Flex5/DAC
Alternating current output expansion
The Flex5/DAC provides 5 terminals for controlling both AC and DC loads.
Each terminal can be configured as an output with the following attribute type:
• Relay, dry contact for AC or DC devices of up to 10A
• TRIAC ON/OFF, electronic contact that functions as a relay for AC devices up to 3.5A
maximum
• TRIAC dimmer, dimmer contact for power-choke type AC devices of up to 3.5A
Each terminal has a sensor that measures the current (both AC and DC) absorbed by
the load and ensures that the terminal is galvanically isolated from the rest of the
board.
From the measurements performed on the board and for each of the terminals, the usable
electrical parameters are provided both on the Flex5/DAC display (by navigating with the
right/left keys) and on the Alien user interface (through the “Commands” section) and via
management software for INIM systems:
• Supplied voltage to external load
• Power absorption from external load
The electrical power value is calculated using the measure of the current drawn and
the values of the set or effective voltage, as in the case of the connection with the
primary power-supply network.
• Phase displacement or power factor (PF), measured exclusively for AC loads with
non-dimmable mains voltage and only when phase and neutral are connected to
expansion through terminals 15 and 16
• Percentage of the supplied power with respect to the maximum possible, measured
exclusively for dimmable loads.
• Consumption, in KWh
The consumption can be viewed only on the FLEX5/DAC display and is supplied as a
total (“KWh TOT”), as partial (“KWh Pr1” and “KWh Pr2”, two partials resettable from
the menu) for each terminal and for all devices (“BOARD TOT”).
For a detailed description of the functionality and configuration of a FLEX5/DAC in a
INIM intrusion control system please refer to the installation manual of the control
panel.
1Technical description
FLEX5/DAC
TERMINAL 01
VOLTAGE [V] 218
POWER [W] 0050
POWER FACTOR 1.0
TERMINAL 01
KWh Pr1 00000012
KWh Pr2 00000344
KWh TOT 00003814
Table 1: Flex5/DAC - electrical and mechanical features
Power supply voltage nominal
13.8V
range
from 9 to 16V
Voltage connectible to the AC~ input
115/230V~ -15% +10%
50/60Hz
Range of the voltage
connectible to the OUTx
output
Alternating Current
from 0 to 253V~, 50/60Hz
Continuous Current (relay
use)
from 0 to 253V @0.35A
from 0 to 28V @10A
Maximum sustainable load
from each output
relay output
10A, PF=1
triac ON/OFF output
3.5A, PF=1
triac dimmer output
3.5A, PF=1
Operating environmental
conditions temperature
from -10 to +40°C
relative humidity
75% without condensation
Pollution Degree
2
Maximum current draw
200mA
Isolation class
II
DIN-rail mount
9 module enclosure
Dimensions including enclosure (W x H x D)
158 x 88 x 58.5 mm
Weight including enclosure
300g
DCMIINIEFLEX5DAC-R110-20160912