Hydrotech Water 3200ET User manual

IMPORTANT: Fill in pertinent information on page 3 and page 6 for future reference.
3200ET Control Valve/Remote Meter Timer
Service Manual

Printed in U.S.A.
Page 2
3200ET Control Valve/Remote Meter Timer
Table of Contents
Timer Installation And Start-Up Procedures .................................................................................................................. 3
Timer Start-Up Procedures (Cont’d.) ............................................................................................................................. 4
Remote Meter Installation And Start-Up Procedures .................................................................................................... 6
Remote Meter Start-Up Procedures (Cont’d.) ............................................................................................................... 7
Timer/Remote Meter Control Operation ........................................................................................................................ 9
Timer/Remote Meter Control Operation (Cont’d.) ....................................................................................................... 10
Timer/Remote Meter Control Operation During A Power Failure ........................................................................... 11
Timer Control Operation During Regeneration ...................................................................................................... 11
Remote Meter Control Operation During Regeneration ......................................................................................... 12
Timer/Remote Meter Control Operation During Programming ............................................................................... 13
Timer/Remote Meter Lockout Input Operation ....................................................................................................... 13
3200ET Control Valve/Remote Meter Timer Assemblies ............................................................................................ 14
3200ET Control Valve/Remote Meter Timer Assemblies Parts List ............................................................................ 15
3200ET Remote Meter ................................................................................................................................................ 16
3200ET Remote Meter for 2900/3900 Multivalve System #7 ...................................................................................... 17
2750/2850/3150/3200ET System #4 ........................................................................................................................... 18
2900/3900/3200ET System #4 .................................................................................................................................... 19
2750/2850/3150/3200ET System #5 and System #6 Lead ......................................................................................... 20
2750/2850/3150/3200ET System #5 and System #6 Lag............................................................................................ 21
2900/3900/3200ET System #5 and System #6 Lead ..................................................................................................22
2900/3900/3200ET System #5 and System #6 Lag .................................................................................................... 23
2750/2850/3150/3200ET System #7 (3-Way Solenoid Output Lead) ......................................................................... 24
2750/2850/3150/3200ET System #7 (3-Way Solenoid Output Lag) ........................................................................... 25
2900/3900/3200ET System #7 Lead ........................................................................................................................... 26
2900/3900/3200ET System #7 Lag ............................................................................................................................. 27
9000/9500/3200ET System #4 .................................................................................................................................... 28

Printed in U.S.A.
Page 3
Control Valve Timer Programming
Water Hardness: ________________________
System Capacity: _______________________
Regeneration Time: ______________________
Regeneration Cycle Step Programming:
Step #1 _______________________________
Step #2 _______________________________
Step #3 _______________________________
Step #4 _______________________________
Step #5 _______________________________
Notes:
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
WARNING
Backplate must be grounded when voltages greater than
24V are used with valve.
3200ET Control Valve/Remote Meter Timer
Timer Installation And Start-Up Procedures

Printed in U.S.A.
Page 4
3200ET Control Valve/Remote Meter Timer
Timer Start-Up Procedures (Cont’d.)
1. During cold weather it is recommended that the installer warm the timer up to room temperature before operating.
2. Once the timer has reached Service normal operation is resumed. In Normal Operation the Time Of Day and, if
flow meter equipped, the Volume Remaining Displays will alternate being viewed. Set the Time Of Day Display by
depressing the Up or Down Set Button to the correct time. (See above figure.)
3. Flow Meter Equipped Timer Only: The Volume Remaining Display is the volume of water (in gallons) remaining
prior to regeneration, including any reserve capacity. Without any water usage the Meter Arrow should be either off
or on but not changing. Open a soft water tap. The Meter Arrow should begin flashing at a rate that varies with flow
rate. Close the tap after 3 - 5 gallons of water flow.
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
Backwash
Brine/Rinse
Rapid Rinse
Tank Fill
Low Battery
Water Hardness
System Capacity
Regeneration Time
Extra Totalizer
Flow
Rate
Program S
E
T
Cycle
Service Indicator
Valve in Service - Arrow On
Manual Regeneration Tonight - Flashing Arrow
Time of Day Display
Reserve Indicator:
Volume Remaining Above Reserve - Arrow Off
Volume Remaining At Or Below Reserve - Arrow Flashing
Totalizer Display Indicator
Flow Indicator:
Arrow Flashes With Water Flow
Sensor Indicator:
Sensor Input Signal - Flashing Arrow
Valid Regeneration Signal - Arrow On
Flow Rate Display Indicator
Program Display
Volume Remaining Display Indicator
Lockout Indicator:
Lockout Signal - Arrow On
Regeneration Indicator
Valve In Regeneration - Arrow On
ET003-0
ET064-0
For Example:
12:59 P.M.
(Valve in Service)
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
ET002-0
For Example:
125 Gallons Of Water
Remaining
(Valve in Service)
(No water flow)
(Volume is below
reserve capacity,
Reserve arrow
flashing)
For Example:
0 Gallons Of Water
Remaining
(Valve in Service)
(Water flowing)
(Volume is below
reserve capacity,
Reserve arrow
flashing)
ET003-0

