
1.3
FOUNDATION, LEVELLING AND ANCHORING
Machine location should be carefully selected. A at concrete oor area should
be chosen. It should have enough free space surrounding the machine to enable
free access for safe operation and maintenance. The machine should be leveled
in both directions (from side to side & from front to back). Six leveling screws
used for securing machine to the pallet during transport, should be installed,
one in each corner of the machine base, as shown below. It might be required
to place steel plates under leveling bolts to prevent their sinking into the con-
crete oor. In cases when the machine is to be anchored permanently, anchoring
holes are provided. They are located next to the leveling screw holes. The larger
diameter hole is used for retaining during shipping and for use with concrete oor
anchors. The smaller diameter threaded hole at each corner, are used for leveling
the saw.
Using a level on the machine out-feed table, level machine front to back and side
to side.
NOTE: In some cases leveling the saw infeed with a slight slope towards the blade is recommended. This will prevent
coolant from running down the raw stock. (This is especially true when cutting tubing or bundles).
EARTH GROUNDING PROCEDURE
1. The customer is to provide and install a ground rod approximately .60 (15mm) diameter, copper clad steel, to be
driven no less than 8’ (2.5m) into the ground, no more than 10’ (3m) away from control enclosure.
2. The ground rod is to be connected to customer’s in plant ground system. This connection shall be made directly
at the ground rod. (If applicable).
3. It is desirable that the overall resistance to ground measured at the ground rod does not exceed 3 ohms.
Customer is advised to consult local power company for further information on grounding.
4. The ground rod is to be connected to the ground terminal in the control enclosure using insulated, stranded
copper wire. The wire gauge size is to be determined according to the electrical code of the customers
local electrical authority.
5. An additional point to check is to ensure continuity of all ground within the control enclosure. Start with the main
power entrance ground terminal where the internal ground conductors should originate and then connect to, the
DIN terminal strip, control transformer, and the lid of control enclosure. Also, the PLC and Interface units
should have their own ground conductors connected to one of the main ground terminals.
6. A properly functioning ground system will:
- provide safety for personnel.
- ensure correct operation of electrical/electronic apparatus.
- prevent damage to electrical/electronic apparatus.
- help dissipate lightning strikes.
- divert stray radio frequency (RF) energy from electronic/control equipment.