IDEAL Mexico Super FF440 User manual

Supplied By www.heating spares.co Tel. 0161 620 6677
users guide
Mexico Super
Your Ideal users guide
See reverse for Mexico Super installation & servicing instructions
ENGINEERED FOR PEACE OF MIND
When replacing a part on this appliance use only spare parts that you can be assured
conform to the safety and performance specification that we require. Do not use
reconditioned or copy parts that have not been clearly authorised by Ideal Boilers.
FF440, FF450, FF460,
FF470 & FF480
200939-1.p65 3/1/2004, 4:34 PM45
Supplied By www.heating spares.co Tel. 0161 620 6677
2Mexico Super FF440 - FF480 - Users
Safety
It is essential that the instructions in this booklet are
strictly followed, for safe and economical operation of
the boiler.
Gas Safety (Installation & Use)
Regulations or rules in force.
In your own interest, and that of safety, it is the law that this
boiler must be installed by a CORGI registered installer or in IE
a competent person, in accordance with the above regulations.
Electricity Supply
This appliance must be efficiently earthed.
Supply: 230 V ~ 50 Hz.
The fusing should be 3A.
Connection must be made in a way that allows complete
isolation of the electrical supply such as a double pole switch
having a 3mm (1/8") contact separation in both poles, or a plug
and socket, serving only the boiler and system controls. The
means of isolation must be accessible to the user after
installation.
Important Points
a. If the boiler is installed in a compartment then the
compartment MUST NOT be used for storage purposes.
b. The ventilation provided for the boiler during installation MUST
NOT be blocked, and a check should be made periodically
that the ventilation areas are free from any obstruction.
c. If it is known or suspected that a fault exists on the boiler then
it MUST NOT be used until the fault has been corrected by a
CORGI registered installer or in IE a competent person.
d. Under NO circumstances should any of the sealed
components on this appliance be used incorrectly or tampered
with.
In cases of repeated or continuous shutdown a CORGI registered
person or in IE a competent person should be called to investigate
and rectify the condition causing this and carry out an operational
test after each intervention on the device. Only the manufacturer's
original parts should be used for replacement.
Minimum Clearances
A clearance of 533mm (21") MUST be available at the front of
the boiler for servicing.
The minimum clearances given in Table 1 MUST be complied
with, in order to maintain the safe running of the boiler.
To light the boiler. Refer to Frame 2
If a programmer is fitted refer to separate instructions for the
programmer before continuing.
1. Check that the electricity supply to the boiler is OFF.
2. Open the control panel drop-down door and ensure that the
thermostat knob (G) is in the OFF position.
3. Switch ON the electricity supply to the boiler and check that
all external controls, e.g. room thermostat etc., are ON.
4. Set the boiler thermostat knob (G) to position 6. The fan will
start. After the fan has run for a few seconds the pilot
solenoid valve should open and the intermittent spark
commence, continuing until the pilot is established. The
main burner will then cross-light smoothly.
Winter conditions (i.e. central heating and domestic hot
water). The thermostat should be positioned at setting 5 or 6.
Summer conditions (i.e. domestic hot water only). The
thermostat should be positioned at setting 2.
These settings are offered for general guidance only and other
settings may be found preferable, dependent upon the type of
system installed or as recommended by the installer.
Mexico Super FF440 ................. G.C. No. 41 392 26
Mexico Super FF450 ................. G.C. No. 41 392 27
Mexico Super FF460 ................. G.C. No. 41 392 28
Mexico Super FF470 ................. G.C. No. 41 392 29
Mexico Super FF480 ................. G.C. No. 41 392 30
MEXICO SUPER (Natural Gas Models Only)
Certified - P.I. No. 87 AU 83
Destination Countries: GB, IE
1 BOILER CLEARANCES
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of
this appliance care should be taken when handling edges of sheet steel components
Table 1
Boiler Flue Dimension A
Model Length Rear Flue Side/Top flue
mm (in.) mm (in.) mm (in.)
FF440, FF450
Up 10 35
FF460, FF470
to (3/8) (1 3/8)
FF480
600
FF440, FF450
600 to
FF460, FF470
3000 35 35
FF480
(23 5/8 to (1 3/8) (1 3/8)
118)
200939-1.p65 3/1/2004, 4:34 PM46
Supplied By www.heating spares.co Tel. 0161 620 6677
3
Mexico Super FF440 - FF480 - Users
Note. Grille assembly not shown, for clarity
2 BOILER CONTROLS
LEGEND
A. Gas control valve.
B. Burner pressure test point.
C. Main burner pressure adjuster.
D. Inlet pressure test point.
E. Gas service cock.
F. Sightglass.
G. Boiler thermostat knob.
H. Main burner 'On' neon.
J. Overheat thermostat reset button (optional).
To shut down the boiler
1. For short periods
Turn the boiler thermostat knob (G) to OFF. When heating is
again required, restore the knob to its original setting.
2. For longer periods
a. Turn the boiler thermostat knob (G) to OFF.
b. Switch the electricity supply to OFF.
Frost protection
If no frost protection is provided and frost is likely during a short
absence from home, leave the heating controls (if fitted) at a
reduced temperature setting.
For longer periods, the entire system should be drained -
including the domestic water supply.
