ICS Schneider Messtechnik PPS 1210 User manual

Operating instruction
high pressure calibrator PPS 1210 / L
ICS Schneider Messtechnik GmbH
Briesestraße 59
D-16562 Hohen Ne endorf / OT Bergfelde
Tel.: 03303 / 504066
Fax: 03303 / 504068
www.ics-schneider.de

Table of Contents
Components of high press re calibrator 3
Notes on the operating instr ctions 4
1.
Description of the device 4
2.
General safety warnings 4
3.
Operating the calibrator 5
4.
Description of the f nctions 5
5.
Men navigation for calibrators 6
6.
Commissioning 6
7.
Maintenance / disposal 7
8.
Eval tion with the PC 8
Technical data 9
Declaration of conformity 10
Temperat re controller 17

Components of High Press re Calibrator PPS 1110
1 PC connection (witho t f nction)
2 Device base (only PPS1110)
3 Display
4 SELECT and ENTER b ttons
5 Oil chamber
6 Recirc lation pipe
7 Screwed sealing pl g
8 Man al booster p mp
9 Press re connection for test object (only PPS1110)
10 Drain valve
11 Screw compressor
Additional components of High Press re Calibrator PPS 1210
12 Heatable press re port
13 Press re pipe
14 Temperat re controller
15 On / Off switch for press re port heating
16 Temperat re controller casing
17 Electrical connector for test nit adapter
18 Power line pl g
3

Notes on the operating instr ctions
- The operating instr ctions are in-
tended for specialist workers and
trained personnel.
- Before each stage of work, read the
relevant notes and warnings care-
f lly, and keep to the seq ence as
stated.
- Pay partic lar attention to the sec-
tion on ”General safety warnings”.
If yo have any problems or q estions,
please contact yo r s pplier or
cons lt the company MARIANNE
MAYER, ELECTRONISCHE SCHAL-
TUNGEN directly.
1.
Description of the device
General description
The high press re calibrator enables
press re to be generated by means of
the integrated press re p mp, p to
700 bar relative.
The meas rement technology incor-
porated into this device allows ac-
c rate meas rement and doc men-
tation of the characteristic of a test
object that is connected to it. The
meas red press re progression can
be displayed, eval ated and saved
with a comp ter monitoring program
(CCS30).
The calibrator is operated with the
two f nction b ttons SELECT and
ENTER, located directly below
the display. The calibrator itself is
powered by a 3,0 V battery.
Copyright
For copyright reaons this operating
man al may only be sed for inho se
p rposes.
Any reprod ction, even in part and for
inho se p rposes, req ires the assent
by Messrs
Also, any distrib tion to third parties is
prohibited for competitive reasons.
Commissioning
A press re-resistant connection for
the test object is req ired in order to
se the high press re calibrator. The
press re connection for the test object
is already screwed to the press re
distrib tor of the high press re calibra-
tor so that it is press re resistant when
it leaves the factory, and it m st not be
dismantled.
Recommended torq e for the test
object press re connection: 30 Nm
IMPORTANT!
Nothing m st adhere to the s rface of
the test object (no oil, grease, water,
etc). Imp rities co ld pass tro gh the
adapter to reach the high press re
calibrator and damage it.
Overpress re
If the press re exceeds the meas ring
range by more than 20%, the meas r-
ing cell or the mechanism of the high
press re calibrator may be destroyed
Recalibration
The recalibration cycle depends on
the conditions of se. Recommended
recalibration cycle: 1 year.
Intended se
The high press re calibrator may
only be sed to generate press re
with the type HLP 22 BP hydra lic oil
that is s pplied with the prod ct. Use
of the calibrator with other media will
damage it. The operational safety
of the device s pplied is g aranteed
only if it is sed as intended. The limit
val es as stated (see page 9: ”Tech-
nical data”) m st never be exceeded.
Before installing the high press re
calibrator, check that it is s itable for
yo r applications
2.
General safety warnings
The c rrent national reg lations on
accident prevention and
workplacesafety m st be followed
whenever work is carried o t.
Internal reg lations iss ed by the
operator m st
be followed, even if
they are not mentioned in these
instr ctions.
Never se the high press re calibra-
tor together with an external press re
so rce.
Do not remove any connected compo-
nents (e.g. test objects) when the high
press re calibrator is nder press re.
Open the screwed sealing pl g before
removing parts.
Do se Teflon tape to seal the
press re connection caref l. Resid es
of
Teflon tape co ld penetrate the
high- press re calibrator and damage
it.
Only se the adapters and seals that
are available as accessories.
Do not store the calibrator nder pres-
s re: only store the high press re cali-
brator with the drain valve open.
Avoid the action of force of any kind
on the high press re calibrator and its
operating controls.
Do not se high press re calibrators if
they are damaged or fa lty.
4

