Hunterstoves Group Parkray ASPECT 80B User manual

1
ASPECT 80B WOODBURNING
CENTRAL-HEATING STOVE
Instructions for:
Installation/Operating/Maintenance/Servicing
JINPA22W REV C 06/06/2019

2
STOVE MODEL
ASPECT 80B
CVSPA80BWB/CVSPA80BWS

3
CONTENTS INDEX:
STOVE MODELS………………………………………………………………………………………………… 2
TECHNICAL SPECIFICATION………………………………………………………………………………. 4
IMPORTANT INFORMATION…………………………………………………………………………….. 5/6
SAFETY…………………………………………………………………………………………………………….. 6
REMOVE INTERNAL COMPONENTS………………………………………………………………….. 7/8
ASSEMBLY INSTRUCTIONS……………………………………………………………………………….. 8/9
APPLIANCE DIMENSIONS…………………………………………………………………………………. 9
PRE INSTALLATION REQUIREMENTS……………………….……………………………………….. 9/10
LEGAL REQUIREMENTS……………………………………………………………………………………. 10/11
CLEARANCES……………………………………………………………………………………………………. 11/12
INSTALLATION OF BOILER MODELS………………………………………………………………….. 12-14
COMMISSIONING AND HANDOVER…………………………………………………………………. 15
OPERATING INSTRUCTIONS…………………………………………………………………………….. 16-18
MAINTENANCE &SERVICING………………………………………………………………………….. 18-20
TROUBLESHOOTING……………………………………………………………………………………….. 21/22
SPARES……………………………………………………………………………………………………………. 23
COMMISSIONING &INSTALLATION CHECK LIST………………………………………………. 24
SERVICE RECORDS…………………………………………………………………………………………… 25
FULL WARRANTY INFORMATION…………………………………………………………………….. 26/27
Welcome to the Hunter Stoves family and thank you for purchasing a
Parkray Aspect stove. This stove was designed and built to be a high
performance heating appliance, and we hope it will bring you great
enjoyment. The natural environment is important to us, so our stoves are
manufactured to provide you with a clean and efficient burn that will keep
you warm through cold winter nights.

4
Technical Specification
GENERAL
Aspect 80B
Energy Efficiency Class
Wood
Nominal Heat Output
Wood
16.5kW
Energy Efficiency
EEI
95
Output to Water
Wood
11.3 kW
Output to Room
Wood
5.2kW
Efficiency
Wood
71.9%
Mean CO (@13% O₂)
Wood
0.23%
Appliance Mass
Wood
181kg
Recommended Fuels
Wood
Seasoned Wood (less than 20%
moisture content)
Log Length
350mm
FLUES
Mean Flue Gas Temperature
Wood
358°C
Flue Gas Mass Flow
Wood
15.2g/s
Flue Outlet Size (Top or Rear Option)
Wood
178mm
VENTILATION
-Where leakage is greater
than 5m³/hour/m²
-Ventilation normally
required = 550mm² per kW
output over 5kW
6325mm²
-Where leakage is less than or
equal to 5m³/hour/m²
-Ventilation normally
required = 550mm² per kW
output
9075mm²
For further information on ventilation please refer to Building Regulations Document J or your installer.