If the system includes a frost thermostat then, during cold
weather, the boiler should be turned OFF at the time switch (if
fitted) ONLY. The mains supply should be left switched ON, with
the boiler thermostat left in the normal running position.
Control of water temperature
1. Set the boiler thermostat knob (G) to give the required
temperature for central heating.
2. The boiler thermostat automatically switches the main
burner OFF and ON to maintain the selected temperature.
To relight the boiler
Repeat the procedure 1 - 4 detailed in 'To light the boiler'.
Boiler Overheat Thermostat
(Fitted for sealed systems only)
For a boiler fitted with a safety 'cutout' thermostat: this
thermostat will shut down the boiler in the event of overheating.
Should this occur, allow the boiler to cool, press the reset
button (J) on the overheat thermostat then relight as detailed in
steps 1-4 under 'To light the boiler'.
All CORGI registered installers carry a CORGI ID card, and have a registration number. Both should be recorded
in your Benchmark Log Book. You can check your installer by calling CORGI direct on 01563 72300
THE LOG BOOK SHOULD BE COMPLETED AFTER EACH SERVICE AND KEPT WITH THESE INSTRUCTIONS
Caradon Ideal Limited is a member of the Benchmark initiative and fully supports the aims
of the programme. Benchmark has been introduced to improve the standards of installation
and commissioning of central heating systems in the UK and to encourage the regular
servicing of all central heating systems to ensure safety and efficiency.
If the 'cutout' condition persists turn off the boiler and consult a
CORGI registered installer or in IE a competent person.
Loss of system water pressure
(Boilers fitted with the Overheat Thermostat Kit only)
If the red arrow on the system pressure gauge is set above
zero and the system pressure is seen to fall below this value
over a period of time then a water leak is indicated. In this
event a CORGI registered installer or in IE a competent person
should be consulted.
DO NOT FIRE THE BOILER IF THE PRESSURE HAS
REDUCED TO ZERO FROM THE ORIGINAL SETTING
Escape of gas
Should a gas leak or fault be suspected, contact your gas supplier
without delay.
Do NOT search for gas leaks with a naked flame.
Cleaning
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains, wipe with a damp cloth
and finish off with a dry cloth.
Do NOT use abrasive cleaning materials.
Maintenance
The appliance should be serviced at least once a year by a
CORGI registered installer or in IE a competent person.
Note.
The appliance model is given on the data plate, located on the
front of the boiler base plate, behind the grille assembly.
200939-1.p65 3/1/2004, 4:34 PM47
Supplied By www.heating spares.co Tel. 0161 620 6677
Ideal Boilers, P.O. Box 103, National Ave, Kingston Upon Hull, HU5 4JN. Tel.
01482 492251 Fax. 01482 448858. Registration No. London 322 137.
Caradon Ideal Limited pursues a policy of continuing improvement in the design and
performance of its products. The right is therefore reserved to vary specification without notice.
Ideal Consumer Helpline
Tel: 01482 498660
www.idealboilers.com
POINTS FOR THE BOILER USER
Note. In line with our current warranty policy we would ask that you check through the following guide to identify any
problems external to the boiler prior to requesting a service engineers visit. Should the problem be found to be other than
with the appliance we reserve the right to levy a charge for the visit, or for any pre-arranged visit where access is not gained
by the engineer.
TROUBLESHOOTING - TYPICAL NON PRODUCT FAULTS
Problem Solution
Boiler is not working for
central heating or hot water.
• Check boiler thermostat (G) is turned up.
• Check the overheat thermostat reset button (J) by holding button in for 2 seconds and then
releasing.
• If fitted to a sealed system check the pressure gauge on the system, this should read a
minimum of 1 bar. If necessary re-pressurise the system via the filling loop. Press the
overheat thermostat reset button (J). If the boiler still does not fire or if the pressure continues
to drop after refilling contact the installer.
Boiler goes through ignition
sequence but fails to light in
either mode.
• Check gas supply (try at another gas appliance cooker/fire etc) If no gas supply then this is not
a boiler fault – contact your gas supplier.
Boiler is operating
satisfactorily for domestic
hot water but will not operate
for central heating.
• If an external programmer is fitted check that the central heating channel is at an ‘on’ period.
• Check that the room thermostat is set at the required temperature. Test the room thermostat
by turning this fully up – if this does not respond contact your installer.
Boiler is operating
satisfactorily for central
heating but will not operate
for domestic hot water.
• If an external programmer is fitted check that the domestic hot water channel is at an ‘on’
period.
• Check that the domestic hot water cylinder thermostat is set at the required temperature. Test
the cylinder thermostat by turning this fully up – if this does not respond contact your installer.
Boiler will not fire the pilot
light is lit but the igniter
continues to spark and the
main burner does not ignite.
• This is a symptom of crossed polarity i.e. the live and neutral supply to the boiler are crossed
over. This is not a boiler fault contact your installer to correct the wiring.
200939-1.p65 3/1/2004, 4:34 PM48

