Page 15
Function
The remote inputs have multiple functions including
0= Override onboard sensor with remote sensor.
1= Average onboard sensor with remote sensor.
2 = Force fresh air. 3 = Remote mute. 4 = Reserved. 5 = Report
status to Mobus/BACnet. 6 = Outside air sensor. 7 = Pause all
alarms (Unoccupied). Default is 0.
Ventilation
High Outside
Air
Temperature
Lockout
entilation function uses the inside and outside (if
fitted) air temperature sensors to determine if outside air is
suitable to be used to ventilate the room.
The outside air temperature must be under this value to be
deemed suitable for the Active Ventilation function to operate.
Default is OFF. Adjustments are Off, then 5 degrees to 100 degrees
in 1-degree steps.
Ventilation
Low Inside Air
Temperature
Lockout
uses the inside and outside (if
fitted) air temperature sensors to determine if outside air is
suitable to be used to ventilate the room.
This setting defines the inside air temperature threshold that if
exceeded (and if outside air is suitable) will begin the Active
Ventilation function.
Default is Off. Options are Off, then 5 degrees to 100 degrees in 1-
degree steps.
Page 16
Ventilation
Output
can introduce fresh outside air
conditions are suitable. This option defines the output(s) that
control this function. The letter “A” will be shown on the display
when this function is enabled and flash when it is working. (Tap
the “A” to see outside temp)
Default is 0 = Function Off.
Options are 0= Function Off. 1 = Relay only. 2 = Temp 0-10V only.
3 = Relay and temp 0-10V.
Min
Value
This option permits you to select the lowest temperature value to
be used. Temperatures below this value will be ignored. (See
graph on page 6)
Default is 0 degrees. Adjustments are -20 degrees to 150 degrees
(C or F) in 1-degree steps.
Value
This option permits you to select the highest temperature value to
be used by the SC-CO2-TH. Temperatures above this value will be
ignored. (See graph on page 5)
Default is 100 degrees. Adjustments are -20 degrees to 150
Low Voltage
10V output voltage when at
the minimum temperature value. (See graph on page 5)
Default is 0V. Adjustments are 0-10V in 0.5V steps.
Voltage
at the maximum temperature value. (See graph on page 5)
Default is 10V. Adjustments are 0-10V in 0.5V steps.