Printed in U.S.A.
Page 5
3200ET Control Valve/Remote Meter Timer
Timer Start-Up Procedures (Cont’d.)
4. Manually initiate a regeneration cycle and allow water to run to drain for 3 to 4 minutes. Next, manually step the
valve through a regeneration cycle checking valve operation in each step.
A. Initiating Regeneration (Depending on the timer regeneration type you have one or two (2) Options):
1. Press and Release the Extra Cycle Button. With Immediate Regeneration Timers the control will go into
Regeneration immediately. With Delayed Regeneration Timers the Service Arrow will begin to flash imme-
diately and a regeneration will occur at the preset regeneration time (i.e. 2:00 a.m.)
2. Press and Hold for 5 seconds the Extra Cycle Button. The control will go into Regeneration immedi-
ately.
B. Control Operation
1. During Regeneration: During Regeneration the control will display which regeneration step number the
valve is advancing to, or has reached, and the time remaining in that step.
2. When the first cycle step is reached, a red LED will turn on to indicate the current regeneration cycle step.
3. Pushing the Extra Cycle Button during a regeneration step will immediately advance the valve to the next
regeneration step position.
4. Pushing the Up or Down Set Button during a regeneration step will adjust the time remaining in that current
regeneration step. Programmed regeneration step times will not be changed.
5. Once all regeneration cycle steps have been completed the valve will return to Service and resume normal
operation.
5. Manually step the valve to the Brine Draw position (see Step #14) and allow the valve to draw water from the brine
tank until it stops. Note: The air check will check at approximately the midpoint of the screened intake area.
6. Manually step the valve to the Brine Refill position and allow the valve to return to Service automatically.
7. Make sure the brine refill time (salt dosage) is set as recommended by the manufacturer.
8. With the valve in Service, check that there is about 1sof water above the grid in the brine tank, if used.
9. Fill the brine tank with salt.
10. A 9V Alkaline Battery is recommended to be installed at all times for proper valve operation. The control will
indicate when the battery needs to be replaced by turning on the Low Battery LED.
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
For Example:
(Valve is advancing to Regeneration Step #1)
(#1 flashing)
(Regeneration arrow on)
Backwash
ET065-0
For Example:
(Regeneration Step #1 has been reached)
(10.0 minutes remain in Step #1)
(Regeneration arrow on)
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
Backwash
ET067-0

Printed in U.S.A.
Page 6
3200ET Control Valve/Remote Meter Timer
Remote Meter Installation And Start-Up Procedures
Remote Meter Timer Programming:
Water Hardness: ________________________
System Capacity: ________________________
Regeneration Time: ______________________
Regeneration Signal Time: ________________
Notes:
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
__________________________________________________________________________________________
1. Follow the installation procedures contained within the remote meter service manual.
2. The remote meter/timer should be installed with the inlet and outlet and connections (if any) made in accordance
with the manufacturer’s recommendations and to meet all applicable plumbing codes.
3. Follow the installation and start-up procedures contained within each valve(s) service manual.
4. Referencing the wiring diagram furnished with each valve in the system, make the proper electrical connections to
the remote timer. All electrical connections must be made in accordance with the manufacturer’s recommendations
and to meet all applicable electrical codes.
5. During cold weather it is recommended that the installer warm the remote timer up to room temperature before
energizing.
6. Plug the remote timer into an approved power source. The valve(s) connected to the remote timer may then cycle
themselves back to Service.
WARNING
Backplate must be grounded when voltages greater than
24V are used with remote meter.

