Ingersoll-Rand VON DUPRIN 7311 User manual

VON DUPRIN
Partof worldwide Ingersoll-Rand
941604-00
© Copyright 1993,Von Duprin, Inc. Printed in U.S.A.
•
•

1.
.
D
5.
General Description
The Von Duprin 7311 keypad is a self-contained
access control unit which fits in a single-gang
electrical box. It requires a power supply and locking
device to make a complete system. The keypad uses
non-volatile solid state memory so when power fails
or is removed, programmed memory is retained. The
Von Duprin 7311 keypad holds 100different codes
(user positions 1through 100). All programming is
accomplished through the keypad. The keypad has
multiple inputs and outputs preprogrammed for
specific functions. Two inputs are available: a
request-to-exit switch that operates the unlock relay
and a door position switch. One standard SPOT
(single-pole, double-throw) output is used for lock
control.
The Von Duprin 7311 keypad is available with an
optional plug-on 7308 relay board which provides
three additional SPOT output relays. These relays
can operate an alarm shunt output and signalling
features to report a door open, duress code input, or
keypad lockout due to incorrect code entries.
7311 Packing Checklist
i.
731
i
Keypad
2. 3-Wire harness
3. Hardware Pack contains: diode, resistor, MOV,
2-slotted screws, 2-security screws
4. Gasket
5.
731
i
Installation and Operation Manual
Specifications
Faceplate-Stainless steel single gang plate.
Circuit board dimensions: 1.7"W x 2.6"H x 1.675"0
Voltage: 12 or 24 volts DC (field selected)
Current: @12VDC 150 milliamperes
@24VDC 150 milliamperes
Outputs: Lock Relay SPOT 2 ampere @24VDC
(can operate one EL device)
Temperature Range:
-
20F (
-
28C) to 130F(54C)
Terminology
Keys
-
There are 12 keys: 0-9, # and
*·The
#
isusedtosignifytheseparationofcommands,
times, or userswhenprogramming. The
*
isused
to signify the endof acode entry.
Codes
-
Codes are user numbersthat are
programmedtounlockthedoororperformother
functions. Codes may consist of2to6digits,with
any combination or repetition allowed. This
providesforoveronemillionpossiblecodes.
Latch/Toggle
-
Anycodeprogrammedforlatch/
toggle changes the state of arelay ina
maintained
fashion until another code programmed for latch/toggle
is entered.

Default
-
Defaultisthe initial power upvalue
assignedtoaspecificfunction.Forexample,
the
unlockrelaydefaulttimeis5seconds.
Userpositions
-
Thereare100user
positions
available:
Mastercode
-
Alwaysuserposition1:
Enteringcodeunlocksdoor,Enteringcode
after
99#accessesprogrammingmode.
Supervisors
-Always user positions 2
and3:
Entering code unlocks door, Cannot
access
programming mode, Clears 30
second lockout
alarm(wrongentries)
beforeittimesout.
The remaining ninety-seven user positions 4
through 100 are non-programming and may
contain one of three types of user codes. They
include:
User
-
Enteringcodeunlocksdoor,andif
equipped with optional 7308 board actuates
relay 2.
Duress
-
Enteringcodeunlocksdoor,andif
equipped with optional 7308 board actuates
relay2andrelay 4.
Lockout
-
Enteringcodetoggles useofcodes
inhigheruserpositionsON/OFF.
2

Features
1.
Yellow program LED: Flashes when any key is
pressed,andindicatesvariousprogrammingmodes.
2.
Red/green LED: Shows status of the relay. Red
indicateslocked,greenindicatesunlocked.
3. Plastic protector: Wraps over circuit board to
prevent wiresfrom shorting against electrical box.
4. J1 jumper: Removing and replacing this jumper
when power is applied to the keypad will force
keypadintoprogrammingmode.
5.
4-Pin LED terminal:For 4-pin connector for red
andgreen LEDs.
6.
PA1 terminal pins: For 2-pin LED connector.
7.
J2jumper: 12VDC or 24VDC voltage selector.
8.
+,
-
Input voltage terminals: 12VDC or
24VDC, as selected byJ2jumper.
9. Unlock relay: (NO, C, NC) 2 ampere SPDT
contact controls door strikeorother equipment. This
relay contact switches when a correct code or a
request-to-exit inputisentered. Actuation time is
programmable.
10.
Door position switch input: (White wire)
Connecting anormally closed switch betweenthe
white/orange wire andthe white wire allows the
keypad to monitor the door position. The door will
Electrical
Box-
/
NotFurnished
LED
Connector
10
pin
connector
Wires out
bottom
..._Orange/White
White
/
Brown
@!
@
automatically relock as soon as it closes, preventing
another personfrom following through an unlocked
door. This automatic relock feature requires the use
of a door position switch. An additional output relay
may be triggered on alarm when used with the 7308
relayboard.
11.
Request-To-Exit input: (Brown wire) A
momentaryclosurebetweenthewhite/orange wire
and the brown wire will activate the unlock relay for
the same time period as programmed for the master
code. NOTE: This will only work if the door position
switch is closed.
1. Locate keypad at height to suit user.Check
handicap requirements inyour jurisdiction.
2.
Install keypad in a single-gang electrical box (not
furnished}.
Pull wires to junction box:
3.
Pull power supply wires
4.
Pull door lock wires
5.
Pulldoor position switchwires, if equipped
6.
Pullrequest-to-exit switch wires, if equipped
Install7311 keypad:
7.
Install gasket between keypad and wall (sticky
side toward keypad).
8.
Attach keypad to single-gang electrical box (not
furnished) with supplied screws.