3.
Operating the calibrator
Operating the high press re calibrator
is described starting on page 6.
Connect the test object
Yo can connect yo r test object to the
high press re calibrator via the pres-
s re connection (9).
Press re generation
When sing the calibrator, the screwed
sealing pl g (7) m st be opened (2
t rns), so that overpress re cannot
b ild p in the oil reservoir.
Use the man al booster p mp (8) to
set the press re to abo t 10 bar. Yo
can se the screw compressor (11) to
increase or red ce the press re.
Release press re
1.
Open the screw compressor (11)
completely
2. Open the drain valve (10)
IMPORTANT!
Do not open if there is high pres-
s re in
the system!
If yo can no longer reach the desired
press re, please cons lt the section on
"Maintenance" to find o t how to vent
the system.
Zeroing the device
Open the drain valve (10) to release
any press re that may have b ilt p.
If the press re display does not show
zero, perform a zeroing proced re
(Set Zero) and then close the drain
valve.
Information abo t the display
If no press re can be shown on the dis-
play, it will show
OFL
(overflow) or
UFL
( nderflow).
If press re o tside the device’s
meas ring range is applied, the
last valid press re val e that was
meas red will flash on the display
(overload warning).
last valid press re val e that was
meas red will flash on the display
(overload warning)
Reset
4.
Description of the f nctions
Men navigation
If the selected f nction or nit is not ac-
tivated by pressing the ENTER b tton
within 5 seconds, the display will ret rn
to meas ring mode witho t changing a
setting.
5