Printed in U.S.A.
Page 7
3200ET Control Valve/Remote Meter Timer
Remote Meter Start-Up Procedures (Cont’d.)
1. In normal operation the Time Of Day, and if flow meter equipped, Volume Remaining Displays alternate being
viewed. Set the Time Of Day Display by depressing the Up or Down Set Button to the correct time. (See above
figure.)
2. The Volume Remaining Display is the volume of water (in gallons) remaining prior to regeneration, including any
reserve capacity. Without any water usage the Meter Arrow should be either off or on but not changing. Open a soft
water tap. The Meter Arrow should begin flashing at a rate that varies with flow rate. Close the tap after 3 - 5 gallons
of water flow.
ET001-0
For Example:
12:59 A.M.
(Valve in Service)
ET002-0
For Example:
125 Gallons Of Water
Remaining
(Valve in Service)
(No Water Flow)
(Volume is below
reserve capacity,
Reserve Arrow
Flashing)
For Example:
0 Gallons Of Water
Remaining
(Valve in Service)
(Water Flowing, Meter
Arrow Flashing))
(Volume is below
reserve capacity,
Reserve Arrow
Flashing)
ET003-0

Printed in U.S.A.
Page 8
3200ET Control Valve/Remote Meter Timer
Remote Meter Start-Up Procedures (Cont’d.)
3. Manually initiate a regeneration cycle of all valves in the system through the remote timer. Allow water to run to
drain on each valve for 3 to 4 minutes. Manually step each valve through a complete regeneration cycle checking
valve operation in each step.
A. Initiating Regeneration (Depending on the timer regeneration type you have one or two (2) Options):
1. Press and Release the Extra Cycle Button. With Immediate Regeneration Timers the control will go into
regeneration immediately. With Delayed Regeneration Timers the Service Arrow will begin to flash immedi-
ately and a regeneration will occur at the preset regeneration time (i.e. 2:00 a.m.)
2. Press and Hold for 5 seconds the Extra Cycle Button. The control will go into regeneration immediately.
Delayed Regeneration Timers Only)
B. Control Operation While Sending A Regeneration Signal:
1. When sending a regeneration signal the control will display the remaining signal time.
2. A red LED will also turn on to indicate that a regeneration signal is being sent.
3. Pushing the Extra Cycle Button during a regeneration signal will immediately advance the timer back to
Service.
4. Pushing the Up or Down Set Button during a regeneration signal will adjust the signal time remaining. Pro-
grammed signal time will not be changed.
5. Once the Regeneration Signal has been completed the timer will return to service and resume normal
operation.
For Example:
(Timer is sending a 6.0 minute
regen. signal)
(Regeneration arrow on)
Regeneration
Signal
ET004-0
For Example:
(Timer has sent 3.5 min.
of a 6.0 min. signal))
(2.5 minutes of signal time remain)
(Regeneration arrow on)
Regeneration
Signal
ET005-0

Printed in U.S.A.
Page 9
3200ET Control Valve/Remote Meter Timer
Timer/Remote Meter Control Operation
Normal Operation
Flow Meter Equipped Delayed Regeneration Valves/Remote Meter Delayed Regeneration Systems -
In Normal Operation the Time Of Day Display will alternate being viewed with the Volume Remaining Display. Water
flow through the unit is indicated by the Meter Arrow that will flash in a direct relationship to flow rate. As treated water
is used, the Volume Remaining Display will count down from a maximum value to the calculated reserve capacity. Once
this occurs, the Reserve Arrow will begin to flash as an indication that reserve capacity is being used. At the preset
Regeneration Time, a regeneration cycle will then be initiated immediately.
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
Backwash
Brine/Rinse
Rapid Rinse
Tank Fill
Low Battery
Water Hardness
System Capacity
Regeneration Time
Extra Totalizer
Flow
Rate
Program S
E
T
Cycle
Service Indicator
Valve in Service - Arrow On
Manual Regeneration Tonight - Flashing Arrow
Time of Day Display Indicator
Reserve Indicator:
Volume Remaining Above Reserve - Arrow Off
Volume Remaining At Or Below Reserve - Arrow Flashing
Totalizer Display Indicator
Flow Indicator:
Arrow Flashes With Water Flow
Sensor Indicator:
Sensor Input Signal - Flashing Arrow
Valid Regeneration Signal - Arrow On
Flow Rate Display Indicator
Program Display Indicator
Volume Remaining Display Indicator
Lockout Indicator:
Lockout Signal - Arrow On
Regeneration Indicator
Valve In Regeneration - Arrow On
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
For Example:
125 Gallons of Water Remaining
(Valve in Service)
(No water flow)
(Volume is below reserve capacity)
ET064-0
Timer
ET003-0
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
For Example:
0 Gallons of Water Remaining
(Valve in Service)
(Water flowing, Meter arrow flashing)
(Volume is below reserve capacity)
ET007-0
Sensor Indicator:
Sensor Input Signal - Flashing Arrow
Valid Regeneration Signal - Arrow On
Flow Rate Display Indicator
Volume Remaining Display Indicator
Lockout Indicator:
Lockout Signal - Arrow On
Regeneration Indicator
Valve In Regeneration - Arrow On
ET006-0
Program Display Indicator
Service Indicator
Valve in Service - Arrow On
Manual Regeneration Tonight - Flashing Arrow
Time of Day Display Indicator
Reserve Indicator:
Volume Remaining Above Reserve - Arrow Off
Volume Remaining At Or Below Reserve - Arrow Flashing
Totalizer Display Indicator
Flow Indicator:
Arrow Flashes With Water Flow
Remote Meter

