IDS X Series User guide


2
IDS X-Series Installer Manual 700-398-02O

3
IDS X-Series Installer Manual 700-398-02O
Contents
Contents ........................................................................................................................................................................................3
1. Keypads ....................................................................................................................................................................5
2. Introduction to the IDS X-Series...............................................................................................................................7
Features of the IDS X-Series .......................................................................................................................................................... 7
3. Installation and Wiring...............................................................................................................................................8
Installation Requirements..............................................................................................................................................................9
End-of-Line Resistors ....................................................................................................................................................................9
Box Tamper Input ..........................................................................................................................................................................9
Connecting the Telephone Communicator - Advanced ................................................................................................................9
Programmable Outputs.................................................................................................................................................................9
Key-Switchor Remote Control Unit ...............................................................................................................................................9
Installing Expander Modules..........................................................................................................................................................9
IDS Remote Receiver .....................................................................................................................................................................9
Transmitter Connection ................................................................................................................................................................9
Hardware Default Switch.............................................................................................................................................................10
Keypads .......................................................................................................................................................................................10
Replacing a DamagedKeypad/Bus-wired Peripheral ...................................................................................................................10
Defaulting Keypads ..................................................................................................................................................................... 11
4. Event Log................................................................................................................................................................11
5. Access Codes.........................................................................................................................................................11
Normal User Code ....................................................................................................................................................................... 11
Master User Code ........................................................................................................................................................................ 11
Maid’s Code (Arm to Disarm Code) ............................................................................................................................................. 11
Duress Code................................................................................................................................................................................. 11
Installer Code............................................................................................................................................................................... 11
Maintenance Code....................................................................................................................................................................... 11
Download Code ...........................................................................................................................................................................12
6. How to Read Location Values ................................................................................................................................12
7. Programming of the Panel......................................................................................................................................12
8. Programming Quick Reference Guide....................................................................................................................13
9. Programming Location Summary...........................................................................................................................14
Zones...........................................................................................................................................................................................14
Global Setup ................................................................................................................................................................................16
Daylight Savings ..........................................................................................................................................................................20
Miscellaneous–Advanced ...........................................................................................................................................................21
Phone Numbers...........................................................................................................................................................................24
Zone Properties ...........................................................................................................................................................................25
No Movement–Advanced ...........................................................................................................................................................27
Security Codes.............................................................................................................................................................................28
Partition Options .........................................................................................................................................................................29
Delays ..........................................................................................................................................................................................30
Options to Configure Keypads..................................................................................................................................................... 31
aXess Control...............................................................................................................................................................................32
Wireless Integration Options.......................................................................................................................................................32
Reporting Codes - Advanced .......................................................................................................................................................32
Global Reporting Codes ...............................................................................................................................................................32
Zone Reporting Codes .................................................................................................................................................................35
Partition Reporting Codes ...........................................................................................................................................................36
User Reporting Codes.................................................................................................................................................................. 37
Programmable Outputs...............................................................................................................................................................38
Output Disarm Clear....................................................................................................................................................................38
Partition Event Driven Outputs–Advanced.................................................................................................................................39
Zone Programmable Output Events............................................................................................................................................40
Output Pulse Timing - Advanced.................................................................................................................................................41
Output Scheduling On Time - Advanced .....................................................................................................................................41
Output Scheduling Off Time - Advanced.....................................................................................................................................42
Output Scheduling On/Off Days - Advanced...............................................................................................................................42
Event Reporting Options - Advanced ..........................................................................................................................................43
10. Touch Keypad Switch to Programmable Output Mapping .....................................................................................45
11. Voice Module ..........................................................................................................................................................45

4
IDS X-Series Installer Manual 700-398-02O
12. Xwave2Outputs ......................................................................................................................................................45
13. LCD Keypad Information ........................................................................................................................................45
14. Panel Information....................................................................................................................................................46
15. User Options...........................................................................................................................................................46
16. Appendix .................................................................................................................................................................47
17. Hardware Identification...........................................................................................................................................49
18. Serial Communication Jumper Settings .................................................................................................................49
19. Trouble Display.......................................................................................................................................................50

5
IDS X-Series Installer Manual 700-398-02O
1. Keypads

New LCD KEYPAD
Keypad Indicator Icons
Power indicator icon has two functions:
1. When the icon is on, this indicates the keypad is powered up.
2. Flashing indicates an issue has occurred and needs your attention.
Armed icon indicates the system is armed either in ‘away’ or ‘stay’ mode. The LCD will
display the armed mode.
Unarmed icon will be illuminated when the system is not armed.
Alarm icon will flash when an alarm condition has occurred.
Button Details
Partition Button is to select a partition that you would like to interact with via the keypad.
NOTE: Only available if the keypad is configured as a global keypad!
Stay Button allows you to select which stay profile to stay arm the system with.
NOTE: Only available if more than one stay profile has been programmed. (see X-Series user
manual)
Switch Button has two functions:
1. Access to outputs that could be used to switch devices, lights on/off or open/close gates, etc.
(Function not currently implemented)
Bypass button allows you to disable zones so that they cannot violate the alarm.
Chime button selects which zones, will cause the keypad to chime when violated while the system is
disarmed.
Navigation buttons allows you to scroll through menus, and when editing zone names, etc.
Press and hold left arrow buttons to change the keypad sounds.
Panic button when held down for 3 seconds will sound the siren and send a panic signal to the
security company if the alarm is configured to do so.
LCD Display
Power, Armed, Unarmed, Alarm Indicators
Touch keys