5
General Guidance
It is important that your stove is correctly installed and operated as Hunter Stoves Group cannot accept
responsibility for any fault arising through incorrect installation, use, maintenance or servicing.
These instructions cover the basic principles to ensure satisfactory installation of the stove, although detail may
need slight modification to suit particular local site conditions.
The installation must comply with current Building Regulations, National and European Standards, Local Authority
Byelaws and other specifications or regulations as they affect the installation of the appliance.
The Building Regulations requirements may also be met by adopting the relevant recommendations in the current
issues of British Standards BS 8303 and BS EN 15287-1.
Only use approved fuels on this appliance. Information about this can be found on Page 18.
This is a Domestic Appliance and must only be used in accordance with these instructions. Do not place articles that
are affected by high temperatures on, or near, this appliance. Do not place furniture or other items within 1 metre
of the front of this appliance. See the note on material clearances on pages 11/12.
Fitting a stove in a room which also contains an extractor fan and/or cooker hood should be avoided where
possible. If this is unavoidable, the suitability of the space for fitting this appliance must be decided at the discretion
of a qualified installer, and a flue draught interference test must be performed.
Do not obstruct the ventilation required for the safe use of this appliance.
Competent Persons Scheme
Hunter Stoves Group recommend that this stove is installed by a member of an accredited competent persons
scheme e.g. HETAS.
If the installer is not a member of a competent person’s scheme, it is a legal requirement, in the UK, to notify your
Local Building Control Officer in advance of any installation work starting.
Health and Safety Precautions
Special care must be taken when installing the stove such that the requirements of the Health and Safety at Work
Act are met.
Handling
This appliance is very heavy. Adequate facilities must be available for loading, unloading and site handling.
Fire Cement
Some types of fire cement are caustic and should not be allowed to come into contact with the skin. In case of
contact, wash immediately with plenty of water.
Asbestos
This stove contains no asbestos. If there is a possibility of disturbing any asbestos in the course of installation, then
please seek specialist guidance and use appropriate protective equipment.
PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION AND OPERATION. KEEP THESE
INSTRUCTIONS IN A SAFE PLACE FOR FUTURE REFERENCE AND SERVICING.
THIS APPLIANCE WILL BECOME VERY HOT WHEN USED IN ACCORDANCE WITH THESE INSTRUCTIONS,
HUNTER STOVES RECOMMEND THAT AN APPROVED GUARD IS USED TO PROTECT THE YOUNG, ELDERLY
OR INFIRM FROM HARM.
THE INSTALLER COMMISSIONING SHEET CAN BE FOUND ON THE BACK COVER. PLEASE ENSURE THAT IT IS
COMPLETED PRIOR TO USE.

6
Metal Parts
When installing or servicing this stove, care should be taken to avoid the possibility of personal injury.
Modification
No unauthorised modification of this appliance should be carried out.
Safety
WARNING –This appliance will be hot when in operation and due care should be taken. The supplied operating tool
or glove may be used to open the door and operate the air controls.
Aerosols
Do not use an aerosol spray on or near the stove when it is alight.
Fireguards
Always use a fireguard in the presence of children, the elderly or the infirm. The fireguard should be manufactured
in accordance with BS8423 –Fireguards for use with solid fuel appliances.
Do Not Over-Fire
It is possible to fire the stove beyond its design capacity. This could damage the stove so watch for signs of over-
firing. If any part of the stove starts to glow red, the stove is in an over-fire situation and the controls should be
adjusted accordingly.
Never leave the stove unattended for long periods without first adjusting the controls to a safe setting.
Careful air supply control should be exercised at all times.
Fume Emission
Properly installed and operated, this appliance will not emit fumes. Occasional fumes from de-ashing and refuelling
may occur. Persistent fume emission must not be tolerated.
This appliance should not be operated with the door open.
If fume emission persists, then the following immediate action should be taken: -
➢Open doors and windows to ventilate the room.
➢Let the fire go out, or eject and safely dispose of fuel from the appliance.
➢Check for flue/chimney blockage and clean if required.
➢Do not attempt to re-light the fire until the cause of the fume emission has been identified and corrected.
If necessary, seek expert advice.
Adverse Weather
In a small number of installations, occasional local weather conditions (e.g. wind from a particular direction) may
cause downdraught in the flue and cause the stove to emit fumes. In these circumstances, the stove should not be
used. A professional flue installer will be able to advise on solutions to this problem (e.g. anti-downdraught cowl).
Carbon Monoxide Detector
Hunter Stoves Group recommend a Carbon Monoxide Detector that conforms to the latest issue of BS EN 50292 is
placed in the same room as the appliance. The installation of such an alarm is not considered as a substitute for
regular maintenance or servicing or the appliance and Flue system.
IN THE EVENT OF A CHIMNEY FIRE:
➢Raise the alarm
➢Call the Fire Brigade
➢Close appliance air controls
➢Move furniture, ornaments etc. away
➢Place a fireguard in front of stove
➢Check the chimney breast for signs of excessive heat.
If the wall is becoming excessively hot, move furniture away.
Ensure the Fire Brigade can gain access to your roof space in order to check for fire spread.