6

We recommend that you have the
company ICS SCHNEIDER,
change the oil. The entire system is
cleaned at the same time. nly use
type HLP 22 BP hydraulic oil.
➞
➞
shown, and press ENTER to activate.
Yo can now se SELECT to choose
the f nction yo want, and ENTER to
exec te the f nction. Depending on
the c rrent setting, the first f nction
to be shown is either
min/max disp
or
LEAK disp
.
Leak meas rement f nction
Leak mode is sed to determine
the press re change over a defined
period, which can be adj sted. The
nit to be tested m st be connected
to the high press re calibrator on the
press re side.
Start leak meas rement
Activate the
MANO
men . The display
shows Leak dISP. Press the ENTER
b tton and then the SELECT b tton.
Press ENTER to confirm Leak Start.
The leak meas rement starts, and the
display alternates between the c rrent
leak time and the press re change
meas red th s far.
Active leak meas rement
D ring leak meas rement, the lower
part of the display alternates each sec-
ond between the meas rement time
that has now elapsed [mm:ss] and the
press re change meas red th s far.
➞ Mano mode
ENTER
➞ La nch Leak
mode by press-
End leak meas rement early
To end a leak meas rement early,
press the ENTER b tton and confirm
the ”Leak Stop” display by pressing
ENTER.
Leak meas rement completed
If the leak meas rement time has
elapsed or if the meas rement was
man ally ended ahead of time,
the display alternates between the
elapsed leak meas rement time and
the meas red press re change.
Set leak meas rement time
The leak meas rement time is preset
to 10 min tes in the factory, and it can
only be changed with the ”Mano Con-
fig” software.
(➞ Software for calibrators)
MANO / "Contin o s" f nction
A tomatic switch-off f nction (the de-
vice switches off a tomatically 15 mi-
n tes after a b tton was last pressed).
Leak meas rements are canceled by
the a tomatic switch-off f nction if the
meas rement time is more than the
switch-off time.
Cont on: Disables the a tomatic
switch-off f nction
Cont oFF: Enables the a tomatic
switch-off f nction
If the "Contin o s" f nction is en-
abled, Cont flashes on the display.
7 Maintenance / disposal
Venting the press re system
Release the press re completely and
then open the drain valve (10) and the
screwed sealing pl g (7). Screw the
screw compressor (11) in completely.
P mp steadily with the man al boos-
ter p mp (8) to clear the system of air.
When no more b bbles come o t of
the recirc lation pipe (6), close the
drain valve (10).
(8)
(10)
(7)
(11)
Changing the oil
Battery
The press re calibrator is powered
by a 3 V b tton-cell battery (behind
the display). If the battery is low, the
battery symbol on the display
lights p.
Replacing the battery
Please switch the device off. T rn the
ENTER ing the ENTER
b tton
Leak r n-
➞ Unit of press re
➞ C rrent
meas red val e
display section ring beyond the limit
stop ntil it is released from the ho s-
ing section (t rn thro gh abo t 180°).
Open the battery compartment and
Leak r n-
ENTER
➞ Start the leak
meas rement
with ENTER
➞ Unit of press re
➞ C rrent
meas red val e
time in
mm:ss
➞ ➞
Press re change
within leak
r ntime
change the battery (type CR 2430).
time in ➞
mm:ss
Press re change
within leak
r ntime
7

Disposal
This prod ct m st not be disposed of
as normal ho sehold waste at the end of its sef l lifetime. To
prevent possible damage to the environment or to health d e to ncontrolled waste disposal, this
prod ct
m st be separated from other waste and recycled correctly in order to ens re s stainable
se of the raw materials.
8. Eval ation with the PC
Installation
Before the first opening of the Excel sheet, copy the file "s30c.dll" in die folder C:\WINDOWS/SYSTEM (not SYSTEM32).
Yo req ire administrator rights in order to be able to do this. If necessary, inform yo r IT administrator.
Meas ring and completing the Excel sheets
Connect the USB o tp t of the calibrator with the PC's USB port.
Under Connections in the Device Manager, look for the n mber of the USB port of the PC, to which the calibrator is
connected.
Enter this val e in the cell P-31 at the description "Com-Port-N" in the Excel sheet.
In the next step, the cells E-16, L-9, L-11, L-15, L-17, L-19, L-21 and L-23 are completed. The candidate's 100% bar range
is entered in the cell L-11 (printing area).
The cells L-11, L-15, L-23 and P-31 are obligatory fields.
The res lt of the meas rement is evident from the cells G-26, G-27 and G-28. This information relates to the data in cell L-
15 (acc racy).
Start the meas ring by clicking the b tton "Meas rement 1" in the depress rized state.
The data of the reference sensor in the calibration and the candidate's are read. At the meas rement 1, the calibrator's
data with the serial n mber and the date, with the time of the meas rement, is also a tomatically read.
Increase the press re of the calibrator to abo t 50% of the final val e. Wait ntil the val e stabilizes (evident on the
calibrator's display). Click the b tton "Meas rement 2".
Increase the press re in the calibrator to 100% of the candidate's, b t only to a maxim m of 700 bars.
Ca tion: The calibrator can be damaged or destroyed with a press re of more than 700 bars (+ 10% max).
Save the test protocol nder a different name.
The read data is deleted by clicking the "Delete All" b tton.
Image: Excel sheet for the eval tion of the meas rement
8