Printed in U.S.A.
Page 10
3200ET Control Valve/Remote Meter Timer
Timer/Remote Meter Control Operation (Cont’d.)
Timeclock Regeneration Valves -
In Normal Operation the Time Of Day Display will be viewed at all times. The control will operate normally until the days
since the last regeneration reaches the preset number of days. Once this occurs, a regeneration cycle will then be
initiated immediately at the preset Regeneration Time.
Flow Meter Equipped Immediate Regeneration Valves/Remote Meter Immediate Regeneration Systems -
In Normal Operation the Time Of Day Display will alternate being viewed with the Volume Remaining Display. Water
flow through the unit is indicated by the Meter Arrow that will flash in a direct relationship to flow rate. As treated water
is used, the Volume Remaining Display will count down from a maximum value to zero. Once this occurs a regeneration
cycle will then be initiated immediately.
Sensor Immediate Regeneration Valves -
In Normal Operation the Time Of Day Display will be viewed at all times. The control will operate normally until a valid
sensor input signal is received. Once this occurs, a regeneration cycle will then be initiated immediately. The Sensor
Input Arrow will flash until the signal is determined to be valid.
Sensor Delayed Regeneration Valves -
In Normal Operation the Time Of Day Display will be viewed at all times. The control will operate normally until a valid
sensor input signal is received. Once this occurs, a regeneration cycle will then be initiated immediately at the preset
Regeneration Time. The Sensor Input Arrow will flash until the signal is determined to be valid. Then the Reserve
Arrow will begin to flash as a indication that reserve capacity is being used.
Immediate Regeneration Valves/Meters With Days Between Regeneration Override Set -
When the timer has reached its set Days Since Regeneration Override value a regeneration cycle will be initiated
immediately. This event occurs regardless of the Volume Remaining display having reached zero.
Delayed Regeneration Valves/Meters With Days Between Regeneration Override Set -
When the timer has reached its set Days Since Regeneration Override value a regeneration cycle will be initiated at the
preset Regeneration Time. This event occurs regardless of the Volume Remaining display having reached the
calculated reserve capacity.
For Example:
525 Gallons of Water Remaining
(Timer in Service)
(Water flowing, Meter arrow flashing)
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor ET008-0
For Example:
12:58 A.M. With Invalid Sensor Signal
(Timer in Service)
(Sensor arrow flashing)
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
For Example:
12:59 A.M. With Valid Sensor Signal
(Timer in Service)
(Sensor arrow on)
(Reserve arrow flashing) (Delayed Regen.)
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
ET009-0