7
Removing Internal Components
All internal components must be removed prior to fitting the stove. This will make handling the stove easier; allow
access to fixings and the flue outlet; as well as protect the internal components from damage during the installation
process.
Log Retainer
Open the door and remove the log retainer. Lift the right-hand edge up until the log retainer is free and then lift it
out of the stove.
Base Bricks
Lift the front edge of the centre base brick up and remove the brick from the stove. Slide the left-hand base brick
towards the centre of the stove and lift out. Repeat with the right-hand base brick.
Side Bricks
Remove the left-hand side brick by sliding the front edge of it towards the centre of the stove and then removing it.
Repeat with the right-hand side brick.

8
Ignition Air Bar
Remove the ignition air bar by simply lifting it out of the stove.
Baffle
Lift the baffle up (1) and slide it to the left (2) and then lower the right-hand side of it down into the firebox (3) and
remove from the stove.
STOVE ASSEMBLY
Flue Collar
Top or rear flue outlet Place the flue collar gasket on the Wind the four M6 studs supplied
outlet to be used into the fixing holes in the flue
collar until finger tight. Place
the flue collar onto the stove
and tighten using the supplied
washers and nuts from inside
the stove.

9
Place the gasket on the unused outlet and put the blanking plate on top of this. Wind the four M6 studs supplied
into the fixing holes until finger tight. Place the plate onto the stove and tighten using the supplied washers and nuts
from inside.
Appliance Dimensions
Pre-Installation Requirements
PLEASE CHECK THE FOLLOWING:
Any existing chimney/flue system must be confirmed as suitable for this appliance as defined in Building
Regulations Document J. It must be swept and inspected, by a competent person (see notes), to confirm that it
is structurally sound and free from cracks and obstructions.
The diameter of the Flue should not be less than Ø175mm and not more than Ø230mm. Do not connect to
systems that have large voids or spaces. If any of these requirements are not met, the chimney should be lined
by a suitable method.
If the chimney is suspected of previously serving an open fire it must be swept again, within a month of regular
use, to clear any soot that may have been dislodged due to the variation in combustion levels and higher flue
gas temperature levels. The chimney/flue system exit must comply with Building Regulations Document J. The
minimum height and position should terminate in accordance with Table 1.
Connection to the Chimney
An existing fireplace opening can be bricked up or sealed with a register plate. A short length of flue pipe of
minimum 175mm internal diameter may then be used to connect the stove to the chimney. This flue pipe
should be made of 316 grade stainless steel or vitreous enamelled steel, nominal thickness 1.2mm. Ensure that
the pipe end is no closer than 76mm to the chimney walls. The length of any horizontal run of flue pipe must
not exceed 125mm. It is essential that all connections between the stove and chimney-flue are sealed and
made airtight.

