Installation manual iNELS RF Control18 19Installation manual iNELS RF Control
For dimmers in general, the output vs. maximum load
should not be more than 70%.
Furthermore,dimmer cooling is a valid concern there-
fore do not install dimmers next to each other or with
another source of heat (or contact, whose switching
produces EMC and thereby may aect the correct
operation). For all ELKO EP dimmers there is an inte-
grated thermal fuse, which at elevated temperatures
above 82 °C deactivates the output of the dimmers
(indicated by a blinking LED), while activated the dim-
mer cannot of course be controlled. After cooling it-
self, dimmer control is again possible It is advisable to
move dimmer, to prevent recurrence.
To eliminate noise interference of switching contacts
(and thanks to the electronic switching) dimmers can
also be used for switching smaller loads such as fans.
One of the great advantages of iNELS RF Control is
a range of universal dimmers with the marking RFDEL
and connection of existing keys on installing terminal
„S“. Their versatility is performed by setting the light
source R, L, C, LED, ESL and also the possibility to set
4.2 Dimming components
the minimum luminance value - this (especially for
LED light sources) eliminates flicker during dimming.
Load light source (circuit) in the case of the classic
resistive load can be calculated easily, however, with
the LED light source, the issue is greater.
A common issue in this context is how many LED light
sources can be connected to the dimmer?? Did you know
that even though the manufacturer indicates the load
parameters of the dimmer , you have not yet won? Why?
Each dimmer has overload protection which reacts
at a certain peak current value. Each load (incandes-
cent, LED, energy-saving lamps) has some power. The
manufacturer usually indicates this on the package.
But there is no specified peak current value of the
load. And because each LED or energy-saving lamp
has some electronics inside, the peak current values
for dierent products can vary widely. For this reason,
you can not generally determine the number of indi-
vidual LED bulbs, so you cannot know this value. Out-
side of testing a specific number of pieces. We have
tested the dimmer for you.
The following information is particularly important
for Thermal components.
The thermal component sends the measured tem-
perature value to the system controller at regular 5
minute intervals. If there is a sudden temperature
change it can send it within 1 minute. Sudden chang-
es in temperature means a decrease/increase in the
temperature by 3 °C since the last transmitted value.
However, if the temperature change is of less than
3 °C the component send the information to the sys-
tem controller at the next 5 min regular interval.
Another reason for this is that if the household pow-
er supply operates on a two taris (D25d) and after
switching on the heating element will begin to heat
during the more expensive tari. In case of a situa-
tion where the heating element loses communica-
tion with the system, as part of the its security func-
tion it turns itself o.
Safety features of thermal components:
RFSA-6x RFSTI-11B or G, these components can be
assigned for the switching of heating.
RFSA-6x is controlled by the Smart RF box (eLAN-
RF) using a delayed shutdown with a time of 5 min-
utes. This means that if eLAN has ceased commu-
nicating (e.g. Loss of power) the relays are always
safely o. The Smart RF box eLAN-RF regulates
temperature and responds whenever the status
changes (temperature change, regime change) and
the relay turns o/on according to the current re-
quirement. In case that the message is not received
by the RF component (crosstalk, interference, loss
of power supply units) The eLAN command is re-
peated every two minutes.
RFSTI-11B/G has within its self a secure autonomous
OFF only with eLAN an ON or OFF. If communica-
tion is lost,The relay switches itself o in 5 minutes
and the LEDs on the panel start flashing in red. The
component its self at intervals of about five minutes
sends the measured temperature to the eLAN and
checks that it matches feedback report. The compo-
nent evaluates as valid and communicates this The
relay will stay on. The relays safety functions thus,
responding to commands on/o, but also to the
temperature.
After successful installation, the wireless RFATV-1
thermo value takes 3 minutes to adapt (this is the
time it takes to open and close the valve).Wireless
thermo valve RFATV-1 has software installed that
adapts to the environment, direction and speed of
the increase/decrease in temperature over the next
14 days (operation is not aected). The benefit is an
eective control method,which allows the valve to
react to temperature changes proportionally.
In the event of pulling out the batteries of wireless
RFATV-1 valve (if you had an oset temperature)
This should be set again in iHC-MARF/MIRF.
What happens after a power failure of the system
unit (ELAN-RF ...) in the case functionality with the
wireless thermal head RFATV -1?
4.3 Temperature components
Check out the following summary table of the lamps load capacity:
More on dimmers in the dimming brochure:
http://www.elkoep.cz/reseni/stmivani-svetel/
http://www.elkoep.cz/ke-stazeni/rele/brozury/
How to determine the maximum connectible lamps:
Power factor of dimmable LEDs and ESL bulbs ranges cos =
0.95 to 0.4. The approximate value of maximum load you get
by multiplying the load capacity of the dimmer by the power
factor of the connected light source.
If you do not know the above, we recommend the use of lights
from ELKO lighting sources, which of course we have tested.
In the event that the final desired temperature was
greater than 21 ° C, then the wireless thermal head
RFATV -1 will autonomous heat to 21 ° C. When the
last required temperature was less than 21 ° C, then
RFATV-1 will autonomous heat to the last set tem-
perature.
When changing the water pressure in the heating
circuit (water filling during maintenance) re-cali-
brate the RFATV-1 according to the instructions to
ensure proper process functionality.
In general, with all temperature components you can
adjust the system controller or application:
Function:
HEATING/COOLING
OFFSET: The adjustable temperature correction of
the measured element (which is aected by mount-
ing in an installation box or a switching temperature
relay, which produces heat) vs real.
HYSTERESIS: A delay in response to regulatory in-
tervention: eg. When the valve shuts o the hot wa-
ter in the radiator, the room temperature will con-
tinue to rise because the radiator is full of hot water.
Conversely, when although the valve is open, tem-
perature decreases, as it will take a long time before
the radiator is filled with hot water.
The length of the external temperature component
sensor can be 10 cm, 3 m, 6 m, 12 m, however, it can
be extended with a cable up to 30m max. Cross-
section 2 x 2.25, It is not recommended to run in
parallel with power lines.
When installing a wireless thermo valve, these adapt-
ers that are compatible with valves are included:
LED bulbs LED spotlights LED panels LED/RGB strips
DLB-E27-
806-2K7
DLB-E27-
806-5K
DLSL-GU10-
-350-3K
LSL-GU10-
350-3K
LSL-GU10-
350-5K
LP-6060-
3K
LP-6060-
6K
LED strip
7.2W
LED strip
14.4W
LED strip
19.2W
LED strip
28.8W
RGB strip
7.2W
RGB strip
14.4W
quantity quantity quantity quantity quantity quantity quantity quantity quantity quantity quantity quantity quantity
RFDSC-71 21 21 45 25 -----------------
RFDEL-71B 11 11 25 13 13----------------
RFDA-73M/
RGB --------------
3x8 m 3x4 m 3x5 m 3x4 m 20 m 10 m
RFDAC-71B----------
50 50------------
Load capacity
light sources