7
IDS X-Series Installer Manual 700-398-02O
2. Introduction to the IDS X-Series
Thank you for purchasing an IDS Alarm Panel.
The IDS X-Series alarm is a versatile, Bylaw 25 compliant, expandable Alarm Panel. It comes in three versions, X8, X16 and X64.
Both have up to 8 partitions and can have 8 keypads. The X16 can be expanded from 8 to16 zone, the X64 from 8 to 64 zones
and the X8 only has 8 zones with no dialler. Most features are configurable and may be programmed directly through a keypad
or via serial PC connection or telephone system, using the IDSwift 2 Download Software and appropriate modem (P/N: 860-36-
0001).
There are up to 64 programmable burglary zones on the X64, 16 programmable burglary zones on the X16 and 8 programmable
burglary zones on the X8. A dedicated panic zone, monitored siren output, auxiliary power output, and 5 onboard programmable
outputs expandable to 41 outputs with the 860-07-596 Output expander on the X-Series, are available.
For correct operation, the IDS X-Series panels must be used in conjunction with the specified transformer/battery combination
(ask your sales representative for a copy of the IDS Power Budget spreadsheet to identify your needs) and appropriate peripheral
sensors andsignalling devices.
NOTE: X-SERIES products are not compatible with any previous IDS products, such as the IDS816 and IDS1632.
Features of the IDS X-Series
Zones and Partitions:
➢8 onboard zones, expandable to 16 onboard zones with a X-Series 8-zone Plug-in Expander
(P/N: 860-06-X-08PI) –A very cost-effective 16 zone solution
➢Further expandable to 64 zones with the use of up to 6 bus-wired X64 8-zone Unpowered Expander modules (P/N:
860-06-X-08S) or 8 keypad zones - 1 per keypad
➢All zones can be expanded with wireless receivers to receive signals from the Duevi or the Xwave range of enabled
wireless detectors. All wireless zones are fully supervised.
➢The system can also have a hybrid of wired and wireless zones totalling 64 zones for the X64 and 16 zones for the X16
and 8 for the X8.
➢8 partitions
➢4 stay profiles per partition
Users:
➢128 users
➢Options to set user codes as Master, Duress, Maid, Arm only, Disarm only or Output Trigger.
System Options:
➢Tamper reporting per zone using double end-of-line resistors (12K and 4K7)
➢5 programmable outputs on the Alarm Panel, expandable to 41 when using zone expanders (2 per expander),
keypads (1 per keypad) and output expanders (8 per expander)
➢Event log (1000 events) date and time relative
➢Auto arm/disarm capability per partition and by day of the week.
➢No movement auto arm and medical reporting
➢Panel firmware installer upgradable via serial data cable
➢Telephone communicator that supports Ademco, FBI, Silent Knight, Contact ID, and SIA
➢Fax defeat/answering machine override
➢Dual reporting provides for duplicated reporting to two independent central base stations
➢Split reporting to report to either 1 of 2 dual reporting number pairs
➢Comprehensive lightening protection
➢Dynamic battery self-test
➢Low battery monitoring and cut-out circuit
➢Dual power supply, with an independent battery charging circuit, means more onboard power for simplified alarm
installation
➢Voice module support (860-06-X64-0412). Only version “D” hardware and above.
➢Xsms support from version 2.34 to control the alarm via smses
➢2 x 8 channel output expander support. (Firmware version 2.50 and above)

8
IDS X-Series Installer Manual 700-398-02O
3. Installation and Wiring
*The kick start jumper must be in-circuit when using only a battery (i.e. no AC). Simply short the pins out with a screwdriver,
or use a jumper. Remove the short/jumper once the Panel Status LED lights up (indicating power up), as leaving it on
disables the low battery cut-out.*
Figure 1: Connection Diagram
Note: When using extra power supplies to power any peripheral connected to the keypad bus an IDS RS485 isolator (860-06-
0557) must be used.

9
IDS X-Series Installer Manual 700-398-02O
Installation Requirements
➢A suitable transformer with an output voltage of 16 VAC ±10% with a 32VA minimum rating must be used. A 40VA
transformer is recommended.
➢A 12V sealed lead acid battery with a capacity of 7AH must be used. The backup period after mains failure will depend on
the number of keypads, sensors, and bus-wired peripheral devices connected to the system.
➢Connect a 12V self-driven siren or piezo siren (not a horn speaker) to the siren output.
➢The panel can supply a total continuous current of 750mA to bus-wired peripheral devices such as keypads, remotes,
receivers, passives etc; from Aux 12V terminals.
End-of-Line Resistors
➢All zones, including Panic zones, are end-of-line supervised.
➢All zones, whether they are used or unused, need to be terminated with a 3K3 resistor (resistor colour-code is orange,
orange, red, gold).
➢For maximum security, the end-of-line resistor must be placed inside or as close to the sensor as possible.
➢For tamper by zone, 4K7 and 12K end-of- line resistors must be connected instead of a single 3K3 resistor.
➢If the panel is unarmed and a tamper condition occurs, the siren will not sound but a tamper condition will be reported if it
is enabled to do so. See Table 41to enable/disable this option.
➢If the panel is armed and a tamper condition occurs, an audible alarm will register, and a tamper condition AND zone
violation will be reported.
Box Tamper Input
The box tamper input does not require an end-of-line resistor, but does require a normally closed contact. The panel is shipped
with the box tamper input bypassed. To use it, remove the jumper and connect a normally closed contact onto the terminals.
Refer to Figure 1: Connection Diagram
Connecting the Telephone Communicator - Advanced
Refer to: Figure 1: Connection Diagram
For optimum lightning protection, connect a low resistance earth to the communicator earth input.
➢Connect the telephone communicator in line seizure mode and never in parallel with the telephone.
➢Ensure the telephone receiver is connected to the communicator terminals marked “phone” and the incoming line to the
terminals marked “line”.
Programmable Outputs
A relay must be used when any device requiring a current greater than 50mA is connected to an onboard programmable output.
The onboard programmable output circuitry is a current sink circuit with a maximum output voltage of 13.6Vdc and a maximum
output current of 50mA. Programmable outputs are primarily connected for radio transmitter. The output expander, part no.
860-06-0596, has eight 1 amp DC relays to be able to manage a higher current to be used for connecting, LEDs, sirens, bus-wired
peripherals, etc.
Key-Switchor Remote Control Unit
A key-switch, (not recommended) or non-IDS remote receiver maybe connected to any zone to allow remote arm/disarm and
remote panic capability.
➢When using a key-switch or remote control unit, a 3K3 resistor must be connected between the zone input and ground.
➢Use only a spring-loaded momentary key-switch or non-latching remote control unit.
Installing Expander Modules
When installing expander modules please refer to the document supplied with the module. Note that up to 6 bus-wired, 8-zone
expander modules (P/N: 860-06-X-08S), 1 plug-in expander (P/N: 860-06-X-08PI) and 2 bus-wired output expanders may be
added to the IDS X64 Alarm Panel. Zones 9-16 are reserved for the Plug-in Zone Expander module which may be used on the X16
as well.
IDS Remote Receiver
Up to 4 IDS Remote Receivers (P/N: 860-07-X02-DI) may be connected to the keypad Bus. Using this facility allows remote arming
and disarming of the panel while providing user identification for a maximum of 128 remotes. For a full list of features and
benefits of the receiver, please see the manual that comes with it.
Transmitter Connection
When connecting a GSM transmitter, use the TX terminal provided on the panel to supply power to the transmitter. This
output is protected by a 4 Amp fuse. This will also help protect the battery by cutting power to it to stop it from being drained.
Note: Do not use with high power transmitters that draw more than 1.5Amps.