10
Make provision to access the chimney/flue system for cleaning and the removal of debris. If there is no
existing chimney then either a prefabricated block chimney in accordance with Building Regulations Approved
Document J, or a twin-walled insulated stainless-steel flue to BS4543 can be used. These chimneys must be
fitted in accordance with the manufacturer’s instructions and Building Regulations. New masonry and flue
block chimneys must meet the requirements of Building Regulations Document J. Any connecting flue pipe
systems must also meet these regulations.
Please check the suitability of the fireplace and/or surround for use with this appliance before installing it. If
you have any doubts about the suitability of your chimney, consult your local Dealer/Stockist or Installation
Engineer. Both the chimney and flue pipe must be accessible for cleaning and if ANY part of the chimney
cannot be reached through the stove (with baffle removed), a soot door must be fitted in a suitable position.
Flue Outlet Positions (Document J):
A full copy of Document J can be found here:
http://www.planningportal.gov.uk/uploads/br/BR_PDF_ADJ_2010.pdf
Legal Requirements
Hunter Stoves Group requests that before installation and/or use of this appliance that you read these
instructions carefully to ensure that all the relevant requirements are fully understood.
These instructions cover the basic principles to ensure satisfactory installation of the stove, although detail
may need slight modification to suit particular local site conditions. In all cases the installation must comply
with current Building Regulations, Local Authority Byelaws, European and National Standards and other
specifications or regulations as they affect the installation of the stove.
It should be noted that the Building Regulations requirements may be met by adopting the relevant
recommendations given in British Standards BS 8303, BS 6461 and BS 7566 as an alternative means to achieve
an equivalent level of performance to that obtained following the guidance given in Approved Document J.
Your local Building Control Officer can advise you regarding the interpretation of the Regulations should there
be any questions. This appliance must be installed by a Registered Installer (see Competent Persons Scheme)
or approved by your local Building Control Officer.
All works undertaken must be carried out with due care and attention to meet the requirements of the Health
& Safety code of practice and any other legislation that may have been introduced since the publication of
these instructions.
Position on Roof
Clearances to flue exit
A
At or within
600mm of the ridge
At least 600mm
above the ridge
B
Elsewhere on a roof
(Pitched or Flat)
At least 2.3 M horizontally from the
nearest point on the weather
surface and:
a) At least 1.0 M above the highest
point of intersection between the
chimney and weather surface; or
b)at least as high as the ridge
C
Below (on a pitched roof)
or within 2.3 M horizontally
to an opening window or
dormer
At least 1.0 M above the top of the
opening
D
Within 2.3 M of an
adjoining or adjacent
building, whether or not
beyond the boundary
At least 600mm above any part of
the adjacent building within 2.3 M
Table 1

11
Competent Persons Scheme
Members of the following schemes may self-certify the installation of this stove. If the installer is not a
member of one of these schemes, your local Building Control Department must approve the installation.
Scheme
Web address
Telephone
APHC (Association of Plumbing and
Heating Contractors (Certification)
Limited
www.aphc.co.uk
02476 470 626
Building Engineering Services
Competence Accreditation (BESCA
Limited)
www.hvca.org.uk / www.besca.org.uk
0800 652 5533
HETAS Ltd (Heating Equipment Testing
and Approval Scheme)
www.hetas.co.uk
01462 634721
NAPIT Registration Ltd
www.napit.org.uk
0870 444 1392
NICEIC Group Ltd
www.niceic.org.uk
0800 013 0900
Air Supply
The room or space containing this appliance does need a permanent, unobstructed air opening of at least
6,325mm². If a draught stabiliser is fitted, the air opening should be at least 10,700mm². Due consideration
should be given to air requirements for any other appliance in the same room or space. Any air opening must
be kept clear from blockage or obstruction.
HEARTH/MATERIAL CLEARANCES
Hearth constructions must comply with the current building regulations.
Your stove must be installed on a floor with adequate load-bearing capacity, otherwise suitable measures
should be taken.
If the existing construction does not meet this pre-requisite, suitable measures (e.g. load distributing plate)
should be put in place.
Care should be taken to level the stove using the adjusting screws in the feet.
MATERIAL CLEARANCES
COMBUSTIBLE MATERIAL
Minimum Distances to Combustible Material
Behind the stove
175mm
At the side of the stove
200mm
In front of the stove
900mm
**Note:
Combustible material refers to any material that will degrade when subjected to heat e.g. plaster.

