatingStatusIndicatorservesasbothanACpowerandaself-testindicator.During
normaloperation,thegreenOperatingStatusIndicatorwillbeilluminated,indicatingthepresence
ofACpower.Duringallautomaticormanualself-testcycles,thegreenOperatingStatusIndicator
willblinkata1Hz.rate.
MAINTENANCE
93028961
93028963
93029014
93029019
93029025
93029029

END MOUNT
Makeconnectionsusingquickconnectorsprovided
andinsertconnectorsincaptureslots.
(SeedetailA)
IMPORTANT:Routewiresthroughtop
openingincanopyforeaseofwiring.
Usepre-tinnedpigtailleads
providedforACinputtosign.
ACtransformer.
120VAC-connectblackandwhiteleads
277VAC-connectredandwhiteleads
Storeunusedleadin
transformercompartment.
*Foremergencymodels-
plug2-pinbattery
connectorintoPCboard.
Chargerboard
and
batterypack.
(Emergency
modelsonly*)
93029014
Routewiresinchannel
asshown.
INSTALLATION INSTRUCTIONS
IMPORTANT:Optionconnectionwiresmustberunbeforesignhousingis
attachedtocanopy.
FIRE ALARM PANEL (-FAP) OPTION
FAPoptionconnectsto24voltACorDC(purplewires).
FlashRate:.5secondson,.5secondsoff.
DC REMOTE (-DC) OPTION
DCRemoteoptionconnectsto6-24voltDC[yellow(–),blue(+)].
FLASHER MODULE (-FM) OPTION
EmergencyModeFlashRate:.5secondson,.5secondsoff.
AUDUBLE/FLASHER MODULE (-AF) OPTION
EmergencyModeBeep/FlashRate:.5secondson,.5secondsoff.
Connectoptionwires(-FAP
or-DC)togreyconnectoron
optionboard.
Routewiresthrough
transformercompartmentand
outcanopyorbackplate.
93029029
DUAL CIRCUIT (-2C) OPTION
Dual-circuittransformer
secondarywiresconnect
toinputconnector
onoptionboard.
Connectdual-circuitprimarytransformer
wirestoutilitysource.
120VAC-connectblackandwhiteleads.
277VAC-connectredandwhiteleads.
93029025
WALL MOUNT
Routewiresinchannelasshown.
Storeunusedleadin
transformercompartment.
Makeconnectionsusingquick
connectorsprovidedandinsert
connectorsincaptureslots.
(SeedetailA)
Selectappropriateknockouts
forwallbox.
ACtransformer.
120VAC-connectblackandwhiteleads.
277VAC-connectredandwhiteleads
Usepre-tinned
pigtailleads
providedforAC
inputtosign.
Chargerboard
and
batterypack.
(Emergencymodelsonly*)
*Foremergencymodels-
plug2-pinbattery
connectorintoPCboard.
93028963
CEILING MOUNT
ACtransformer.
120VAC-connectblackandwhiteleads.
277VAC-connectredandwhiteleads
Usepre-tinnedpigtailleads
providedforACinputtosign.
Routewires
throughlarge
holeatsnap.
Makeconnectionsusingquick
connectorsprovidedandinsert
connectorsincaptureslots.
(SeedetailA)
Routewiresin
channelasshown.
Storeunusedleadsin
transformercompartment.
Chargerboard
and
batterypack.
(Emergency
modelsonly*)
IMPORTANT: Routewiresthroughtop
openingincanopyforeaseofwiring.
*Foremergencymodels-
plug2-pinbattery
connectorintoPCboard.
93029019
93029019
Other Hubbell Work Light manuals
Popular Work Light manuals by other brands

Chicago Electric
Chicago Electric 94761 operating instructions

NANLITE
NANLITE PavoTube II 6C user manual

Underwater Kinetics
Underwater Kinetics UK3AA instructions

Dewenwils
Dewenwils HLFL01B instruction manual

Metabo HPT
Metabo HPT UB18DB Safety instructions and instruction manual

Kartell
Kartell Taj Mini manual