10
IDS X-Series Installer Manual 700-398-02O
Hardware Default Switch
Use the hardware default switch (refer to Figure 1) to return the panel to its factory default settings.
The procedure to default the panel is as follows:
1. Remove the battery and AC power from the panel
2. If you are only using a battery make sure that the kick-start jumper is in circuit
3. Hold down the default switch and reapply power to the panel (battery or AC)
4. Wait for the Panel Status LED to flash
5. Release the default switch
6. Remove the kick-start jumper, if one was used
7. Defaulting is complete once the Panel Status LED starts flashing
The effects of applying the default:
1. Factory default values are restored to all locations
2. All attached keypad IDs are defaulted
3. The event log is not cleared
4. The “system default” event is logged to the event log
NOTE: The hardware default switch can be disabled in location 35.
See also: Defaulting the Panel or Master User Code –location 0Enrolling Keypads and Other Bus-wired Peripherals
Keypads
Keypads must be enrolled on the system before they can be used. Keypads are allocated an ID in the order in which they are
enrolled. To enrol a keypad:
1. Wire it to the keypad BUS
2. Power the system up
3. Press the[#]key
Repeat this process with the remaining keypads where more than 1 keypad is used. The first keypad enrolled will have an ID of
1, the second enrolled will have an ID of 2, the third an ID of 3 etc.
NOTE:
➢All the zone and LEDs will flash on a keypad that does not have an ID.
➢The POWER and READY LEDs will be on for a keypad that has an ID and no zone violations.
➢Only the POWER LED will be on for a keypad that has an ID with a zone violation. The LED for that zone will also flash.
Trouble shooting
If the ID process, for an LED keypad, has failed zones 1-8, and zones 9-16 will flash alternately. At this point press the [#] key to
retry.
If the flashing persists, try the following steps:
1. Check all wiring
2. Check that you have not exceeded 8 keypads on the bus
3. Contact the IDS helpdesk for further support
NOTE: To enrol other devices (IDS Remote Receivers or Zone Expanders); consult the installation manuals for those devices. The
IDS X64Alarm Panels can accept6 zone expanders and 4remote receivers.
Replacing a DamagedKeypad/Bus-wired Peripheral
To replace a damaged device (non-dipswitch –like a keypad):
1. Disconnect only the faulty device while the system is powered down.
2. Program a value of [4] into location 0 to free up all redundant IDs (previously unallocated IDs remain free), wait for
approximately 30 seconds then continue to step 3.
3. Connect the replacement device and enrol it –by pressing [#] for keypads –it will now be enrolled in the first available
address.
NOTE:
➢If other devices are disconnected (or damaged), at the time of performing step 2, their addresses will also be freed. Any
new devices being enrolled will automatically be allocated addresses beginning from the lowest free address.
➢When you free up the ID of the damaged unit, the panel settings, relevant to the ID, will be defaulted too. Therefore, the
keypad will need to be re-added to a partition.
➢If a new keypad was enrolled, go to location 243 to check the keypad’s ID (1-8).
Solution
If there are problems with device IDs on a complex installation, do not assign IDs randomly, rather, at the end of the installation,
default all device IDs and then enrol them in sequence.
To re-enrol a Zone Expander or a Remote Receiver; consult the installation instructions for the particular device.

11
IDS X-Series Installer Manual 700-398-02O
Defaulting Keypads
To default the ID of an individual keypad:
1. Remove power to the keypad (or the whole panel if easier).
2. Hold down the [1]and [3]keys simultaneously.
3. Restore the power.
4. Wait for three seconds and then release the keys (there will not be a beep).
5. All the keypad LEDs will flash simultaneously indicating that the keypad has been de-registered
4. Wait for five seconds and ensure that the Panel Status LED on the panel is flashing, if the panel power was removed.
5. Press the [#] key to allocate a new ID to the defaulted keypad. Keypad IDs are allocated incrementally.
6. The ID of any (correctly registered) keypad can be viewed in location 243 from the keypad of interest.
To default the ID of ALL keypads:
1. Enter a value of [3] into location 0.
[INSTALLER CODE] [*] [0] [*] [3] [*]
2. On pressing the final [*], wait a few seconds and ALL the keypad LEDs will begin flashing. (Do NOT press the [#] key at the
end of this sequence, unless you wish the keypad you are using to be registered in the first address).
3. Re-enrol all keypads by pressing the [#] key on each keypad –in the CORRECT sequence to ensure that keypad zone and
partition allocation is as required by the user.
4. Event Log
A comprehensive log of the 1 000 most recent events is retained in the non-volatile EEPROM. The log may be retrieved using the
up/download software, or on the LCD keypad. (See the LCD Keypad or User Manual to see how to view the event log).
IDSwift 2 software is available for account customers, to download event logs via direct serial download, or via a modem.
5. Access Codes
The panel supports up to 128 users. The user codes can have various properties assigned to them. These properties allow the
user codes to have different functions.
Normal User Code
A normal user code is used to arm/disarm the panel, and to access certain user options.
Master User Code
When assigned to a user, this property allows the user to act as a master user. The Master User Code has full access to
programming all the user options. For a full list of user programmable options, refer to the X-Series User Manual.
Maid’s Code (Arm to Disarm Code)
This property may be used to limit access to the premises. A Maid's Code will only disarm the system if the same code was used
for arming. If armed with a code other than this code, the system will view an attempt to disarm using a Maid's Code as an invalid
entry. Any valid user code will disarm the system if it has been armed with a Maid’s Code.
Duress Code
This property denotes a user code as a special code to be used in the unique situation where an intruder forces one to disarm
the system "under duress".
When the [DURESS CODE] is entered, the Alarm Panel disarms normally - however a DURESS REPORTING CODE is transmitted to
the monitoring company to inform them that you have been forced to disarm the Alarm Panel by an intruder.
It is advisable to choose a code that can easily be remembered by all family (or staff) members.
Installer Code
The Installer Code (location 197) is used by the installer to program and configure the Alarm Panel. It has full access to all installer
mode menus as listed in this manual.
Maintenance Code
The Maintenance Code (location 199) acts in a similar way to the Installer Code, but it has limited access to installer menus. The
default Maintenance Code is 8888, or 888888 for a 6-digit code. This code is used to access the following locations:
Locations 17 - 18
Siren Time & Delay
Locations 20 –22
Keypad Lockout and Sleep
Locations 25 –31
Daylight Savings
Locations 171 –173
No Movement, Auto Arm
Locations 174 –176
No Movement, Medical Alarm
Locations 180 –190
Auto Arm Times
The assignment of this property to a user allows the relevant user to perform certain “maintenance” tasks that would ordinarily
require the use of the installer code.