3

SECTION3
-
-
-
Wire LED's:
1.
Plug the 4-wire connector onto the 4 pins
(not labelled) at the top of the circuit board.
Make sure the red dots are
in
alignment!
2.
Wire the two loose red wires to the "+"
terminal as shown.
Select proper voltage for operation:
3.
The control board is shipped with the voltage
selector jumper (J2) installed on one pin for 24
volt operation. Confirm this position.
4.
For 12 volt operation, install the jumper (J2)
on both pins.
Connect power:
5. The power supply, 12 or 24 volts as set by
jumper J2, is connected to
"+"
and "
-
"
terminals on terminal strip at bottom of circuit
board.
6.
TURN ON THE POWER
The red LED will come on solid indicating the
relay is in the locked position.
Test keypad:
7.
Enter the factory default code:
1-2 3·4-*
The relay will "click" and the red LED will turn
green for 5 seconds (factory default time).
NOTE: If you do not get this response, refer to
"troubleshooting" section.
Connect door position switch to the 3-wire harness
on the 7311 keypad:
9.
If a door position switch is not used, tie the
white and white/orange wires together and
insulate the connection.
10.
The door position switch input requires a
closed-when-secure contact between the white/
orange wire and the white wire in order to
monitor the door position and control the unlock
relay. If the door is equipped with such, connect
it to the white and white/orange wires.
Connect the request-to-exit switch to the 3-wire
harness on the 7311 keypad:
11.
If the request-to-exit switch is not used,
insulate the brown wire.
12.
A momentary closure between the brown
and white/orange wires will activate the unlock
relay for the same time period as programmed
for the master code. If a request-to-exit switch is
used, connect the normally open contacts to the
brown and white/orange wires. NOTE: This will
only work if the door position monitor loop is
closed.
13.
TURN ON THE POWER
14.
Test the switch by closing the request-to-exit
switch. The unlock relay will click and remain
energized as though a valid code had been
entered.
15.
TURN OFF THE POWER
Tie the orange/white and
7311Circuit Board white wires together
when a door position
/
switchisnotbeingused.
Normally closed
8. TURN OFF THE POWER Brown
-
White
ondetector
door position
switch
Moti
or other Request
to Exit Switch
Normally Open
Red
10 pin connector
Wires out
bottom
t --orange/White
White
/
Brown
Note: If optional relay board is used, see
installation
sheet included with 7308 board to
attach inputs.
INITIAL CONFIGURATION
AND TEST

Connect lock:
16. The unlock relay has SPOT contacts to
control a fail-safe or fail-secure operation.
17. If the lock uses the same power supply as
the keypad, use one of the following wiring
diagrams.
18. To use the keypad power supply, install a
jumper from the " + " terminal to the common
"C" terminal of the unlock relay.
19. Connect one wire of the load to the "
-"
side of the supply and the second wire to a
contact on the unlock relay. Use the NC for fail-
safe and the NO for fail-secure.
4

Test lock:
20.
Apply power to lock power supply and, if
separate, to keypad supply.
21.
Verify that the lock is locked before entering
a code.
22.
Enter the factory default code [1-2-3-4-*] or
another programmed valid code.
23.
Lock should release.
Example Application 1 7311 Circuit Board
'
og
.:G
MPB-840
Remove
:
J
o
.;o
Jumper
11 2
3
120 VAC
Fall Secure
6000 Series
Electric Strike
diode 120VAC
1Amp.
7311
0
Electric
Strike
Example Application 2 7311 Circuit Board
MPB-840
Remove
Jumper
11
2 3
4 s6
1s
9J
120 VAC
4000 Series IlTlt.:: -
[-
:J· Circuit Board
Magnetic Lock
(Fail-Safe) 120 VAC
1Amp.
DS4000
7311
0