This manual suits for next models

4

Other IDEAL Boiler manuals

IDEAL Vanguard L User manual

IDEAL

IDEAL Vanguard L User manual

IDEAL MINI C24 User manual

IDEAL

IDEAL MINI C24 User manual

IDEAL Vanguard L 340 User manual

IDEAL

IDEAL Vanguard L 340 User manual

IDEAL Classic LXRS 230 Manual

IDEAL

IDEAL Classic LXRS 230 Manual

IDEAL ES26 User manual

IDEAL

IDEAL ES26 User manual

IDEAL MINI HE C24 User manual

IDEAL

IDEAL MINI HE C24 User manual

IDEAL he15 User manual

IDEAL

IDEAL he15 User manual

IDEAL imax W60 User manual

IDEAL

IDEAL imax W60 User manual

IDEAL Imax Plus II F90 User guide

IDEAL

IDEAL Imax Plus II F90 User guide

IDEAL Concord CXDi 110 User manual

IDEAL

IDEAL Concord CXDi 110 User manual

IDEAL Concord CXA 40/H User guide

IDEAL

IDEAL Concord CXA 40/H User guide

IDEAL Viceroy GT Series Guide

IDEAL

IDEAL Viceroy GT Series Guide

IDEAL he24 User manual

IDEAL

IDEAL he24 User manual

IDEAL LOGIC CODE COMBI ESP1 33 User manual

IDEAL

IDEAL LOGIC CODE COMBI ESP1 33 User manual

IDEAL he15 User manual

IDEAL

IDEAL he15 User manual

IDEAL GTE 5 User manual

IDEAL

IDEAL GTE 5 User manual

IDEAL Europa 24 User guide

IDEAL

IDEAL Europa 24 User guide

IDEAL Vanguard L 170 User manual

IDEAL

IDEAL Vanguard L 170 User manual

IDEAL Logic Heat 30 User manual

IDEAL

IDEAL Logic Heat 30 User manual

IDEAL Elise H24 User manual

IDEAL

IDEAL Elise H24 User manual

IDEAL Europa 224 User manual

IDEAL

IDEAL Europa 224 User manual

IDEAL c80 ff User manual

IDEAL

IDEAL c80 ff User manual

IDEAL Evomax 30 User guide

IDEAL

IDEAL Evomax 30 User guide

IDEAL Mexico Super CF 3/60P User manual

IDEAL

IDEAL Mexico Super CF 3/60P User manual

Popular Boiler manuals by other brands

Biasi M275V.2024 SM Service manual

Biasi

Biasi M275V.2024 SM Service manual

Sime MURELLE HE 110 R ErP Original instructions

Sime

Sime MURELLE HE 110 R ErP Original instructions

Bryant 4PW232 installation instructions

Bryant

Bryant 4PW232 installation instructions

RVR Energy Technology CAHA Midi 340 Installation, use and maintenance instructions

RVR Energy Technology

RVR Energy Technology CAHA Midi 340 Installation, use and maintenance instructions

Radiant RMA Installation, use and maintenance manual

Radiant

Radiant RMA Installation, use and maintenance manual

U.S. Boiler Company X-203 Installation, operating and service manual

U.S. Boiler Company

U.S. Boiler Company X-203 Installation, operating and service manual

FireBird Enviromax Popular C20 Technical manual

FireBird

FireBird Enviromax Popular C20 Technical manual

Immergas MINI NIKE 24 3 E manual

Immergas

Immergas MINI NIKE 24 3 E manual

HydroTherm HeatNet KN -6 User information

HydroTherm

HydroTherm HeatNet KN -6 User information

Riello Array AR 3000 Installation and operation manual

Riello

Riello Array AR 3000 Installation and operation manual

Bryan Boilers Knockdown RV-350 Specification sheet

Bryan Boilers

Bryan Boilers Knockdown RV-350 Specification sheet

Trianco Contractor WM70 HE INTERNAL User, installation, commissioning & servicing instructions

Trianco

Trianco Contractor WM70 HE INTERNAL User, installation, commissioning & servicing instructions

Boyertown Furnace Solaia SL375 Installation and operator's manual

Boyertown Furnace

Boyertown Furnace Solaia SL375 Installation and operator's manual

Potterton Gold 4 kW Installation and servicing instructions

Potterton

Potterton Gold 4 kW Installation and servicing instructions

Viessmann Vitocrossal Service instructions

Viessmann

Viessmann Vitocrossal Service instructions

Ariston Type C Installation and servicing instructions

Ariston

Ariston Type C Installation and servicing instructions

Benchmark GB10 Design, installation & servicing instructions

Benchmark

Benchmark GB10 Design, installation & servicing instructions

Viessmann Vitocrossal 300 CA3B Lifting Instructions

Viessmann

Viessmann Vitocrossal 300 CA3B Lifting Instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.