12
IDS X-Series Installer Manual 700-398-02O
Download Code
The Download Code, location 198, (in conjunction with the Installer Code) is required for download access via the IDS Download
Software. The default Download Code is 9999 or 999999 for a 6-digit code.
NOTE: It is possible to program location 34 to either allow or disallow defaulting of the Download Code.
6. How to Read Location Values
Values within a data program location will be displayed by the zone LEDs in binary coded decimal format i.e. zone LEDs 1-4
indicate units (ones) and zone LEDs 5-8 indicate tens (tens), and so on.
To read a binary value on the keypad, add up the values represented by each lit LED as shown in Table 1
Table 1: Values Represented by each Zone LED
Zone LED
Value
Digit
Zone LED
Value
Digit
Zone 1
1
Units
Zone 9
1
Hundreds
Zone 2
2
Zone 10
2
Zone 3
4
Zone 11
4
Zone 4
8
Zone 12
8
Zone 5
1
Tens
Zone 13
1
Thousands
Zone 6
2
Zone 14
2
Zone 7
4
Zone 15
4
Zone 8
8
Zone 16
8
EXAMPLE:
Imagine the following zone LEDs are on: Zone 1, Zone 3 and Zone 5.
Units are represented by the sum of Zone 1 and Zone 3 (i.e. 1 + 4).
Tens of units are represented by the value of Zone 5 (i.e. 1 x ten).
Therefore, the displayed value is (1+4) + (10) = 15.
Values within a time program location are displayed in a similar format as per Table 2.
Table 2: Binary Coded Decimal Four Digit Display
Zone LED
Calculation
Unit
Zone LED
Calculation
Unit
1
(x 1 = 1)
M
9
(x 1 = 1)
S
2
(x 2 = 0)
10
(x 2 = 2)
3
(x 4 = 4)
11
(x 4 = 4)
Mm:Ss
4
(x 8 = 0)
12
(x 8 = 0)
= 45:36
5
(x 1 = 1)
m
13
(x 1 = 1)
s
M = LEDs 4 through 1
6
(x 2 = 0)
14
(x 2 = 2)
m = LEDs 5 through 8
7
(x 4 = 4)
15
(x 4 = 1)
S = LEDs 12 through 9
8
(x 8 = 0)
16
(x 8 = 0)
s = LEDs 16 through 13
Using an LCD keypad means that data and time information can be read directly without a need to convert.
7. Programming of the Panel
The X-Series control panels is optimised to be programmed and use with an LCD keypad. The system can be programmed with a
LED keypad except for a few locations, will be highlighted when such locations are discussed. The following section describes
how programming data is represented in the X-Series panels and how to program it, specifically with the LED keypad.
For all programming procedures, the [*] key functions as the <ENTER> key and the [#] hash key functions as a<CLEAR> or an
<EXIT> program key.
Invalid data entries are indicated by means of an error beep consisting of 3 short beeps of the keypad buzzer.
There are two location categories:
➢Standard locations which are single tiered and do not contain any sub-locations.
➢Extended locations, which are double tiered and have strings or sub-locations depending on programming preference.
Both standard and extended locations may contain further sub-categories referred to as bitmapped locations.
For both main categories, clear visual keypad prompts are provided, which aid the programming process.
NOTE: When you use the [*] key to scroll through a bitmapped location, it will scroll through the pages.
When using the [*] key to scroll through numbered locations, it will scroll through the bytes.
➢Alpha-numeric locations (location 51 - telephone number), will show 1 digit per press of the [*] key.
➢Numeric locations (location 197 –installers code), will show 2 digits per press of the [*] key.
➢To view how the data is represented, please see Table 1.
Where a hexadecimal number must be programmed, use the [MODE] key as per Table 3.