Example Application 3
4 x 18
7311
7311Circuit Board
Remove
Jumper
12 Gauge Wires
120VAC
1 Amp.
Example Application 4
7311 Circuit Board
·
.:O
D
Remove
l;oE _.
::;,o
Jumper
11
2 3 4 5 6 7 8
9J
120VAC
";
16Gauge Wires
1.>=-t=-
12GaugeWires
120 VAC
1Amp.
Junction
3x 16
2x 12
EPT-218
7311
5

The keypad can be programmed prior to installation.
Programmed information is stored in nonvolatile
memory so it will not be lost when power is removed.
ToEnterProgrammingMode:Press9-9-#and
themastercodeFactory setat1-2-3-4,followed
by the
*·
Note: You must press
*
after entering any code
number.Many commands dealing with user codes
require the code to be entered twice during the
programmingsequence for verification purposes. The
keypad will automatically log out of programming
mode after 30 seconds without a key entry.
The keypad is now inprogramming mode, and
the yellow light will flash slowly. The unit is
preprogrammed with a factory code of 1234. This
code is removed when you program a master code
(See command 50). If the master code is forgotten,
remove and replace jumper J1when power is
applied to force the keypad into programming mode.
ToExit ProgrammingMode:Press
*·
Theyellow
LEDwillstopflashing.
Note: If a programming error occurs, indicated by a
solid yellow LED, simply press
*·
The yellow LED
should start flashing again. Re-enter command.
Command
46
50
50
50
52
70
99
Function
Erase complete memory.
Erases the master code. After executing this
command, go to command 50 and define a new
master code. If keypad logs out of programming
mode before you define a master code, briefly
removejumper J1 to access programming.
Change master code.
The code in user position 1 actuates the unlock relay
and also accesses programming mode. See
command 99. Default: factory code=1234.
Adduser.
These codes will unlock door. In addition, the codes
in user positions 2 and 3 will clear the keypad
lockout prior to its timeout.
Delete user, duress user, lockout user.
Erases code in user positions 2 to 100.
Add user lockout location.
These codes disable users in higher numbered user
positions until the user lockout code is entered again
(toggle ON/OFF). User lockout codes will not unlock
door.
Set keypad lockout count.
Multiple incorrect code entries will not allow a user to
unlock the door for 30 seconds. Indicated by a solid
yellow LED. The master and supervisor codes (users
1, 2, and 3) clear the keypad for use. Default=3
wrongentries.
Enterprogrammingmode.
Default=master code is 1234.
Code Entry
46#00000#00000#**
50#T#1#Code*Code*
T=O to 90 seconds (O=toggle)
Code=2 to 6 digit number
SO#T#U#Code*Code*
T=O for toggle or 3 for master time
U=user position 2 to 100
Code=2 to 6 digit number
SO#O#U#**
U=user position 2 to 100
52#0#U#Code*Code*
U=user position 2to 100
Code=2 to 6 digit number
70#0#N#**
N=3 to 25 wrong entries
99#Master*
Master=master code
(seecommand#SO)

6

Additional Commands for 7308 Board:
Command
44
45
51
Function
Setdoor-held-opentime.
Default:After 10seconds, actuates relay3. Resets
when door is closed or a valid code is entered.
Setdoorforced-open time.
Default: Actuates relay 3for 10seconds, Resets
automaticallyaftertimeexpires.
Addduress user.
This code activates the main relayfor the master
code time to unlock the door and also activates the
duress alarm output relay 4 for 10seconds.
Code Entry
44#T#O#**
T=10 to 900 seconds
45#T#O#**
T=10 to 900 seconds
51#O#U#Code*Code*
U=user position 2 to 100
Code=
2
to
6
digit number
EXAMPLE: Adding User Codes
Code Sequence:
COMMAND #
CC#
TIME#
T#
USER POSITION #
U#
CODE*
CODE
*
CODE
*
CODE
*
STEP 1: Enter program mode: 99# [master code]*
Response: yellow LEDslow flash
STEP 2: Enter command: CC# (Program Command
function)
Add user CC =50
Add duress user CC =51
Add lockout user CC=52
Response: yellow LEDslow flash
STEP 3: Enter time: T# (0 to 90 seconds)
If T=0, code will toggle the lock (locked to
unlocked or vice versa). If set to 3, time
equals the master time set in position
number 1. Any other number will set a
unique time for this user.
Response: yellow LEDslow flash
STEP 4: Enter the USER position: U# (1 to 100)
Response: yellow LED slow flash
STEP 5: Enter the user code: [_ _ _ _ _
-l*
(2to 6
digits)
Response: yellow LED fast flash
STEP 6: Verify user code was entered correctly:
[_ _ _ _ _
-l*
(same 2 to 6 digit number)
Response: yellow LED slow flash
STEP 7: To program another command begin at
step 2, or
STEP 8:Toend program mode PRESS the
*
key
again.
Response: yellow LED stops flashing