12
NON COMBUSTIBLE -FIREPLACE RECESS
INSTALLATION OF BOILER MODELS
We strongly recommend that a knowledgeable, experienced and qualified plumbing and heating
engineer is responsible for the design and installation of the heating and hot water system. Hunter Stoves
Group cannot accept responsibility for any consequential loss, however caused, due to under or over
specification of the appliance in any installation.
Do Not –Under any circumstances connect the stove to a sealed (pressurised)heating system or unvented hot
water cylinder.
Do Not –Link the stove into a heating or hot water system with an existing boiler without the use
of suitable equipment such as a neutraliser. When fitting this type of system, the neutraliser manufacturer’s
instructions must be followed.
Do –Fit an open cold feed and expansion cistern with separate cold feed and vent pipes. The cold feed and
vent pipes must be unvalved. The open vent pipe should have a diameter of 22mm and rise continuously from
the boiler. It is common practice to form the vent pipe from an extension of the primary flow (see diagram).
Do –Connect the stove to a double feed, indirect hot water cylinder via 28mm copper flow and return
pipework, rising continuously from the boiler to the cylinder. The cylinder and heat leak radiator must be sited
higher than the stove.
Semi pumped systems should be used on heating and hot water systems with gravity circulation to the hot
water cylinder and one unvalved 2 KW radiator to act as a heat leak when the central heating is switched off.
All four tappings on wraparound boilers should be used for systems incorporating separate gravity and
pumped heating loops. Each flow and return should be taken from diagonally opposite sides of the boiler.
If a common flow and return is used, these should also be taken from diagonally opposite sides of a
wraparound boiler, and plugs inserted into the sockets not used.
Systems using a common flow and return to the boiler should incorporate an injector tee on the primary
return connection from the central heating pump (see diagram).
The stove can be recessed in a suitable sized
fireplace but must have a permanent free air gap
of at least 150mm on top and 50mm (although we
recommend 150mm) around the sides and 50mm
at the back of the stove to obtain maximum heat
output and for access to the rear of the stove.
The hearth should extend at least 300 mm from
the front of the stove. The stove should stand
wholly above a solid, non-combustible hearth, at
least 125 mm thick (this may include the thickness
of a solid floor or a non-combustible decorative
hearth.

13
A HIGH LIMIT thermostat should be fitted to the gravity flow pipe close to the boiler and set at 90°C. This
should override any pump control, switching the pump on and dissipating any excess heat around the radiator
circuit.
To prevent boiler corrosion due to condensation it is necessary to maintain the return water temperature
above 45°C. This can be achieved by the use of a LOW LIMIT thermostat on the return pipe from the hot water
cylinder, close to the boiler. The thermostat should make on temperature rise, preventing the circulating
pump from operating until the gravity circuit is up to temperature.
A corrosion inhibitor should be added to the system to ensure satisfactory performance and long system life.
Wiring Diagram for general guidance only
All electrical work must be carried out by a competent electrician in accordance with the rules in force and the
instructions provided by the circulating pump and heating controls manufacturer.

14
Four Tapping System
Two Tapping System
Room Thermostat
High Limit
Thermostat
90°C
Circulating Pump
Low Limit Thermostat (45°C)
Time Switch
Drain Cock
Room Thermostat
High Limit
Thermostat
90°C
Circulating Pump
Low Limit Thermostat (45°C)
Time Switch
Drain Cock Injector Tee