13
IDS X-Series Installer Manual 700-398-02O
Table 3: Hexadecimal Values
Hex Value
Decimal Value
Key Strokes
Hex Value
Decimal Value
Key Strokes
A
10
[MODE] key then [0] key
D
13
[MODE] key then [3] key
B
11
[MODE] key then [1] key
E
14
[MODE] key then [4] key
C
12
[MODE] key then [2] key
F
15
[MODE] key then [5] key
NOTE: The hex values of A-F can be used for account codes. Only B-F can be used for phone numbers. This means that for
locations 50-54, Ais NOT a hex number –but is rather used to CLEAR a telephone number.
8. Programming Quick Reference Guide
Entering Program Mode
•[#] [INSTALLER CODE] [*] to enter program mode.
•A long beep will confirm entry.
•The READY LED will flash.
Programming Standard Locations
•The panel is in program mode –the READY LED is flashing.
•[LOCATION NUMBER] [*]
•The READY LED is solid on, and the AWAY LED will flash.
•Either [NEW DATA] [*] or [#] to exit.
•If data is entered, a long beep will confirm entry.
•In both instances, the READY LED will to flash and the AWAY LED will turn off.
•[#] to exit the READY LED will stop flashing.
•The panel is now in standby mode.
Programming Extended Locations with Strings
•Panel is in program mode –the READY LED is flashing.
•[LOCATION NUMBER] [*]
•The READY LED is solid on, and the ARM and AWAYLEDs will flash.
•[STRING][*]
•The ARM and AWAY LEDs turn off, and the READY LED will flash.
•If you do not want to change data press [#].
•The READY LED will continue to flash, whilst the ARM and AWAY LEDs turn off.
•[#] to exit the READY LED will stop flashing.
•The panel is now in standby mode.
Programming Extended Locations with Sub-locations
•Panel is in program mode –the READY LED is flashing.
•[LOCATION NUMBER] [*]
•The READY LED is solid on, and the ARM and AWAYLEDs will flash.
•[SUB-LOCATION NUMBER] [*]
•The READY and ARM are solid on, and AWAY is flashing.
•[NEW DATA] [*]
•The READY LED is solid on, and the ARM and AWAY LEDs will flash.
•[#] if you do not wish to make changes.
•The READY is flashing, and the ARM and AWAY LEDs turn off.
•[#] to exit current location.
•The READY is flashing, and the ARM and AWAY LEDs turn off.
•[#] to exit and the READY LED will stop flashing.
•The panel is now in standby mode.
Programming a Bitmapped Location
•Panel is in program mode –the READY LED is flashing.
•[LOCATION NUMBER] [*]
•The READY LED is solid, and the AWAY LED flashes.
•[#] to exit current location.
•READY is flashing.
•[#] to exit and the READY LED will stop flashing.
•The panel is now in standby mode.
For a more detailed programming explanation, please see the X-Series training manuals

14
IDS X-Series Installer Manual 700-398-02O
9. Programming Location Summary
A detailed description of each location and its options follow.
LOCATION 0 Defaulting the Panel or Master user Code
This location allows you to default the panel, user codes and their properties, and bus-wired peripherals. Refer to Table 4 for the
values, that can be programmed, and their actions.
[INSTALLER CODE] [*] [0] [*] [VALUE] [*]
Table 4: Defaulting Data
Value
Action
0
Will reset all locations and ID’s to the factory default values.(Master User Code 1234)
1
Will default the Primary Master User Code back to 1234 - or 123456 if 6 digits are being used.
Master User Code properties will also be defaulted.
2
Defaults ALL user codes and their properties.
3
Defaults ALL keypads.
4
Remove Missing Devices.
Any missing devices (keypads, for example), will have its address freed up, making its address available for a new
device when it is enrolled. This MUST be performed when replacing a faulty device. (You must wait for 30 seconds
from device failure or removal.)
5
Default “Central Monitoring Mode”. Defaults telephone numbers, dialling options, reporting options, reporting
code options and sets some options not to factory settings. (Implemented in vers.2)
6
Default “Private Reporting mode”.( sets some options not to factory settings) (Implemented in vers.2)
7
Defaults all wireless zones and settings
Zones
Location 1 –8 Individual Zone Type Setup
These locations allow you to program the zone types for zones 1-64.The zones are divided into 8 zones per location. After the
zone type is programmed for zones 9 through 64, they will need to be assigned to a partition before being enabled.
Refer to Partition Options to see how to add zones to partitions and what options are available.
Each location represents a set of 8 zones:
➢Location 1 zones 1-8 (X8)
➢Location 2 zones 9-16 (X16)
➢Location 3 zones 17-24 (X64)
➢Location 4 zones 25-32 (X64)
➢Location 5 zones 33-40 (X64)
➢Location 6 zones 41-48 (X64)
➢Location 7 zones 49-56 (X64)
➢Location 8 zones 57-64 (X64)
Refer to Table 5: Zone Types
NOTE:
➢If you require a panic zone whose status can be viewed on a keypad, Do NOT use the dedicated panic as it cannot be
viewed on a keypad.
➢Zones 1-8 are onboard zones.
➢Zones 9-16 are plug-in expander zones. (supported only by X16, X64)
➢Zones 17-64 are expander zones. (supported only by X64)

15
IDS X-Series Installer Manual 700-398-02O
Table 5: Zone Types
Value
Zone Type
00
DISABLED
A zone violation of a Disabled zone is ignored by the Alarm Panel and will not be indicated on the keypad.
01
PRIMARY ENTRY/EXIT ZONE
Violations of an Entry/Exit zone are ignored during the exit delay period of the arming procedure. Violating an
Entry/Exit zone when armed will initiate the entry delay period. If a valid User Code is not entered before the entry
delay period expires, an alarm condition will be registered. Failure to exit through an Entry/Exit zone after arming will
cause the panel to Stay Arm. This zone may also function as an Entry/Exit zone that is COMMON to two partitions. In
such a case, should a user violate this zone and then disarm this partition, the OTHER partition will re-arm after the
entry delay.
02
FOLLOWER ZONE
A Follower zone is not monitored during the Entry/Exit delay period; therefore it will not cause a violation. This allows
the user to enter/exit via the Follower zone. A Follower zone will behave as an Instant zone while the panel is armed
and an Entry/Exit zone is not violated prior to violation of the Follower zone.
03
PANIC/PRIORITY ZONE
Regardless of whether the panel is armed or not, a violation of a Priority zone will cause the Alarm Panel to register a
panic condition. This zone type CANNOT be bypassed.
04
INSTANT ZONE
Violation of an Instant zone will cause the Alarm Panel to register an alarm condition.
05
ARM/DISARM ZONE
Violation of an Arm/Disarm zone will cause the panel to toggle between (away) armed and disarmed. It is typical to
connect a momentary key-switch, or non-latching remote control unit to this zone. NOTE: A zone must be added to a
partition in order for it to arm.
08
SECONDARY ENTRY/EXIT ZONE
The Secondary entry delay will be activated if this zone is violated while the panel is armed.
09
Instant Fire Zone(New)
Zone triggers on the first violation and triggers a standard fire alarm signal
10
FIRE ZONE
Violation of a Fire zone will cause the siren to sound regardless of whether the panel is armed or not. The siren will
sound intermittently (one second on, one second off). For correct operation, a programmable output programmed as
a fire detector power output must be used to control power to the fire detector (refer to Table 36)
11
TAMPER ZONE
Violation of a Tamper zone will be reported to the base station regardless of whether the panel is armed or disarmed.
If the panel is armed, the siren will sound.
12
24 HOUR ALARM ZONE
Regardless of whether the panel is armed or not, a violation of a 24 Hour Alarm zone will cause the Alarm Panel to
register a panic condition.
13
WARNING ZONE
Violation of a Warning zone will cause the siren to beep. The violation is logged in the event log but it is not reported
to the base station. Warning zones may be included and will be counted when used as part of the cross-zone.
14
PUSH TO ARM ZONE
Violation of a Push to
A
rm zone during the exit delay will immediately arm the panel.
15
OUTDOOR INSTANT ZONE
Violation of an Outdoor Instant zone will cause the panel to register an alarm condition.
NOTE: This is a reporting code and it functions in the same way as zone type 04.
How to program using the string method:
To program 8 zones at a time, fill in a row with the corresponding zone types (2 digits per type, found in Table 5: Zone Types)
and enter these values as one long 16-digit string for location 1. This method can be used for the remaining 56 zones by noting
that location 2 references zones 9 to 16, location 3 references zones 17 to 24, etc.
I.e. To program the defaulted zone types (Table 6) for the first 16 zones use the following:
[INSTALLER CODE] [*]
[1][*] reference zones 1 - 8
[0102040404040404][*]
[2][*] reference zones 9 - 16
[0000000000000000][*]