Technical data
Press re range (FS) 0…700 bar (others on req est)
Overpress re 840 bar (FS+20%)
Resol tion of display 1mbar
Acc racy, error band (1) (10…40 °C) < 0,05 %FS
Acc racy, error band (1) (0…50 °C) < 0,1 %FS
Leak rate* 700 bar: -2 bar @ 10 min.
N mber of digits on display 5 digits
Meas rement interval 0,5 seconds
Interface USB (RS485 o t of f nction)
Compensated temperat re range 0…50 °C
Operating temperat re 0…50 °C
Storage temperat re -10…60 °C
Air h midity 5…95% relative h midity
Power s pply
heatable press re port and sensor 115V AC or 230V AC
Display B tton-cell battery, type CR2430
Battery lifetime : > 2000 h in contin o s operation
Hydra lic oil HLP 22 BP or olive oil
Press re port 1/2"20UNF or M18x1,5
Media compatibility Press re transd cer with stainless steel diaphragm
Dimensions (L x W x H) 470 x 170 x 280 mm
Weight approx. 7,2kg
Degree of protection IP 54
Selectable press re nits bar, mbar, hPa, kPa, MPa, PSI, kp/cm2, cmH2O, mH2O, inH2O, ftH2O,
mmHg, inHg
Delivery in a stable al mini m transport case!
(1) incl ding acc racy, temperat re coefficients, zero point and range tolerance
* Physical effects ca sed by a press re change lead at first to a clear difference in press re.
Advice: To minimise the infl ence of these physical effects increase steadily the last 5% of the target press re and reg late
towards the target press re for the first min tes.
The stated leakage rate is at a thermal balanced condition (when temperat re of press re media and of the environment is eq able).
9

Konformitätserklär ng Declaration of Conformity Déclaration de Conformité
10

17
The temperature regulator is a high quality control instrument for both simple ON/OFF two-position regulation or, if desired,
PID control systems with autotuning function.
In the ON/OFF mode, the degree of hysteresis is freely programmable. In the ON/OFF mode, the degree of hysteresis is
freely programmable
The temperature regulator has been designed for heating and cooling operations in the range -200°C to +1, 50°C. The measurement
range is only determined by the type of sensor used.
It is easy to operate and configure, and is ideal for industrial use thanks to the many important customisation options it offers. These
include useful additional functions such as sensor break detection with automatic power cutoff, alarm output, maximum or minimum
set value setting and password access etc.
Safety notes:
Do not use the device in explosive atmospheres or in the vicinity of flammable liquids or gases.
Bear in mind that if you are not qualified to work with electricity, this can result in pain, lasting damage to your
health or your death.
This instruction manual assumes that you are qualified to work with electrical equipment. If you are not qualified
to work with electricity, please have an electrician carry out all works on this equipment!.
General:
OPERATING INSTRUCTION
Temperature regulator

18
Technical ata:
Dimensions ............ approx 48x48x105 mm (W x H x D)
Sampling period: .................
<3 sek.
Installation depth approx 100mm
Max output load ..................
approx 2A (resistive load, mechanical relay)
Mounting cutout
:
45 x 45mm (DIN 1/16)
Max switch voltage
..............
230 V AC
Display viewing area
.. -1999°C bis +9999°C
Voltage output SSR ..............
approx 12VDC/25mA
Temperature
measu
....................
-200 ...+1 50°C
dependent on sensors
Environmental temperature ..
max. 45°C
Display height
........
approx 10mm
Humidity of environment
max 85% relative humidity in
Resolution ............. 0,1°C
(Display resolution is customisable)
non-aggressive environment
Closed-circuit current ......
< 3W
Control/Display elements:
Status message isplay
1
4
4
RTD
The display then changes to operating mode
PV = Current process value; SV is the current set value
PV
SV
PV
SV
Set value
Display SV
Cursor-key
and autotuning
Cursor key
Display software version 1s
(
Sn
menu
)
Display measurement range
1s (PV display = INPH
menu, SV display = INPL
menu)
PV
OUT
AL1
SV
Cursor key
TR
-
81
SET
AT
Menu access
and confirmation
LED OUT
Active if control
output is
switched
on
LED ALARM
Active if alarm
output is
switched
on
PV
SV
Display software version 1s
Process value t
Display PV