15
Commissioning & Handover
Appliance Check
Please check that all components are correctly assembled and working correctly.
Ensure the Air Controls are working correctly. Hunter Stoves Group recommend that you carry out a smoke
draw test to check the soundness of the chimney/flue system and seals:
Place a Smoke Pellet in the centre of the Grate, ensure that all of the Air Controls are fully open and close the
Door.
The smoke should now be drawn up the chimney and you should be able to see it exit from the chimney/flue
terminal.
We recommend that you do this test with all of the windows and doors, to the room where the appliance is
fitted, closed.
If there any adjoining room(s) that have an Extractor Fan fitted, open the adjoining door to ensure that the
chimney/flue system is not compromised when the fan is operating. If there is a ceiling fan fitted in the room,
please operate it and ensure that it does not affect the operation of the chimney/flue system.
If any of these tests fail, please re-check the suitability of the chimney/flue system together with the
ventilation.
A small fire can now be lit and allow the appliance to heat up slowly ensuring that no products of combustion
enter into the room.
Carry out a spillage test using a smoke match around the door opening.
If there is excessive spillage, please allow the appliance to cool and then re-check the chimney/flue system and
ventilation.
Do not run the stove at full output for at least 24 hours.
On completion of the commissioning:
Upon completion, allow a suitable period of time for any fire cement and mortar to dry out.
Please instruct the user on the safe operation of this appliance, how the controls work and basic maintenance
requirements.
Ensure that the operating instructions and appliance tools are left with the customer and the check lists have
been filled out correctly.
Please advise the customer on the correct use of the appliance with the fuels likely to be used on the stove
and warn them to use only the recommended fuels for the stove.
Advice the user on what to do should smoke or fumes be emitted from the stove.
The user should be warned to use a fireguard to BS 8423 in the presence of children, aged and/or infirm
persons.
Hunter Stoves Group also recommend that a CO alarm is fitted into the room where the appliance is located.
Flue Draught
If the draught exceeds the recommended maximum, a draught stabiliser must be fitted so that the rate of
burning can be controlled and to prevent over firing.
If the reading is less than the recommended minimum, then the performance of the appliance will be
compromised. The flue draught should be checked under fire at high output with windows and doors closed.
Minimum Draught –1.2mm Water Gauge
Maximum Draught –2.5mm Water Gauge

16
Operating Instructions
Read the ‘General Guidance’ Section at the start of these instructions before operating your stove for the
first time.
Allow sufficient clearance between the stove and pictures, plasma screen televisions or ornaments etc., as
these could be damaged and could potentially create a fire hazard (For more information read the ‘Material
Clearance’ section of these installation instructions).
WARNING –This appliance will be hot when in operation and due care should be taken. The supplied
operating tool or gloves may be used to open the door and operate the air controls.
Please Note
Your Building Insurance Company may require you to inform them of this new installation and that the work
has been carried out correctly. Please check your policy to ensure that it is still valid when this installation is
complete.
Using The Appliance For The First Time
When being heated up for the first time, smells and fumes are often produced. This is a normal chemical
process that allows the specialist heat resistant paint to cure and harden.
Please arrange for good ventilation of the room. Open windows and doors and if necessary, use a ventilator
for fast interchange of air. Heat up to operation temperature for at least one hour. If maximum temperature
is not achieved after heating up, release of odour may appear later.
Aerosols
Do not use an aerosol spray on or near the stove when it is alight.
Air Control
This stove has been designed to burn far more efficiently than a traditional stove if used correctly, with the
obvious notable feature of CLEAN GLASS.
It is essential that the stove has an adequate air supply for combustion and ventilation.
The air intake into the stove is controlled by one air control lever. Both primary and secondary air valves are
operated using this control lever.
A) To open the primary air intake, pull the air control lever outwards and to close, push it inwards.
SAFETY ADVICE
During the first operation it is highly likely that fumes and smells maybe produced as part of the
normal heat resistant paint curing process, much like a domestic oven. Therefore, good ventilation
during this process is of utmost importance. We recommend that pregnant women, allergic
persons and small children as well as domestic animals, especially birds, should not unnecessarily
stay in subjected areas.

17
B) To open the secondary air intake, slide the air control lever to the right and to close, slide it to the left.
C) When the air control lever is pushed in fully and slid as far to the left as possible, both the Primary and
Secondary air intakes are in the closed position.
D) When the air control lever is pulled all the way out and slid as far to the right as possible, both the
Primary and Secondary air intakes are in the open position.
Warning! –This appliance will be hot when in operation and due care should be taken.
We advise that suitable gloves, or the operating tool is used when operating the air control, and when opening
the door.
Primary Air
The primary air provides a conventional air draught to the bed of the fire.
Secondary Air
The secondary air is the air control for the airwash that keeps a clean and uninterrupted view of the fire.
Burning Wood
Lighting the Stove
First, load the fire with starting fuel, i.e. paper, dry sticks and/or firelighters. Light the fire at the base with the
air control fully open (B). Allow the fuel to reach a steady glow and build the fire up gradually. Once you have
a good fire established across the grate bed, further fuel can be added as required.