16
IDS X-Series Installer Manual 700-398-02O
How to program using the sub-location method:
To program zones using the sub-location method, program 1 (as indicated by “[]” sub-location (followed by the [*] key) and then
enter the zone type (followed by the [*] key). Then press the [*] key again to advance to the next sub-location. For sub-locations,
the zone type does not have to be 2 digits, i.e. enter 1 or 01.
To repeat for further zones, enter the second zone number (followed by the [*] key) and then the zone type (followed by the [*]
key). This can be repeated for all 64 zones.
I.e. To program the defaulted zone types for the first four zones use the following:
[INSTALLER CODE] [*]
[1][*] reference zones 1 - 8
[1][*][1] [*] [*] zone 1, zone type 1
[2][*][2] [*] [*] zone 2, zone type 2
[3][*][4][*] [*] zone 3, zone type 4
[4][*][4] [*] [*] zone 4, zone type 4
How to program using the [*] key to advance:
A third method to program zones using the star advance method is to enter the location number corresponding to a group of 8
zones you wish to program. Each press of the [*] key will step through a zone.
I.e. To change zone 12 to an Instant zone, use the following:
[INSTALLER CODE] [*]
[2][*] reference zones 9 –16
[*] move to zone 10
[*] move to zone 11
[*] move to zone 12
[4][*] zone type 4
Table 6 represent the default zone types for the 64 zones represented in 2 different programming methods.
Table 6: Zone Types in String Format
Zones
Loc
Sub-loc
As Strings
Zone Type
1 - 8
1
n/a
0102040404040404
ref above table
9 - 64
2 - 8
n/a
0000000000000000
All Disabled
Table 7: Zone Types in Sub-location Format
Zone
Loc
Sub-Loc
As Sub-locations
Zone Type
1
1
1
01
Entry / Exit
2
1
2
02
Follower
3
1
3
04
Audible Instant
4
1
4
04
Audible Instant
5
1
5
04
Audible Instant
6
1
6
04
Audible Instant
7
1
7
04
Audible Instant
8
1
8
04
Audible Instant
The valid data range is: 00 –05, 08, 10 –15.
Global Setup
LOCATION 9 Trouble Display 2
This location determines which trouble conditions are indicated on the keypad by a flashing POWER LED. The POWER LED will
only stop flashing once the trouble condition has been cleared. Trouble conditions will be reported if programmed to do so in
locations 571 and 572, regardless of whether or not they are enabled for display.
To view, hold down the [7] key until the keypad beeps. See “Viewing Trouble Conditions” in the User manual.
Note: These trouble conditions cannot be viewed by LED Keypads
LED
Default
Action
1
OFF
AC fail monitored power supply
2
OFF
Low battery monitored power supply
3
OFF
Fuse fail on monitored power supply
➢AC Fail Monitored Power Supply
This occurs when the monitored power supply does not receive any power from your mains electricity. Check if a power
failure has occurred, or your transformer is not plugged in or faulty.
➢Low Battery Monitoring Monitored Power Supply
This trouble condition will be caused by the battery voltage dropping below 11.3V.
➢Fuse Fail Monitoring
This trouble condition indicates that the fuse on the monitored power supply has blown.