19
Changing the set value an alarm temperature: When the regulator is switche on
Press the button
SET
SU appears on the PV display, and the last figure on the SV display flashes
Use the arrow keys to set the control set value to the desired temperature, and confirm
your selection via the button
SET
.
The value is saved, and the regulator jumps to the set value setting for the second alarm output. The PV
display shows Al1, and the SV display shows the current setting.
Use the arrow keys to set the control set value to the desired temperature,
and confirm your selection via pressing the button twice
SET
The regulator is now back in operating mode, and has saved the changed values ready for use.
Suggestions for selecting the control mo e:
The following information serves to provide an example of temperature regulation for an electric heater, and
is intended to illustrate a possible configuration. Custom applications demand expert knowledge of control
technology, which is beyond the scope of this instruction manual.
The regulator offers you two different options for regulating a set value that you specify either a simple
ON/OFF regulator with hysteresis, or as a PID control system. Before you put the device into operation,
consider which type of regulation would be most appropriate for your particular application.
The ON/OFF regulation with hysteresis is a basic temperature control system in which the regulator allows
the load at the exit (eg heater) to be kept switched on until the preselected set value (menu table A value
SU) is reached. If a hysteresis value (switching delay) is entered in the DFCT menu, this value is added to
the set value. The load is therefore switched off according to the following schema
Set value + Hysteresis value = Load switched off. The load is switched back on again according to the
reverse of that principle Set value - Hysteresis = Load switched back on.
Example
If the set value is 100°C and hysteresis is 0.5°C, the load is switched off at 100.5°C and switched back on at
99.5°C.
This basic regulation is ideal for lots of applications. Its advantage lies in its easy to understand functioning,
plus in its low switching rate and, if mechanical load protectors are used, protection of the load relays that
switch the load.
Switching rates can be minimised by setting as high a rate of hysteresis as possible.
The disadvantage of ON/OFF regulation is that the temperature fluctuates in the range around the set value,
due to the hysteresis that was specified and the sluggishness of individual process components (heater
follow-up time, sensor reaction times, loss of transmission etc).
A PID control system is ideal for many applications, as it can achieve highly consistent temperature values
without fluctuation. In contrast to ON/OFF regulation, this process uses software in the regulator which, when
a load is connected, records the process conditions required for controlling (autotuning function, p5). The
regulator’s software then determines the appropriate PID parameters, which, thanks to special algorithms,
reduce the heat output step by step as the temperature converges with that of the set value.
Reduction occurs by pulsing on the controller output. In an ideal scenario, when the temperature reaches the
set value, the regulator only releases the heat output that is required to maintain the preselected
temperature.
The PID control system is therefore most appropriate when the connected load needs to be triggered at short
intervals using on/off intervals. The advantage of this method lies in the fact that the temperature curve
achieved is very linear, and generally permits only the most minimal fluctuations, with a tolerance of just a
few tenths of a degree.
In many processes, PID regulation requires extremely short switching times, sometimes < 1 sec. Due to
regular pulsing, mechanical relays are subject to a high rate of wear and tear. The temperature regulator has
been designed for triggering an SSR relay (as used in calibrator PPS1210). This enables you to even switch
greater loads with short pulse times, and without wear and tear, thanks to electronic thrysistor switches.
Because certain applications also require the use of regulators with SSR output and semiconductor relays to
trigger mechanical load protectors, the regulator also features a function enabling you to preselect a
minimum pulse time (menu table B – Switching time output (T). Particularly if you are using mechanical load
protectors, this allows you to specify a minimum switching time. The correct setting for your particular
application depends on making a considered compromise between the shortest possible switching time, to
ensure a linear set value progression, and the shortest possible switching frequency, which will prolong the
lifetime of the downstream relay contacts. When using PID controls, a larger safety clearance between the
switching load and the mechanical relay’s specified nominal load is recommended.
>
>
>
>
1