18
Reduced Combustion
In order to shut down the stove, push the air control lever fully in and slide fully to the left. If the controls are
left in this position, the fire will be starved of air and will die down. If you want to revive the fire, pull the air
control lever fully out and slide fully to the right. For normal burning push lever all the way in and leave it
pushed to the right.
Warning! - The stove will remain hot for a considerable time after the fire has been extinguished.
Notes on Woodburning
With a full load of wood, the stove will need to be refuelled approximately once every hour. Wood can be
stacked in the stove, but no higher than the door handle.
Overloading the stove can cause excess smoke to be emitted. Wood burns most efficiently with the air control
primary air closed and secondary air open.
Wood burns most efficiently on a bed of ash and it is therefore only necessary to remove surplus ash from the
stove occasionally.
If there is insufficient burning material in the fire bed to light a new fuel charge, excessive smoke emission can
occur.
Refuelling must be carried out with a sufficient quantity of glowing embers and ash, so that the new fuel
charge will ignite quickly. If there are too few embers, add some kindling to prevent excessive smoke.
When refuelling, it is important to have a damper in the open position if you have one.
Maximum Log Length: 350mm
Ensure your logs are well seasoned with a moisture content of less than 20%
Recommended Fuels
Hunter Stoves Group recommend that only wood logs with a moisture content of less than 20% should be
burnt on this appliance.
Burning wet or unseasoned wood will create excess smoke emissions, tar deposits in the stove and chimney
and will not produce a satisfactory heat output.
WARNING - DO NOT BURN BITUMINOUS COAL, PETRO-COKE, OTHER PETROLEUM BASED FUELS OR TREATED
WOOD SUCH AS PALLETS AS THIS WILL INVALIDATE THE PRODUCT WARRANTY. HOUSEHOLD WASTE MUST
NOT BE BURNT ON THIS APPLIANCE.
A list of approved fuels can be found at:-
HETAS Ltd –Telephone 01242 673257 –
http://hetas.co.uk/public/hetas_guide.html
Solid Fuel Association –Telephone 0800 600 000 –
www.solidfuel.co.uk
MAINTENANCE AND SERVICING
WARNING!
NO unauthorised modification of this appliance should be carried out.
Important!
In order to ensure continued compliance with current Building Regulations and Local Authority Byelaws, this
appliance requires regular maintenance by a competent person. N.B. Refer to the ‘Removing Internal
Components’ section of the installation instructions for details on how to remove each component.

19
Periods Of Prolonged Non-Use
If the stove is to be left unused for a prolonged period, then it should be given a thorough clean to remove ash
and unburned fuel residues. To enable a good flow of air through the appliance to reduce condensation and
subsequent damage, leave the air controls fully open. If the appliance has been unused for a long period, such
as during the spring and summer months, a competent person should check the chimney for potential
obstructions before lighting the stove i.e. get the chimney swept before the start of the heating season.
Baffle
This should be removed and cleaned at least once a month to prevent any build-up of soot or fly ash that could
lead to blocked flue ways and dangerous fume emission. If the baffle is removed the chimney/flue way can be
swept through the appliance.
Stove Body
Painted Finish - The stove is finished with a heat resistant paint and this can be cleaned with a dry microfibre
cloth or dry soft brush. Do not clean whilst the stove is hot. At no point should any water based or other
cleaning products be used on the stove. The finish can be renovated with Hunter Stoves paint.
Glass Panel
The glass should not be cleaned using cleaners high in alkaline or acidic content. Clean the glass panel when
cool with a propriety glass cleaner by applying the cleaner to a cloth. Do not apply directly to the glass as this
could cause run of which could soak into the rope seals around the edge of the glass.
Highly abrasive substances should be avoided as these can scratch the glass and make subsequent cleaning
more difficult. Wet logs on heated glass, a badly aimed poker or heavy slamming of the doors could crack the
glass panels. The glass will not fracture from heat.
Should you need to replace a glass panel please ensure you purchase a new Gasket at the same time. Please
check periodically that the glass clips and screws have not become loose. They should only be finger tight to
allow for the expansion and contraction of the glass.
Gaskets/Tape
The glass gasket will have to be replaced when a new piece of glass is fitted as the gaskets become brittle after
firing the stove. New self-adhesive glass tape will also be needed if glass is replaced.
Over time you may also find that the gasket changes colour. This is due to a reduction in the pigment used in
the manufacture of the product and no cause for concern.
Firebricks
In normal use, these can last for many years. It is possible however, to crack them if logs are continually
jammed against them or if they are frequently struck with a poker. Check periodically for seriously cracked
bricks, which can be replaced with new, available from your dealer or our spares website
www.hunterstoves.co.uk/spares.
Door Catch assembly
The door catch assembly (shown below) is
adjustable up, down, in and out by loosening
the two screws as shown by the arrows
above.