Printed in U.S.A.
Page 11
3200ET Control Valve/Remote Meter Timer
Timer/Remote Meter Control Operation (Cont’d.)
TIMER/REMOTE METER CONTROL OPERATION DURING A POWER FAILURE
During a power failure all control displays will be turned off and regeneration cycles delayed. The control will otherwise
continue to operate normally until line power is restored or battery backup power is lost.
1. If battery backup power is never lost during a power outage, the control will continue to operate normally, without
the loss of data, until line power is restored.
2. If battery backup power is lost during a power outage, the control will store the current Time Of Day, Volume
Remaining, Regeneration Cycle Status, and various diagnostic displays. These stored displays will then be used
upon line power restoration until updated ones are created. To indicate this type of failure, the control will flash the
current. Time Of Day Display to indicate that this display and the Volume Remaining Display may not be correct.
TIMER CONTROL OPERATION DURING REGENERATION
In regeneration the control will display what regeneration step number the valve is advancing to, or has reached, and
the time remaining in that step. Once all regeneration cycle steps have been completed the valve will return to service
and resume normal operation.
1. First the Regeneration Arrow turns on. Then the display below is viewed to indicate that the valve is advancing to
the first regeneration cycle step.
2. When the first cycle step is reached, the display becomes as shown below. As time passes the control will begin to
decrement the step time in tenths of minutes until zero is reached. A red LED will also turn on to indicate the
current regeneration cycle step.
3. Once the step time reaches zero, the valve drive motor will turn on and the Regeneration Time Remaining Display
revert to all dashes until the next regeneration cycle step position is reached. Steps #2 and #3 will then be repeated
until all regeneration cycle steps have been completed and the valve has returned to Service.
4. Pushing the Extra Cycle Button during a regeneration cycle will immediately advance the valve to the next cycle
step position and resume normal step timing.
5. Pushing the Up or Down Set Button during a regeneration cycle will adjust the time remaining in a regeneration
cycle step. Actual regeneration cycle step programming will not be changed.
For Example:
(Valve is advancing to Regeneration Step #1)
(#1 Flashing)
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
Backwash
ET065-0
For Example:
(Regeneration Step #1 has been reached)
(10.0 minutes remain in Step #1)
Service Time ReserveTotalizerMeter
RegenLockoutVolume
Remaining
ProgramFlow
Rate Sensor
Backwash
ET067-0

Printed in U.S.A.
Page 12
3200ET Control Valve/Remote Meter Timer
Timer/Remote Meter Control Operation (Cont’d.)
REMOTE METER CONTROL OPERATION DURING REGENERATION
During Regeneration a special regeneration display will take the place of either the Time Of Day or Volume Remaining
Display. This display will contain the number one (to indicate only one regeneration signal is being sent) and the signal
time remaining.
1. First the Regeneration Arrow turns on. Then the display below appears to indicate that a Regeneration Signal is
being sent and how long it will be.
2. As time passes the countdown display will decrement in tenths of minutes until the time remaining reaches zero.
When this occurs the control will return immediately to Service
3. Pushing the Extra Cycle Button during a regeneration signal will immediately return the control to Service.
4. Pushing the Up or Down Set Button during a regeneration signal will adjust the signal time remaining. Actual
Regeneration Signal programming will not be changed.
For Example:
(Regeneration Signal has started)
(6.0 minute regeneration signal to be sent)
(Regeneration Arrow On)
Regeneration
Signal
For Example:
(Regeneration Signal has started)
(3.2 minutes remain for signal)
(Regeneration Arrow On)
Regeneration
Signal

Printed in U.S.A.
Page 13
3200ET Control Valve/Remote Meter Timer
Timer/Remote Meter Control Operation (Cont’d.)
TIMER/REMOTE METER CONTROL OPERATION DURING PROGRAMMING
The control will only enter the Program Mode with the valve/meter in Service and operating on line power. While in the
Program Mode the control will continue to operate normally monitoring water usage and keeping all displays up to date.
Control programming is stored in memory permanently with or without line or battery backup power.
TIMER/REMOTE METER LOCKOUT INPUT OPERATION
The Lockout Arrow will turn on whenever a Lockout Signal is being received by the control. Any requests for
regeneration will be delayed until this signal is removed. Regeneration will then proceed normally.
Extra Cycle Button
Pushing this button will initiate a regeneration cycle independently of actual valve conditions.
1. With immediate regeneration valves/meters this extra regeneration will occur immediately.
2. With delayed regeneration valves/meters this extra regeneration will occur at the set Regeneration Time. A
regeneration cycle can be forced to occur immediately by pushing and holding in for 5 seconds this button.
Totalizer/Flow Rate Button
This button is used to view the Totalizer and Flow Rate Displays. Depressing the button once will display flow rate.
Depressing the button again will display the total accumulation of water flow through the valve since it was last reset.
Depressing the button once more will return the display to Time Of Day or Volume Remaining. The Totalizer display is
reset by depressing and holding for 25 seconds this button. During the 25 seconds, the Totalizer Arrow will flash as an
indicator to the operator that the display is being reset properly.
Program Button
This button is used by the installer to program those settings indicated on the front panel by red LEDs.
Up Set Button
This button is used to set the current time of day, adjust time remaining in a regeneration cycle step and in valve
programming. The Up Arrow Button will increment a display setting.
Down Set Button
This button is used to set the current time of day, adjust time remaining in a regeneration cycle step and in valve
programming. The Down Arrow Button will decrement a display setting.
Low Battery Indicator
When the control is operating on line power, this red LED will turn on whenever the 9V Alkaline Battery (Not Included)
used for memory backup needs to be replaced. The battery is stored against the valve backplate. In the event of a
power outage the battery will maintain current operating displays for approx. 24 hours at maximum battery capacity.
Keypad Operation
Extra Totalizer
Flow
Rate
Program
S
E
T
Cycle
ET012-0
Low Battery
ET013-0