20
Using the menus:
The temperature regulator is operated via two menus (A and B). Menu A contains the settings for the set
value (see also page 19 ‘Changing the set value and alarm temperature’). These settings are easily
accessible to any operator by simply pressing the button to call them up. Repeated pressing of the button
moves to the next menu item.
The parameters in menu B are settings for configuration of the regulator, along with other advanced
parameters. As a rule, these are not operating functions. Access to menu B is therefore password protected,
by calling up ‘Loc’ and entering the password 508 (see next page).
The ‘Loc’ menu also provides you with the option to prevent the set value (menu A) being changed, should
you wish that operators are not permitted to change it. To do so, set a value other than 0 (not 508).
consec.
No.
parameter
code pa r a me t e r na me a d ju s tmen t r a n ge d e s cri p tio n
Menu A
1
SU s e t val u e s e tti n g
(SU)
INPL to IN PH
switches output terminal
1, 2 (relay contact potential-free)
2
AL I
alarm value setting
( AL1) INPL to IN PH
switches output terminal
8, 7, 6 (changeover contact potential-free)
3
Loc
password-protected
menu access
LOC
0~9999
LOC=0,
changes in menu A and autotuning are permitted;
LO
C
=0,
Changes in Menu A are not permitted (exception parameters
);
LOC=508,
Call-up and changes to menu B are permitted. After leaving Menu B,
‘Loc’ jumps back to the value that was originally set.
Making changes in the ‘A vance parameters’ menu
:
When the regulator is switched on
Press the button
SET
3x kurz hintereinander.
‘Loc’ appears on the PV display, and the last figure on the SV display flashes (active).)
Use the arrow keys to enter the password 508 and then confirm it with.
SET
.
The PV display now shows the first parameter code Sn. In the SV display, the value that has been set flashes (active).
Change the value by pressing the buttons according to the table, then press
SET
again to call up the next parameter.
Confirm you have finished making parameter settings by pressing and holding down the
SET
button for about 3 seconds.
Customisation is now complete, and the regulator now once again shows the temperature in the PV display and the set
value in the SV display.
After about 30 seconds of inactivity, the parameter settings display returns to normal operating mode.
Customisation is now complete, and the regulator now once again shows the temperature in the PV display and the set
value in the SV display.
After about 30 seconds of inactivity, the parameter settings display returns to normal operating mode.
>
>
>
>