20
Changing The Door Handle
Rope
Check the rope around the door. If rope is becoming detached, use rope glue to reattach it. If the rope is in a
poor condition, a replacement rope kit may be ordered from the Hunter Stoves Group spares range.
Chimney and Flue ways
It is important that the chimney, flue ways and any connecting flue pipe are swept regularly. This means at
least once a year for smokeless fuels and at least twice a year for wood and other fuels. The baffle will need to
be removed from its supports in order to sweep the chimney (see assembly instructions). Only wire-centred
sweeps’ brushes fitted with a guide wheel should be used. If it is not possible to sweep all parts of the chimney
through the appliance, ensure there is adequate access to cleaning doors. If the stove is fitted in place of an
open fire, then the chimney should be swept one month after installation to clear any soot falls which may
have occurred due to the difference in combustion between the stove and the open fire.
Annual Service
Hunter Stoves Group recommend that this appliance is serviced annually, preferably prior to the start of the
heating season, thus avoiding any delay in receiving replacement components, should you need them.
If you feel unable to undertake this task, Hunter Stoves recommend that you contact the installation engineer
for advice.
Remove all the internal components:
Log retainer, bricks, ignition air bar & baffle. Clean them with a soft brush and inspect them for damage.
Sweep the chimney/flue system if necessary. Clean down the internal surfaces of the appliance using a scraper
or wire brush.
Inspect these surfaces for damage/corrosion. If corrosion or damage is found, we advise that you consult with
your installer about rectification/repair. Brush out or vacuum the inside of the appliance and re-fit the internal
components.
Inspect the Glass and Gasket. Clean the Glass with a non-abrasive cleaner if required. If the Gasket is torn or
damaged, we recommend that is replaced to ensure that no products of combustion enters the room when
the appliance is used.
Painted Finish
Use a dry microfibre cloth or dry soft brush to clean the outer surface and touch up the paint if necessary.
Burn the appliance at a low rate, after maintenance, to allow any new seals, paint or glue to cure properly.
The appliance may emit unpleasant odours during this process, please ensure the room is well ventilated.
The paint can be ordered through our website www.hunterstoves.co.uk.
Remove screw holding in door hook with a flat
head screwdriver. Pull hook out of hole in door.
To change the door handle. Use a 5mm Allen Key to
undo the screw. Once screw is removed handle will
come off. To attach work in reverse.
Other manuals for Parkray ASPECT 80B
2
Table of contents
Other Hunterstoves Group Wood Stove manuals
Popular Wood Stove manuals by other brands

Napoleon
Napoleon S9 installation instructions

Nordica
Nordica TERMOCAMINO-650 user manual

castorama
castorama Etinas manual

Invicta
Invicta 700GA Installation and user guide

Vogelzang International
Vogelzang International VG450EL owner's manual

Harrie Leenders
Harrie Leenders Lumos Instructions for installation, use e maintenance