7

Symptom
Cause
Solution
Procedure
No red LED on
power up
No voltage at circuit board
input terminals.
Verify a minimum of 10.5VDC
(12VDC) across
"+"
and"
-
"
voltageinputterminals.
•
If the minimum voltage is not
present, checkthe output atthe power
supply for voltage.
•
Ifcorrect voltage is present at power
supply, check wiring between power
supply and keypad for anopen circuit.
•
Ifvoltage is not present at power
supply output, check the fuses.
•
Iffuses are blown, look for a short
between the power supply and 7311
keypad.
•
If
fuses are not blown, measure
120VAC inputto the power supply.
•
If no120VAC, check circuit breaker.
•
If 120VAC ispresent, return power
supply to supplier for repair.
Input voltage polarity is reversed
at input terminals.
Verify positive lead from DCpower
supply goesto
"+"
input andground
to
"-"
input.
•
If reversed, then correct. This should
notcause damage tothecircuit board.
Voltage jumper (J2) not set
properly.
Verify jumper is on both pins to
operate on 12VDCvoltage.
•
Ifnotproperlyset,correct.
Red LED does not
change to green
when a valid code
is entered.
Code was not entered correctly.
Re-enter proper code correctly.
•
Enter the 2 to 6 digit number (look
foryellowflashwitheachkeypressed).
•
Follownumberenteredimmediately
by
.
Code is notvalid.
Use master code to enter
programming mode and add user
code (command 50).
Master code was erased when
erasingprogram memory.
Briefly removejumper J1to enter
programming mode, enter command
50to redefinemastercode.
Red LED turns to
green, but lock
does not release.
Voltage jumper (J2) not set
properly.
Verify jumper ison both pinsto
operate on 12VDC voltage.
•
If not properly set, correct.
Incorrect wiring between keypad
and lock.
Iflock isfail-secure, remove thewires
tied to the "C" and "NO" terminals
andtietogether. Lock should release.
Ifnot,check wiringbetween keypad
and lockfor opens. Ifthe lock isfail-
safe, removewirefrom "NC"output
terminal. Lockshould release.If lock
releases as itshould, and keypad is
getting correct inputvoltage, return
keypadforrepair.
Master code does
not access pro-
gramming mode.
Did not use current master code.
Press 99#, and enter current code.
Master code was reset by erasing
memory (command 46).
Remove and replacejumper "J1,"use
command 50to redefine master code.
Request-to-exit
switch does not ac-
tivateunlockrelay.
Door position switch is not closed.
Tie the white and orange/white wires
securely together.
Green LED on
solid.
Toggle code has been entered.
Enter toggle code again to
de-energize relay.
Yellow LED on
solid.
Madeaprogrammingerrorwhen
inprogramming mode.
Press •to get back to a slow yellow
flashing LED.

Keypad is ina 30 second entry-
error alarm mode. This occurs
when a number of wrong user
codes are entered.
Enter in a master or supervisory
code (user codes 1,2, or 3).
8

7311Keypad Update
0
The pushbutton replaces Jumper J1 inthe instructions.
@ LED wires no longer connect to the "+" terminal. All four wires are plugged in, as shown, from the factory.
0
D
Programming
Pushbutton

INGERSOLL-RAN D
VON DUPRIN
ARCHITECTURAL HARDWARE
6175010 1.01
Table of contents
Popular Keypad manuals by other brands

Chamberlain
Chamberlain 747EML Series quick start guide

Rose electronics
Rose electronics RCK-KP4x5-P Installation and operation manual

olympia electronics
olympia electronics JA-81F manual

Burg Wächter
Burg Wächter TSE 5111 operating instructions

GE
GE NetworX NX-1192E user manual

Elko
Elko iNels RF KEY - 40 quick start guide