Ingeteam INGECON SUN STORAGE 1Play User manual

Ingeteam Power Technology S. A.
Technical Guide
INGECON SUN STORAGE 1PLAY
Use and Settings of the ISS 1Play working with PYLONTECH
FORCE H1/H2 and POWERCUBE X1/X2
ABH2010IMC13_B
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
2/11
Table of contents
1Introduction................................................................................................................................................... 3
2Connecting the battery pack to the inverter ................................................................................................. 4
2.1 Wiring of CAN communication wire..................................................................................................... 4
3Black start function....................................................................................................................................... 5
4Battery´s firmware update ............................................................................................................................ 6
5Setting the inverter ....................................................................................................................................... 7
5.1 DC Battery type ................................................................................................................................... 7
5.1.1 For ISS 1Play TL M ......................................................................................................................... 7
5.1.2 For ISS 1Play TL ............................................................................................................................. 7
6Final check ................................................................................................................................................... 9
7Trouble shooting......................................................................................................................................... 10
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
3/11
1 Introduction
This document describes the process to configure the INGECON SUN STORAGE 1Play (TL and TL M
version) to work with PYLONTECH FORCE H1/H2 and POWERCUBE X1/X2 batteries.
The PYLONTECH HV and ISS 1Play equipment can be used in the following type of single-phase
installations:
•Stand-alone installations
•UPS installations
•Self-consumption installations
The minimum FW versions to work with the ISS 1Play and PYLONTECH HV are the following:
Minimum Firmware Version used in the PYLONTEHC HV:
•Force H1/H2 →V1.3 or higher
•Powercube X1/X2 →V4.6 or higher
The battery´s firmware is supplied by the qualified distributor of Pylontech. For further details, check the
“Installation Manual of Pylontech”.
Minimum Firmware Version used in the ISS 1Play TL:
•Inverter: ABH1002AA or higher
•Display: ABH1003_Q or higher
Minimum Firmware Version used in the ISS 1Play TL M:
•Inverter: ABH1007_ or higher
For further details, check the “List of approved lithium batteries” available on Ingeteam website.
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
4/11
2 Connecting the battery pack to the inverter
The instructions to connect the battery pack to the inverter are described in the “Installation Manual of
Pylontech”
Please, take into account the following technical notes:
1) The inverter is turned OFF before connecting the battery pack to the inverter.
2) The battery circuit breaker is on the OFF position.
3) Connect the DC power wires with 6-10mm2.
4) Connect the CAN Communication wire.
2.1 Wiring of CAN communication wire
Pylontech batteries require a CAN communication wire to the ISS 1Play.
The ISS 1Play will send the necessary keep-a-live command to the Pylontech battery, which is needed to
keep its internal circuit breaker close. When the battery does not receive for 15 seconds such a command, its
internal circuit breaker opens.
The ISS 1Play uses a two-pin CAN terminal and the Pylontech uses a RJ45 connector. For further details,
check the “Installation and Operation Manual” of ISS 1Play. The pin-out is the following:
Only for ISS 1Play TL, it is mandatory that its display is correctly connected. Otherwise, the Pylontech will
open its internal circuit breaker after 15 seconds.
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
5/11
3 Black start function
This chapter describes how to turn on the system when the PV energy is not available, and the battery is the
only source to turn on the inverter.
To do so, once all the previous steps have been completed, the following steps must be followed:
1) Make sure that the battery circuit breaker is in OFF position.
2) Move the circuit breaker to ON position, press and hold the red start button for 5 seconds to turn the
battery pack on.
3) After 30 seconds press and hold the red start button again for another 5 seconds.
4) Then the inverter and battery should get powered. Make sure that the display´s screen is ON.
In this situation, if the battery does not receive communication from the inverter for 10 minutes, its internal
circuit breaker will be opened.
This period time is enough to do the first commissioning of the system as update the correct inverter´s
firmware and select the correct battery type.
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
6/11
4 Battery´s firmware update
The battery´s firmware is supplied by the qualified distributor of Pylontech. To update the firmware is
necessary a monitoring cable RS-232 supplied by the distributor.
For further details, check the “Pylontech guideline” supplied by the distributor.
A minimum firmware version is necessary to work with the Ingecon Sun Storage 1Play:
•Force H1/H2 →V1.3 or higher
•Powercube X1/X2 →V4.6 or higher
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
7/11
5 Setting the inverter
This chapter describes how to configure the inverter settings when the ISS 1Play has been wired to the
Pylontech battery.
To do so, once all the previous steps have been completed, the following steps must be followed:
5.1 DC Battery type
Please be careful to choose the right battery type when you set up the configuration in
your inverter. The battery or inverter manufacturers have no responsibility on the
damages caused due to incorrect configurations. For instance, if you select “Lead-acid”
as a battery type in the inverter configuration and the battery being used is “Lithium-ion”,
the battery might get damaged or experience performance degradation.