17
IDS X-Series Installer Manual 700-398-02O
LOCATION 10 Zone Shutdown Count (default = 5)
This location determines the number of times a zone may be violated while the panel is armed before it is automatically bypassed.
Disarming the panel will clear all bypassed zones.
The Zone Shutdown Count set here applies to all zones that have option 3 (shutdown zone) enabled in locations 101-164.
[INSTALLER CODE] [*] [1] [0] [*] [ZONE SHUTDOWN COUNT] [*]
The valid data range is: 1 –15.
LOCATION 11 Programmable Zone Loop Response Time (default = 2)
The zone loop response time is the period of time for which a zone must remain violated before a violation is registered. The
time is calculated in 12 millisecond increments starting at 12ms. A partial table between the values of 1 and 255 is shown in Table
8; times not shown on the table can be calculated as per the following example:
198 x 0.012 = 2.38 seconds.
To program the time into this location, the format is [SSS].
[INSTALLER CODE] [*] [1] [1] [*] [ZONE LOOP RESPONSE TIME] [*]
The valid data range is: 1 –255.
Table 8: Loop Response Time Data
Value
Response Time
Value
Response Time
Value
Response Time
Value
Response Time
1
12 ms
10
120 ms
60
720 ms
180
2.16 seconds
2
24 ms
12
144 ms
75
900 ms
210
2.52 seconds
3
36 ms
14
168 ms
90
1.08 seconds
240
2.88 seconds
4
48 ms
15
180 ms
120
1.44 seconds
255
3.06 seconds
5
60 ms
30
360 ms
150
1.80 seconds
105
1.26 seconds
LOCATION 12 Cross-zone Delay Time (default = 0030)
This location defines the cross-zone delay timer period in minutes and seconds, and it is used in conjunction with location 13.
(This is an advanced location).
To program the time into this location, the format is [MMSS].
[INSTALLER CODE] [*] [1] [2] [*] [MMSS] [*]
The valid data range is: 00m00s –59m59s.
LOCATION 13 Cross-zone Count (default = 3)
If the panel is armed and the total number of violations of zones programmed as cross-zones (locations 101-164) or a single
cross-zone reaches this count within the time period programmed into location 12, an alarm condition will be registered.
[INSTALLER CODE] [*] [1] [3] [*] [CROSS-ZONE COUNT] [*]
The valid data range is: 1 - 15, with 0 to disable.
LOCATION 14 Global Options
This location allows you to configure the global options for the X-Series Alarm Panel. Table 9 shows the available options.
NOTE: For each enabled option, the corresponding locations that configures the option must be correctly programmed.
See Location 19: Extra Global Options for more global options
Table 9: Global Options Data
LED
Default
Action
LED
Default
Action
1
ON
A user assigned to any partition may cancel
the siren
9
ON
Siren monitoring
2
OFF
Keypad trouble beep
10
OFF
Bus-wired peripheral tamper monitoring
(Option 9 in location 16 must be enabled)
3
OFF
Telephone line monitoring
11
OFF
Onboard dedicated panic –audible
4
OFF
Keypad beep on successful reporting to the
base station
12
ON
Low battery monitoring (Must be ON for
option 13 to work)
5
ON
Keypad Fire, Medical and Panic Keys
13
ON
Low battery cut-out (See option 12)
6
ON
The display of bypassed and stay zones when
armed
14
OFF
Bypassing with user code
7
OFF
Siren delay
15
OFF
Dedicated panic zone bypassing
8
ON
Box tamper monitoring
16
OFF
Remote transmitters to cancel panic
NOTE: If mains power is present, then the battery is monitored every 30 minutes and with no mains every minute. If the
battery voltage drops below 10V, then the battery will cut-out if option 13 is enabled. If the battery voltage drops below 11V,
then option 12 will be reported if it is enabled.

18
IDS X-Series Installer Manual 700-398-02O
LOCATION 15 AC Fail Reporting Delay (default = 0004)
In the event of a power failure (although instantly displaying the trouble indication) the panel will wait for this period of time
before REPORTING the mains failure to the base station. This delay eliminates unnecessary reporting if the AC power is removed
for a short time period. It is important to note that an AC restoral will only be reported if an AC failure was reported first, i.e. the
delay period was exceeded.
To program the time into this location:
[INSTALLER CODE] [*] [1] [5] [*] [HHMM] [*]
The valid data range is: 00h01m –18h00m.
Note: The restoral event is reported and logged within a minute of AC being restored.
LOCATION 16 Trouble Display Enable
This location determines which trouble conditions are indicated on the keypad when viewing the trouble display. A trouble
condition is indicated by a flashing POWER LED. The POWER LED will only stop flashing once the trouble condition has been
cleared. Trouble conditions will be reported if programmed to do so in locations 571 and 572, regardless of whether or not they
are enabled for display.
To view, hold down the [7] key until the keypad beeps. See “Viewing Trouble Conditions” in the User manual.
Table 10: Trouble Display Options available for viewing
LED
Default
Action
1
ON
AC fail trouble display
2
OFF
Reporting communication fail trouble display
3
OFF
Telephone monitoring line trouble display
4
ON
On-board siren monitoring trouble display
5
ON
Low battery monitoring trouble display
6
OFF
Aux. 12V monitoring trouble display
7
OFF
Engineer’s reset trouble display
8
ON
Box tamper trouble display
9
OFF
Bus-wired peripheral tamper trouble display
10
OFF
Bus-wired peripheral fail trouble display
11
OFF
Bus-wired peripheral low power/battery trouble display
12
OFF
Wireless detector battery trouble
13
OFF
Wireless detector supervision trouble
14
OFF
Wireless detector RF jam trouble
15
OFF
Wireless detector low RSSI trouble
16
OFF
Zone tamper trouble condition
Explanation of Trouble Conditions
➢AC Fail
This occurs when the Alarm Panel does not receive any power from your mains electricity. Check if a power failure has
occurred, or your transformer is not plugged in or faulty.
This trouble condition will only clear once the power has been restored.
➢Reporting Communications Failure
This occurs when communication to the monitoring company is not successful.
The event will clear upon exiting the trouble viewing mode.
➢Telephone Line Monitoring
The causes of this could be a fault, or short, on the phone line; or the phone line could be cut.
This trouble condition will only clear once the phone line restored.
➢Siren Monitoring
This can occur when the siren has been removed or the siren fuse on the panel has blown.
This trouble condition will only clear once the siren or fuse has been replaced.
➢Low Battery Monitoring
This trouble condition can be caused by a low battery voltage, a dead battery, or no battery. If the battery is there, try
charging it. If this not does work, then the battery needs to be replaced.
This trouble condition will only clear once the battery voltage has been restored.
➢Aux 12V Monitoring
This trouble condition indicates that the fuse has blown, or that there is a fault
This trouble condition will only clear once the fault has been restored.