21
consec.
No.
Parameter
code P a r a m e t er n a m e adjustment range description
menu B "Advanced parameters"
4
Sn Input specification,
(SN)
Y
S
E
J
Cu50
Pt
U0-5
UI-5
0-20
4-20
K type thermal element / Possible measurement range - 50 .. . + 135 0 °C
S- type thermal element / Possible measurement range - 5 0 . . . +17 5 0 °C
E- type thermal element / Possible measurement range - 50 . . . +8 0 0 ° C
J- type thermal element / Possible measurement range - 5 0 ...+10 0 0 ° C
Cu50 type RTD (resistance sensors) / Possible measurement range - 5 0 . . . + 1 5 0 ° C
Pt100 type RTD (resistance sensors / Possible measurement range - 2 0 0 .. . + 850 ° C
0 - 5 V d i r e c t v o l t a g e (analogue input) / Possible measurement range - 1 9 9 9 . . . + 9 9 9 9
1 - 5 V d i r e c t v o l t a g e (analogue input) / Possible measurement range - 1 9 9 9 . . . + 9 9 9 9
0-20 mA di r e c t c urren t (analogue input)) / Not active
4-20 mA di r e c t c urren t (analogue input) / Not active
5
dP
D e c i mal poi n t s
- d i s p l a y
(DP)
0-3
DP=0, display without decimal places ; XXXX
DP=1, display with 1 decimal places XXX.X
DP=2, display with 2 decimal places XX.XX
DP=3, display with 3 decimal places X.XXX
When using temperature sensors as input, you can only select Dp0 or Dp1.
The actual internal measurement resolution always remains 0.1°.
6
inPL lower set value limit,
(INPL) - 1 9 9 9 . . . + 9 9 99
Lower set value limit. The specified value limits how the set value on the regulator and alarm output
can be set. (See section ‘Changing the set value and alarm tem
perature’ page 2). The value that you
enter represents the lowest possible setting that can be made.
7
inPH upper set value limit,
(INPH) - 1 9 9 9 . . . + 9 9 99
Upper set value limit. The specified value limits how the set value on the regulator and alarm output
can be set. (See section ‘Changing the set value and alarm temperature’ page 2).
The value that you
enter represents the highest possible setting that can be made.
8
Sc
measurement reading
calibration
(SC)
- 1 9 9 9 . . . + 9 9 99
Calibration function to compensate for sensor d
eviations. The value set in °C will be added to the
display value. If you desire a decrease, enter the value as a negative value.
Recommendation You will achieve best results if you calibrate to a value near to the set value. The
calibration is not officially verifiable!
9
Ctrl regulating mode selection
(CTRL)
oFF
b it.r
b it.d
P id.r
P id
.d
OFF Display function only
BITR On/Off regulation for heating operation (switches off after an ascending slope to set value)
BITD On/Off regulation for cooling operation (switches off after a descending slope to set value)
PIDR PID control heating operation
PIDD PID control cooling operation
10
dFct switching hysteresis at
both sides
(DFCT)
0.1 ...200. 0
(Forma t . )
1 ...2000
(Fo rm a t )
Only active in on/off operation, on output terminal 1, 2. The specified temperature value is added to
both ascending and descending temperature slopes. This therefore doubles the total hysteresis
(switching gap).
Example of a heating control system on output relay terminal 1, 2
Operating mode ON/OFF (BITR), set value = 200.0°C, DFCT = 0.5°C
The output relay will therefore switch off the heating when 200.5°C is reached;
The output relay will switch the heating back on after the temperature has cooled to 199.5°C.
11
AL It alarm output
(AL1T)
oFF
HJ
HJb
LJ
LJb
OFF No alarm active (alarm output on terminals 6, 7, 8 is deactivated)
HJ Absolute alarm value excess temperature (high limit)
Alarm is emitted when the alarm value specified is reached. Alarm stops automatically according to
the preselected switching hysteresis (DFAL menu)
HJB Absolute alarm value excess temperature with hold function
As per HJ above, except that when the regulator is switched on (control voltage on), the alarm does
not emit immediately, even if at the time of switching on the temperature is such that the alarm would
usually be triggered during normal operation (for example, if a refrigerator is still warm).
The alarm will only be emitted if the temperature moves out of the normal range and heads
towards the alarm setting (temperature slope runs up to the alarm setting). Automatic alarm reset in
accordance with DFAL menu. LJ Absolute alarm value insufficient temperature (low limit)
Alarm is emitted when the lower alarm value specified is reached. Alarm stops automatically
according to the preselected switching hysteresis (DFAL menu)
LJB Absolute alarm value insufficient temperature with hold function
Functioning equivalent to HJB
Note
In order to circumvent
the automa
tic alarm reset (alarm with hold function without automatic
12
dFAL
alarm hysteresis
(DFAL) 1-2000 Switching gap reset alarm output (terminals 8, 7, 6). Only works with AL1T
13
P proportional band
(P)
0.1-999.9% of
the measuring range
Proportional band parameter (P value). Setting only works in PID control mode (Menu Ctrl)
14
l
I integral time
(I) 0-9999s Integral part parameter (I value). Setting only works in PID (Menu Ctrl)
15
d
differential time
(D) 0-999.9s Derivative part parameter (D value). Setting only works in PID (Menu Ctrl)
16
t switching time output
(T) 2-120s
T represents the minimum period of time in seconds in which the output remains switched on. In
principle, when using mechanical relay outputs/switching mechanical load relays, you should select
the longest possible switching time, in order to avoid premature wear due to high switching
frequency.
When using regulators with SSR outputs and so-called SSR relay leads, in many cases selecting a
shorter pulse interval results in better linearity of the temperature curve. Thanks to wear-free
switching provided by electronically switching SSR relays, it is possible to choose your own
switching frequency.