It is required to set the DC Battery type: Pylontech Force H1/H2 or Powercube X1/X2
5.1.1 For ISS 1Play TL M
This must be done using the web interface of the inverter. To perform any configuration change, the required
installer access must be entered on the web. When the permission is given, go to:
CONFIGURATION > ADVANCED SETTIGNS > TYPE OF BATTERY > PYLONTECH FORCE H1/H2
or
CONFIGURATION > ADVANCED SETTIGNS > TYPE OF BATTERY > PYLONTECH POWERCUBE X1/X2
Confirm the desired selection by pressing the “Write” button. A message to confirm the modification will pop
up.
5.1.2 For ISS 1Play TL
This can be done using the “Ingecon Sun Manager” software package (downloadable on www.ingeteam.com)
or through the display:
Using Ingecon Sun Manager:
Settings →1-.DC BATTERY TYPE: Type of Battery > Lithium: Pylontech Force H1/H2
or
Settings →1-.DC BATTERY TYPE: Type of Battery > Lithium: Pylontech Powercube X1/X2
Figure 1: DC Battery selection on Ingecon Sun Manager.
Click on the “Send” button. A screen informing that the configuration was successfully saved must appear
when the settings are correctly applied to the inverter.
Using the Display:
To perform any configuration change through the display, the required installer password must be entered on:
MAIN MENU > CONFIGURATION > ENTER PASSWORD
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
8/11
The password is indicated on the “Installation and Operation Manual”, on the chapter dedicated to
configuration.
When the permission is given, go to:
MAIN MENU > CONFIGURATION > BATTERY > LITHIUM > PYLONTECH HV > FORCE H1/H2
or
MAIN MENU > CONFIGURATION > BATTERY > LITHIUM > PYLONTECH HV > POWERCUBE X1/X2
Confirm the desired selection by pressing the “OK” button. A message to confirm the modification will pop up.
A final screen that shows that the process has been completed will be shown on the display.
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
9/11
6 Final check
This chapter describes the instructions to check that all the connections and settings have been successfully
done.
1) Make sure that the CAN communication wire from the PYLONTECH battery to the inverter is
connected.
2) Make sure that the battery circuit breaker is in ON position.
3) Make sure that the inverter is turn-on from the battery and doesn’t show communication Error with
BMS.
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
10/11
7 Trouble shooting
The inverter receives battery´s alarms from BMS and reacts different for each alarm.
Inverter notifies via Interface Web when battery is in alarm status:
Also, the inverter shows the alarm:
The reaction of the inverter for each alarm is:
Inverter Alarm Name
Battery Protection Name
Inverter Reaction
0x0001
High Current Charge
COC: Charge Over Current Protect
Stop battery charge
0x0080
High Current Discharge
DOC: Discharge Over Current Protect
Stop battery discharge
0x0002
High Voltage
BOV: Single Cell Over Voltage Protect
Stop battery charge
POV: Charge system Over Voltage
Protect
MOV: Module Over Voltage Protect
0x0004
Low Voltage
BUV: Single Cell Under Voltage Protect
Stop battery discharge
PUV: Discharge system Under Voltage
Protect
MUV: Module Under Voltage Protect
0x0008
High Temperature
COT: Charge Cell Over Temperature
Protect
In on-grid, stop battery
charge & discharge.
In off-grid, stop inverter.
DOT: Discharge Cell Over Temperature
Protect
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits

INGECON SUN STORAGE 1Play
Technical Guide
19/11/2020
11/11
0x0010
Low Temperature
CUT: Charge Cell Under Temperature
Protect
In on-grid, stop battery
charge & discharge.
In off-grid, stop inverter
DUT: Discharge Cell Under Temperature
Protect
0x0020
BMS Internal
Bit 7: Other Error
In on-grid, stop battery
charge & discharge.
In off-grid, stop inverter.
Bit 6: Other Error
Bit 5: Relay Check Error
Bit 4: Input transposition Error
Bit 3: Input Over Voltage Error
Bit 2: Internal Communication Error
Bit 1: Temperature Sensor Error
Bit 0: Voltage Sensor Error
To read more information about the Battery´s alarms, please contact with Pylontech distributor to get the
communication cable and software.
FranciscoAncín
2021.01.2017:10:06
Firmante:
CN=FranciscoAncín
C=ES
O=IngeteamPowerTechnology- Energy
Llavepublica:
RSA/1024bits
Other manuals for INGECON SUN STORAGE 1Play
7
Table of contents
Other Ingeteam Storage manuals