19
IDS X-Series Installer Manual 700-398-02O
➢Engineer’s Reset
An alarm condition has occurred, the Installer needs to come and clear the condition by entering an installer code. The
panel cannot be armed until this has occurred, nor will the trouble condition clear.
➢Box Tamper
The metal housing where the panel is stored has been opened.
To clear trouble condition, make sure the door to the housing is closed and then view the trouble condition.
➢Bus-wired Peripheral Tamper
This trouble condition indicates that a keypad, remote receiver or bus-wired zone expander has been tampered with.
To clear this trouble condition, restore the tampered device and then view the tamper.
➢Bus-wired Peripheral Fail
The panel has lost communication to one of the peripherals attached to it.
➢Bus-wired Peripheral Low Power / Battery
Supply voltage to a peripheral has dropped below the recommended limit.
➢Wireless Device Battery
This trouble condition indicates a wireless device’s battery needs replacing
➢Wireless Device Supervision
A wireless device has gone missing
➢Wireless Receiver RF Jam
A signal has been detected on the same frequency which may cause signal loss
➢Wireless Device RSSI
RSSI means a wireless device has checked in but the signal strength was very low
➢Tamper
A device has reported being interfered with
LOCATION 17 Siren Time Out Period (default = 0200)
The siren time out period is the period of time for which the siren will sound after an activated.
To program the time into this location, the format is [MMSS].
[INSTALLER CODE] [*] [1] [7] [*] [MMSS] [*]
The valid data range is: 00m01s –59m59s.
LOCATION 18 Siren Delay (default = 0200)
This location sets the siren delay period between when an audible alarm condition is registered and the siren is activated. The
alarm condition will however be reported to the base station as soon as it occurs. Panic zones and Fire zones will cause an
immediate siren even if siren delay is programmed.
Option 7 in location 14 (Global Options) must be enabled for the siren delay to have an effect.
To program the time into this location, the format is [MMSS].
[INSTALLER CODE] [*] [1] [8] [*] [MMSS] [*]
The valid data range is: 00m01s –59m59s.
LOCATION 19 Extra Global Options
This location allows you to configure more global options for the X-Series Alarm Panel.
Table 11: Extra Global Options
LED
Default
Action
1
OFF
Zone violation when wireless supervision loss is detected (Wireless detector)
2
OFF
Voice module lockout to follow keypad lockout settings
3
OFF
24Hour zone report only (Makes all 24Hr zone silent)
4
OFF
Box tamper always triggers the siren
5
OFF
Bus-wired peripheral tamper always triggers the siren
6
OFF
Zone tamper always triggers the siren
7
OFF
Voice module answers before modem
LOCATION 20 Keypad Lockout Count (default = 4)
If a partition has a keypad lockout enabled, the value entered in this location determines the number of consecutive incorrect
codes to activate a keypad lockout. The keypad will remain locked for the time programmed in location 21. Activating a Keypad
Panic (or dedicated panic zone or entering a duress code) will unlock the keypad.
Option 4 in locations 221-228 (Extended Partition Options) must be enabled for the keypad lockout count to have an effect.
[INSTALLER CODE] [*] [2] [0] [*] [KEYPAD LOCKOUT COUNT] [*]
The valid data range is: 2 –16.
On = Enable Off = Disable

20
IDS X-Series Installer Manual 700-398-02O
LOCATION 21 Keypad Lockout Time (default = 0030)
The value determines the period of time for which the keypad will remain locked out if the keypad lockout count programmed
into location 20 has been exceeded. After this period has elapsed, a locked out keypad will return to an unlocked state. Keypad
lockout is enabled by partition; refer to locations 221-228 for extended partition options, but this period applies to all partitions.
To program the time into this location, the format is [MMSS].
[INSTALLER CODE] [*] [2] [1] [*] [MMSS] [*]
The valid data range is: 00m01s –59m59s.
LOCATION 22 Keypad Sleep Delay (default = 0500)
This location sets the time out period before the keypad enters sleep mode. After the delay period, if there is no keypad activity
(on any keypad) the backlighting and all other status and alarm LEDs will turn off.
The following events will bring a keypad out of sleep mode: Zone violations/restorals, Tamper violations/restorals, or key presses.
To program the time into this location, the format is [MMSS].
[INSTALLER CODE] [*] [2] [2] [*] [MMSS] [*]
The valid data range is: 00m01s –59m59s.
LOCATION 23 User, Installer & Maintenance Code - Number of Digits (default = 4)
This location determines whether user, installer and maintenance codes are 4 or 6 digits in length. The value programmed into
this location has no effect on the download code, which is always 4-digits in length.
If the code length is changed from 6 to 4, then all user codes are automatically set to their default values as per Table 12. This is
to avoid duplicate codes being inadvertently created when they have the same first 4 digits.
Table 12: Number of Digits Data
Code
Old four-digit code
New six-digit code
Installer Code
9999
999999
Maintenance Code
8888
888888
Master User Code 1
1234
123456
[INSTALLER CODE] [*] [2] [3] [*] [NUMBER OF DIGITS] [*]
The valid data range is either 4 or 6.
LOCATION 24 Number of Account Code Digits (default = 4)
This location sets the account code length to either 4 or 6 digits. If the length of your account codes is 4 digits and then they are
changed to 6 digits, the last two digits will be set to 0.
[INSTALLER CODE] [*] [2] [4] [*] [NUMBER OF DIGITS] [*]
The valid data range is: 4 or 6.
Daylight Savings
LOCATION 25 Month to Start Daylight Saving (default = 0)
Select the month for Daylight Saving to commence, as per Table 13.
Table 13: Month Data
Value
Month
Value
Month
Value
Month
Value
Month
Value
Month
0
Disabled
3
March
6
June
9
September
12
December
1
January
4
April
7
July
10
October
2
February
5
May
8
August
11
November
[INSTALLER CODE] [*] [2] [5] [*] [MONTH] [*]
NOTE: If this location is disabled, then by default, locations 26 and 27 will also be disabled. This means that even if you put values
into locations 26 and 27, daylight savings will not commence.
LOCATION 26 Day of Week to Start Daylight Saving (default = 1)
Select the day of the week for Daylight Saving to commence, as per Table 14.
Table 14: Day of Week Data
Value
Day
Value
Day
1
Monday
5
Friday
2
Tuesday
6
Saturday
3
Wednesday
7
Sunday
4
Thursday
[INSTALLER CODE] [*] [2] [6] [*] [DAY] [*]
Other manuals for X Series
7
Table of contents
Other IDS Control Panel manuals
Popular Control Panel manuals by other brands

LST
LST Vds EN 12094-1 Brochure & specs

RIB
RIB KS2 manual

Pentair Pool Products
Pentair Pool Products EasyTouch 8 Installation and user guide

Fike
Fike Twinflex pro2 Engineering and Commissioning Manual

Siemens
Siemens SINAMICS Series operating instructions

Ferroli
Ferroli DISPLAY UTILITY Installation, use and maintenance manual