22
Rev: 05-15/12
‘Automatic a justment’ (Autotuning) function
The control panel features a programme that automatically finds the optimum PID settings for the connected load.
For this programme to work, it is important that the regulator is ready for operation, the load is connected and that a
non-critical temperature set value has already been set. In the ‘Loc’ menu (page 20), the value 0 must be set.
When in autotuning mode, the regulator moves through one or more control cycles so that it can establish the
parameters. This can result in considerable deviations from the set value. Bear this in mind when specifying
the set value. In consideration of this, it should be as close as possible to the actual control value.
During normal operation when a load is connected, press the button for about 4 seconds.
In the SV display, the set value flashes in alternation with - AT -. The procedure is complete once SV has
automatically returned to normal display.
In order to cancel autotuning, press the button again for about 4 seconds, until SV stops flashing. The
previous settings are not changed.
Alarm output configuration:
As well as an SSR output, the TR-81 also features an alarm output (terminals 8, 7, 6), which can be provided with its
own set value (Menu B, parameter AL1T) as well as its own hysteresis (Menu B, parameter DFAL). When making
any such settings, refer to the information provided in menu table B, under parameter point ALT1.
If, when the regulator is switched on, an undesired alarm is emitted (when the set value at the time of switching on
corresponds to the alarm value), this can be prevented by the HJB setting (if the alarm range is higher than the set
value) or the LJB setting (if the alarm range is below the set value). Both these settings can be found in menu AL1T.
These settings enable the alarm to be temporarily bypassed after the control voltage has been switched on.
Maintenance an customer service:
In normal operation, the TR-81 regulator does not require maintenance. Excessive dust deposits should however be
avoided. Use in wet rooms is only permitted with the approved housing with protective cover (part no Z-45-
KsKap45x45). Electronic components must be protected against condensation moisture.
Dirt on the front and on the housing can be removed with a slightly moistened cloth when the regulator is switched
off.
Error co e:
HHHH Measurement signal is above the expected range!
If displayed after sensor installation Wrong sensor type set in the ‘Sn’ parameter (Menu table B).
Temperature measured is outside the upper and lower set value range (‘inPL’ and ‘inPH’, page 21).
Load is switched off.
LLLL Measurement signal is below the expected range!
If displayed after sensor installation Wrong sensor type set in the ‘Sn’ parameter (Menu table B).
Temperature measured is outside the upper and lower set value range (‘inPL’ and ‘inPH’, page 21).
Load is switched off.
We reserve the right to amend the technical specifications.
>
>
This manual suits for next models
1
Table of contents
Other ICS Schneider Messtechnik Test Equipment manuals
Popular Test Equipment manuals by other brands

ELPROG
ELPROG PULSAR-EQmini quick start guide

Clas Ohlson
Clas Ohlson SS-1989A Guide

DeFelsko
DeFelsko PosiTest DT instruction manual

Sperry instrument
Sperry instrument PSI8031 operating instructions

Agilent Technologies
Agilent Technologies InfiniiVision MSO6104A Service note

CREATIVE ELECTRONICS
CREATIVE ELECTRONICS ELT 1091 owner's manual

Agilent Technologies
Agilent Technologies E7495A RF Manual operation

Kikusui
Kikusui tos6200 Operation manual

Tektronix
Tektronix TH3000 Series Installation and safety instructions

Chauvin Arnoux
Chauvin Arnoux CA 6161 user manual

IDEAL Networks
IDEAL Networks LanTEK IV User manua

Ripley
Ripley Miller DLS355 user guide