Ier GNR5C User manual

SU0246.DOC 05/04 Änderungen vorbehalten!
Operating Instructions
GNR5C
Sight-Glass Level Controller
Figure. 1: GNR5C with threaded connectors and 2
BSM500W_/d34 bistable switches
Attention!
• Use with low-viscosity media only which
neither tend to become sticky or encrusted,
nor precipitate crystals. Media may not
contain magnetic particles (e.g. metal chips).
• Use only type S5/25d floats.
• The float must be installed with the “TOP”
marking at the top.
• Observe maximum temperature and pressure
ratings.
• Do not allow to tilt during installation! Centre-
to-centre distance and squareness of the
flanges or threaded connectors should be
checked before installing the glass tube.
• Observe correct installation order for sealing
rings (see drawing next page).
Functional Principle:
The GNR5C sight-glass level controller is mounted to the
side of a vessel or a tank. The gauge is filled with liquid
media to the same level as the tank via two shut-off
valves.
A magnetic float is located within the standpipe, which
indicates the current fill-level.
The glass tube is protected against damage with a
semicircular impact guard made of transparent PVC.
The magnetic float can also be used to activate optionally
available BSM 500 W... bistable switches (see also data
sheet SU0090).
Technical Data
Standpipe Glass, DURAN. 34.5 x 2.75 mm
Float Polypropylene (PP), type S5/25d
Fittings Stainless steel 1.4404/316L with
EPDM sealing
Seals Silicon rubber
Operating temperature 0 to + 110° C (120° C intermittent)
Operating overpressure max. 1 bar
Length (flange centre-to-
centre) 300 to 2000 mm
Mounting Flange: DIN 2642 DN 25 PN, steel
alternatively DN20 PN10 steel
or
threaded connector: G½" or G1"
Discharge stopcock
(optional) stainless steel 1.4404
Electrical components BSM 500 W... bistable switch
with 34 mm dia. pipe clamp
Installation Procedure:
GNR5C with Flanges:
• Mount the top and bottom shut-off valves to the tank
flanges using suitable sealing materials. Do not yet
fully tighten the screws.
• Insert the 11 x 12 x 5 mm silicon discs into the shut-off
valves.
• Push the hose clamps for fastening the impact guard
and the sleeve nuts, along with the silicon rings (which
have been snapped into place inside the nuts), over
the standpipe (see figure 2).
• Insert the standpipe between the shut-off valves
making sure that is square.
• Check the length of the glass tube! The tube must fit
flush against the silicon discs. Loosen the flange
screws if necessary to correct distance and
squareness.
• Retighten the flange screws.
• Push the sleeve nuts up to the shut-off valves and
tighten (46 mm open-end wrench).
Tighten the sleeve nuts!
• Attach BSM 500 W… bistable switches if used (the
cable gland must always point down).
• Mount the transparent impact guard (see figure 2).
• After the vessel has been filled, check all fittings for
leaks!
Operating Instructions:
GNR5C
Sight-Glass Level Controller
SU0246.DOC 05/04 Änderungen vorbehalten!
GNR5C with Threaded Connectors:
• Mount the top and bottom shut-off valves to the
threaded connectors at the tank using suitable sealing
materials.
• Insert the 11 x 12 x 5 mm silicon discs into the shut-off
valves.
• Push the hose clamps for fastening the impact guard
and the sleeve nuts, along with the silicon rings (which
have been snapped into place inside the nuts), over
the standpipe (see figure 2).
• Insert the standpipe between the shut-off valves
making sure that is square.
• Check the length of the glass tube! The tube must fit
flush against the silicon discs. Correct if necessary.
• Push the sleeve nuts up to the shut-off valves and
tighten (46 mm open-end wrench).
Tighten the sleeve nuts.
• Attach BSM 500 W… bistable switches if used (the
cable gland must always point down).
• Mount the transparent impact guard (see figure 2).
• After the vessel has been filled, check all fittings for
leaks!
Maintenance:
If used for its intended purpose, the GNR5C is
maintenance-free.
However, the magnetic float accumulates any magnetic
particles which may be present in the medium over a
period of time. In order to prevent operating errors, the
float should be cleaned to remove magnetic particles at
regular intervals.
In order to clean the float, close both shut-off valves and
empty the medium from the glass tube by opening the
stopcock.
Check the condition of the seals during reassembly and
replace if necessary.
Fig.. 2:
GNR5C with Threaded Connectors:
IER Meß- und Regeltechnik
Eberhard Henkel GmbH
Innstrasse 2
68199 Mannheim
Tel.+49-(0)621-84224 0
z
Fax:+49-(0)621-84224 90
e-mail: [email protected]
z
Internet: www.IER.de

Popular Controllers manuals by other brands

Fleck 3200 NT manual

Fleck

Fleck 3200 NT manual

Crane 633 Instructions for installing

Crane

Crane 633 Instructions for installing

NetApp ASA C400 Install

NetApp

NetApp ASA C400 Install

CKD AXD Series instruction manual

CKD

CKD AXD Series instruction manual

Dräger REGARD-1 Installation, operation and maintenance guide

Dräger

Dräger REGARD-1 Installation, operation and maintenance guide

SUSS CIC1200 user manual

SUSS

SUSS CIC1200 user manual

Nidec Unidrive M400 series quick start guide

Nidec

Nidec Unidrive M400 series quick start guide

Sinope Calypso RM3500ZB installation guide

Sinope

Sinope Calypso RM3500ZB installation guide

Sollatek AVR instruction manual

Sollatek

Sollatek AVR instruction manual

dymax BlueWave AX-550 user guide

dymax

dymax BlueWave AX-550 user guide

ControlByWeb X-400C quick start guide

ControlByWeb

ControlByWeb X-400C quick start guide

Steca TR 0704 Installation and operating manual

Steca

Steca TR 0704 Installation and operating manual

Horizon Hobby E-FLITE EFLA1010 instructions

Horizon Hobby

Horizon Hobby E-FLITE EFLA1010 instructions

Lumel SPC5 Service manual

Lumel

Lumel SPC5 Service manual

Johnson Controls PENN P28 installation instructions

Johnson Controls

Johnson Controls PENN P28 installation instructions

Regin RVAZ4L1-230 Instruction

Regin

Regin RVAZ4L1-230 Instruction

Azbil C25 user manual

Azbil

Azbil C25 user manual

Carrier CCU Control manual

Carrier

Carrier CCU Control manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.