Printed in U.S.A.
Page 14
3200ET Control Valve/Remote Meter Timer
3200ET Control Valve/Remote Meter Timer Assemblies
1
2
3
4
5
6
7
8
9
10
11
12
13
15
15
16 16
17
18
19
20
Standard 3/4sTo 2.0s
Electronic Flow Meter
Cap Assy.
Standard 3.0s
Electronic Flow Meter
Cap Assy.

Printed in U.S.A.
Page 15
3200ET Control Valve/Remote Meter Timer
3200ET Control Valve/Remote Meter Timer Assemblies Parts List
Item No. Quantity Part No. Description
11 . . . . . . . . . . . 1 . . . . . . . . . . . . .19144-01 . . . . . . . . . . . . . . . Assembly, Switch Pad (3200ET Remote)
11 . . . . . . . . . . . 1 . . . . . . . . . . . . .19144-02 . . . . . . . . . . . . . . . Assembly, Switch Pad - Standard Downflow
19144-06 . . . . . . . . . . . . . . . Assembly, Switch Pad - Upflow Variable Brining
19144-05 . . . . . . . . . . . . . . . Assembly, Switch Pad - Upflow Brine First
19144-04 . . . . . . . . . . . . . . . Assembly, Switch Pad - Standard Upflow
2. . . . . . . . . . . . 1 . . . . . . . . . . . . .18735. . . . . . . . . . . . . . . . . . Screw, Hex Wash. #8 x 1 1/2
3. . . . . . . . . . . . 1 . . . . . . . . . . . . .18741. . . . . . . . . . . . . . . . . . Housing, Circuit Board - No Hinge
. . . . . . . . . . . . 1 . . . . . . . . . . . . .18741-01 . . . . . . . . . . . . . . . Housing, Circuit Board - Right Hinge
. . . . . . . . . . . . 1 . . . . . . . . . . . . .18741-02 . . . . . . . . . . . . . . . Housing, Circuit Board - Left Hinge
4. . . . . . . . . . . . 1 . . . . . . . . . . . . .40679. . . . . . . . . . . . . . . . . . 24V 3200ET Circuit Board (Version 2.0 Software)
5. . . . . . . . . . . . 1 . . . . . . . . . . . . .18764. . . . . . . . . . . . . . . . . . Shield, Circuit Board
6. . . . . . . . . . . . 3 . . . . . . . . . . . . .12758. . . . . . . . . . . . . . . . . . Screw, Hex Washer #10 x 5/8
7. . . . . . . . . . . . 1 . . . . . . . . . . . . .18749. . . . . . . . . . . . . . . . . . Bracket, Hinge (Not Used With 18741)
8. . . . . . . . . . . . 1 . . . . . . . . . . . . .15159. . . . . . . . . . . . . . . . . . O-Ring .005
9. . . . . . . . . . . . 1 . . . . . . . . . . . . .18814. . . . . . . . . . . . . . . . . . Spacer, Elect. Housing (Not Used With 18741)
10 . . . . . . . . . . . 1 . . . . . . . . . . . . .17831-01 . . . . . . . . . . . . . . . Battery Clip
11 . . . . . . . . . . . 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9V Alkaline Battery (Not Included)
12 . . . . . . . . . . . 1 . . . . . . . . . . . . .14723. . . . . . . . . . . . . . . . . . Pin, Timer Hinge
13 . . . . . . . . . . . 2 . . . . . . . . . . . . .10300. . . . . . . . . . . . . . . . . . Screw, Hex Washer #8 x 3/8
. . . . . . . . . . . . 1 . . . . . . . . . . . . .17749-00 . . . . . . . . . . . . . . . Relay, SPDT (24V) Remote Meter (2 Req.-24V)
. . . . . . . . . . . . 1 . . . . . . . . . . . . .17749-01 . . . . . . . . . . . . . . . Relay, SPDT (120V) Remote Meter (120V)
. . . . . . . . . . . . 1 . . . . . . . . . . . . .17749-02 . . . . . . . . . . . . . . . Relay, SPDT (230V) Remote Meter (230V)
