HVTest SMG3000 User manual

- 1 -
Dear Client
Thank you for Purchasing our SMG3000 Three Phase
Voltammeter. Please read the manual in detail prior to first use,
which will help you use the equipment skillfully.
Our aim is to improve and perfect the
company's products continually, so there may be
slight differences between your purchase equipment
and its instruction manual. You can find the changes
in the appendix. Sorry for the inconvenience. If you have further
questions, welcome to contact with our service department.
The input/output terminals and the test column
may bring voltage, when you plug/draw the test wire or
power outlet, they will cause electric spark. PLEASE
CAUTION RISK OF ELECTRICAL SHOCK!
Company Address:
T4,No. 41, High-tech 2 Road,East Lake High-tech Development Zone,
Wuhan
Sales Hotline: 86-27- 87457960
After Service Hotline:86-27- 87459656
Fax: 86-27- 87803129
E-mail: [email protected]
Website: www.hvtest.cc

- 2 -
SERIOUS COMMITMENT
All products of our company carry one year limited warranty
from the date of shipment. If any such product proves defective
during this warranty period we will maintain it for free. Meanwhile
we implement lifetime service. Except otherwise agreed by
contract.
SAFETY REQUIREMENTS
Please read the following safety precautions carefully to avoid
body injury and prevent the product or other relevant subassembly
to damage. In order to avoid possible danger, this product can only
be used within the prescribed scope.
Only qualified technician can carry out maintenance or repair
work.
--To avoid fire and personal injury:
Use Proper Power Cord
Only use the power wire supplied by the product or meet the
specification of this produce.
Connect and Disconnect Correctly
When the test wire is connected to the live terminal, please do
not connect or disconnect the test wire.
Grounding
The product is grounded through the power wire; besides, the

- 3 -
ground pole of the shell must be grounded. To prevent electric
shock, the grounding conductor must be connected to the ground.
Make sure the product has been grounded correctly before
connecting with the input/output port.
Pay Attention to the Ratings of All Terminals
To prevent the fire hazard or electric shock, please be care of
all ratings and labels/marks of this product. Before connecting,
please read the instruction manual to acquire information about the
ratings.
Do Not Operate without Covers
Do not operate this product when covers or panels removed.
Use Proper Fuse
Only use the fuse with type and rating specified for the product.
Avoid Touching Bare Circuit and Charged Metal
Do not touch the bare connection points and parts of energized
equipment.
Do Not Operate with Suspicious Failures
If you encounter operating failure, do not continue. Please
contact with our maintenance staff.
Do Not Operate in Wet/Damp Conditions.
Do Not Operate in Explosive Atmospheres.
Ensure Product Surfaces Clean and Dry.

- 4 -
-Security Terms
Warning: indicates that death or severe personal injury may
result if proper precautions are not taken
Caution: indicates that property damage may result if proper
precautions are not taken.

- 5 -
Contents
WARNING..................................................................................... - 6 -
I. GENERAL INTRODUCTION..................................................- 8 -
II. MAIN FUNCTIONS................................................................. - 8 -
III. SPECIFICATIONS................................................................. - 9 -
IV. APPARATUS AND FITTINGS........................................... - 10 -
V. HOW TO MEASURE.............................................................- 11 -
VI. MEASURING METHODS.................................................. - 14 -

- 6 -
WARNING
Use this instrument with attention to safety in any case.
Make sure all the accessories are in good condition,
without damage, naked or break line before use.
Cannot be used in the test with voltage over 600 V.
Make sure the connected plugs of wires have inserted
closely into in the interface.
Do not use in damp condition.
Banned use in inflammable and the dangerous
condition.
Pull out the test line after it away from the measured
wires, no finger touch of the input jacks in case of electric
shock.
Do not use in strong electromagnetic environment, to
avoid affecting normal use.
Do not set the instrument for a long period or storage it
in places of high temperature, dewing or under direct sunlight.
Instrument and current clamp must periodically
maintain, keep them clean. Do not use corrosive product or
rough thing to wipe the clamps.
Avoid impact on the current clamp, especially the clamp

- 7 -
joints.
Make full charging if going to be long time without
using.
Use, disassemble, calibration, repair this meter must be
conducted by an authorized qualified personnel.
The instrument shall be immediately stopped using and
sealed when danger will be brought due to its own reason. And
let authorized qualified organization to handle.
Do not the scratch the touch screen by sharp high
hardness objects, avoid damage to the screen.
Do not hit or press hard on the touch screen.