. . . . . . . . . . . . 1 . . . . . . . . . . . . .41054-05 . . . . . . . . . . . . . . . Harness Low Voltage Remote Meter with 3200ET
. . . . . . . . . . . . 1 . . . . . . . . . . . . .41052-04 . . . . . . . . . . . . . . . Harness, Power Remote Meter with 3200ET
. . . . . . . . . . . . 1 . . . . . . . . . . . . .40044. . . . . . . . . . . . . . . . . . Harness, 3200ET, Remote, Delay
41054-03 . . . . . . . . . . . . . . . Harness Low Voltage 2750 with 3200ET
2510, 2750, 2850, 2900
41054-04 . . . . . . . . . . . . . . . Harness Low Voltage 3150 w/3200ET, 3150/3900
41054-06 . . . . . . . . . . . . . . . Harness Low Voltage
9000 w/3200ET, 9000/9500
41052-01 . . . . . . . . . . . . . . . Harness Power
2750/2900 w/3200ET, 2510/2750/2850/2900
41052-02 . . . . . . . . . . . . . . . Harness Power 3150/3900 w/3200ET
41052-03 . . . . . . . . . . . . . . . Harness Power 9000/9500 w/3200ET
19589. . . . . . . . . . . . . . . . . . Plug, Jumper - Home and Step Switch
19891. . . . . . . . . . . . . . . . . . Harness, Battery, All Valves
Optional Electronic Flow Meter Cap Parts List
Item No. Quantity Part No. Description
15 . . . . . . . . . . . 1 . . . . . . . . . . . . .19121-02 . . . . . . . . . . . . . . . Assy. Mtr. Cable 1.8 ft. 2500/9000/9500 System 4
19121-03 . . . . . . . . . . . . . . . Assy. Mtr. Cable 8 ft. All Valves (Optional)
19121-04 . . . . . . . . . . . . . . . Assy. Mtr. Cable 25 ft. All Valves (Optional)
19121-05 . . . . . . . . . . . . . . . Assy. Mtr. Cable 2.3 ft. 2750/2850/2900/3150/3900
Systems 4
16 . . . . . . . . . . . 1 . . . . . . . . . . . . .17798. . . . . . . . . . . . . . . . . . Screw, Hex Washer
17 . . . . . . . . . . . 4 . . . . . . . . . . . . .12473. . . . . . . . . . . . . . . . . . Screw, Hex Washer #10-24 x 5/8
18 . . . . . . . . . . . 1 . . . . . . . . . . . . .14716. . . . . . . . . . . . . . . . . . Meter Cap Assy., Electronic
19 . . . . . . . . . . . 6 . . . . . . . . . . . . .12112. . . . . . . . . . . . . . . . . . Screw, Hex Head
20 . . . . . . . . . . . 1 . . . . . . . . . . . . .14716-01 . . . . . . . . . . . . . . . Meter Cap Assy., 3.0sElectronic

Printed in U.S.A.
Page 16
19222
3200ET Control Valve/Remote Meter Timer
3200ET Remote Meter

Printed in U.S.A.
Page 17
3200ET Control Valve/Remote Meter Timer
3200ET Remote Meter for 2900/3900 Multivalve System #7
19027

Printed in U.S.A.
Page 18
3200ET Control Valve/Remote Meter Timer
2750/2850/3150/3200ET System #4
19132

Printed in U.S.A.
Page 19
3200ET Control Valve/Remote Meter Timer
2900/3900/3200ET System #4
19133

Printed in U.S.A.
Page 20
3200ET Control Valve/Remote Meter Timer
2750/2850/3150/3200ET System #5 and System #6 Lead
19214-01
Table of contents
Popular Control Unit manuals by other brands

Texas Instruments
Texas Instruments TPA6017A2 user guide

UNICORECOMM
UNICORECOMM UM482 user manual

Telit Wireless Solutions
Telit Wireless Solutions GM862PYT Series Product description

VIPA
VIPA SLIO FM 050-1BB30 manual

CRE Technology
CRE Technology i4GEN Technical documentation

Kohler
Kohler TOUCHLESS K-13686 installation instructions