- 8 -
I. General Introduction
SMG3000 Three Phase Meter a high precision instrument
for measurement of three-phase electric parameters, it can be
used to measure the three phase voltage, current and phase
angle, frequency, power, power factor and so on.
SMG3000 Three Phase Meter adopt high-speed Cortex
M3 processor and 24 bits high-speed ADC a for measuring
and calculation , A complete graphical interface, true color
display with resolution of 320 x 240 and touch screen operation
make a friendly man-machine interface. It is easy to carry.
II. Main Functions
Measure three-phase voltages and four lines of current
(includes zero line current) at the same time;
Measure the three-phase ac voltage phase angle,
current phase angle and power phase angle at the same time;
Measure power grid frequency and phase sequence;
Discriminate transformer winding, recognize, capacitive
load and perceptual load automatically;
Show hexagon vector diagram; do color sequence
analysis;
Measure active power, reactive power, apparent power,

- 9 -
three-phase power and power factor;
Data storage and view function;
Data static storage function;
3.5 inch TFT color display with finger touch function;
Lithium battery power supply, rechargeable continuous
standby for more than 20 hours.
III. Specifications
TYPE
MEASUREMENT
RANGE
UNIT
ERROR
RESOLUTION
RATIO
Voltage
1~500
V
0.5%×measuring
range
0.01V
Current
0.001~10
A
0.5%×measuring
range
0.0001A
active power
0.001~5000
W
0.5%×reading
(PF=1)
0.1W
reactive
power
0.001~5000
VAR
0.5%×reading
(PF=0)
0.1VAR
apparent
power
0.001~5000
VA
0.5%×reading
0.1VA
frequency
45~65
Hz
0.1%×reading
0.01Hz
phase
position
0~360
°
±2°
0.1°
Note: Error is ±3°when current is 1mA-5mA

- 10 -
IV. Apparatus and Fittings
1. Main Instrument
Figure 1 Main instrument chart
2. Current Clamp Sensor
Figure 2 Current clamp sensors
We choose high precision and high stability clamp current

- 11 -
sensor for current measurement, this meter can joint 4 current
clamp sensors.
3. Voltage Testing Wire
Figure 3 Voltage testing wires
V. How to Measure
1. ON and OFF
Press the buttons continuously and enter the boot
screen as the following chart:
Figure 4 Boot screen
Press the buttons for 3 seconds and listen to a “tick”
SMG3000
Portable Three phase Meter

- 12 -
sound, then the meter will enter the true state of boot.
2. Measurement Interface
It appears the measurement interface automatically when
the meter is on:
Figure 5 Volt-ampere phase measurement interface
If measurement methods choose three-phase three-wire,
lightly touch icon with the touching pen and the icon
will become , single-phase measurement can be
realized with the same operation.
This meter has data hold and storage function, lightly
touch icon, icon color turns from gray into red
as . Data measurement stops and then appears save
icon, lightly touch save icon and store the data. Circulation
storage is used; new stored data will deleted the first saved
data automatically.
Checking function can help to check the stored data, with
purple icon R * * (* * represents 01 and 02... 10), use the

- 13 -
previous page icon and the next page icon
to scan the data. These functions above are as effective in
power measurement interface.
Press the icon , icon turns to blue as the figure
shows below, the volt-ampere phase measurement date can
also be saved when you click save bottom.
Figure 6 Power measurement interface
Lightly touch vector diagram icon and enters hexagon
vector diagram measurement interface, the hexagon diagram
shows the voltage and current vector diagram by color (A
phase voltage and current in yellow, B phase voltage and
current in green, C phase voltage and current in red).
Judge phase sequence:
Green mark is shown before the voltage value if voltage
phase sequence is right; red mark is shown if wrong.
Green mark is shown before the current value if current
phase sequence is right; red mark is shown if wrong.

- 14 -
Judge load properties:
"L" is shown if it is inductive load; "C" is shown if it is
capacitive load, otherwise shows "-".
VI. Measuring Methods
1. One-Way Measurement Connection Mode
As following:
Figure 7one-way measure connection modes
Live line will be connected to the UA phase of the
instrument, while zero line is connected to UN when use
single-phase electric measurement. Current clamp sensor
should be clamped to live line and insert IA access.
2. Three-PhaseThree-Wire Connection Method
As following:
output
load

- 15 -
Figure 8 Three phases three lines connection method
Connection for pressure-wire: Use the special voltage
testing lines (three groups as yellow, red and black); one end
insert the UA, UC, UN phase socket of the equipment in turn,
and the other end insert the A phase, C phase and B phase of
the circuit being measured respectively.
Note: yellow line joins UV socket, black line joins UN
socket, and red line joins UC socket.
Connection for current line: Insert IA, IC clamp to IC, IA
socket of the equipment, and clutch the other end to the
current circuit being measured.
3. Three-Phase Four-Wire Connection Method
As following:

- 16 -
Figure 9 Three-phase four-wire connection method
Connection for pressure-wire: Use the special voltage
testing lines (four groups as yellow, green, red and black); one
end insert the UA, UB, UC, UN phase socket of the equipment
in turn, and the other end insert the A phase, B phase, C phase
and zero line of the circuit being measured respectively.
Connection for current line: Insert IA, IB, IC clamp to IA, IB,
and IC socket of the equipment, and clutch the other end to the
current circuit being measured.
Table of contents
Other HVTest Measuring Instrument manuals

HVTest
HVTest GM-15kV User manual

HVTest
HVTest GM-10kV User manual

HVTest
HVTest SGB-C Series User manual

HVTest
HVTest HTHL-100B User manual

HVTest
HVTest HT-TC User manual

HVTest
HVTest GM-5kV User manual

HVTest
HVTest HTHL-200A User manual

HVTest
HVTest GM-20kV User manual

HVTest
HVTest HTYWS-H User manual

HVTest
HVTest SMG2000B User manual