
2.23.15 06369F © Inovonics, 2015 - www.inovonics.com 2
1.5 EN6080 Area Control Gateway Internal Components
Figure 3 EN6080 area control gateway internal components
Diagnostic LEDs
Static LED: Yellow indicates the EN6080 is using a static IP address; green
indicates the EN6080 is using a dynamic IP address obtained from the
network; no illumination indicates the EN6080 has been configured to use
a dynamic IP address but has not obtained one from the network, or there
is no Ethernet connection.
Alarm LED: Red indicates an alarm in the EchoStream wireless network.
Fault LED: Yellow indicates a tamper, low battery or repeater line power
loss fault in the EchoStream wireless network.
1.6 What’s in the Carton
• One CR1220 memory backup battery.
• Five drywall anchors.
• Five mounting screws.
2 Installation and Startup
2.1 Installation Notes
• These products are designed to be maintained by professional
security technicians.
• Products are tested for indoor use.
• All products should be manually tested weekly.
2.2 Connect Power Cabling and Install Memory Backup
Battery
Note: The EN6080 area control gateway is Power over Ethernet (PoE)
capable on any network supporting the IEEE 802.3at-2009 PoE+ standard,
and using a PoE switch. Power over Ethernet will only function when line
power is not present.
To use line power, you will need to connect a power source to the EN6080
area control gateway. To do so:
1. Use a Phillips screwdriver to loosen the housing cover release screw
(Figure 3).
2. Lift the cover off the hinges on the top of the housing.
3. Route the power cabling through the cabling ports on the bottom of the
housing (Figure 3).
• If not using the ACC610 14 VAC/20VA transformer, use 14-22 gauge
wire for all cabling.
Note: For UL 2560 installations, all cabling must be UL Listed or
Recognized, Class 2 wire suitable for the application. If connecting cabling
to a DC power source, such as the ACC610 transformer, use two-
conductor 14-22 AWG stranded-tinned copper, rated 300 volts, 60°C
minimum.
4. Connect to the power connection terminal block.
• If connecting cabling to a DC power source, ensure polarity
corresponds to the + and - connections; an AC power source does not
require specific polarity and can use either connection.
• Ensure torque on the screw terminals does not exceed 0.35 - 0.4 Nm
(3.1 - 3.5 inch-pounds).
5. Insert the memory backup battery in the battery holder (Figure 3).
Note: It is a best practice to install the backup battery just prior to powering
on the EN6080 area control gateway.
6. Connect the power cabling to your power source.
• The power source must be 12-24 VAC or VDC. The power supply
must be unswitched, uninterrupted and regulated.
Note: For UL 2560 installations, a Class 2 plug-in transformer, rated
14VAC/120VAC-20VA, must be used with the EN6080 area control
gateway if Power over Ethernet is not provided. Approved Class 2
transformers include the MPI-NEO Co., Ltd., Model W48A-K1429-2T
transformer available from Inovonics as part number ACC610, as well as
the Good Power Electronics, Ltd., Model T48141428V010G or
T48141428V020G transformers.
2.3 Connect Ethernet Cabling
Note: For UL 2560 installations, a UL Certified PoE switch or injector must
be used if the EN6080 area control gateway is to be powered with PoE.
The EN6080 area control gateway connects to network components in a
wired local area network (LAN) using the RJ45 Ethernet jack. To connect to
a LAN:
7. Connect one end of a RJ45 Ethernet cable to the RJ45 Ethernet jack on
the EN6080 area control gateway (Figure 3).
8. Route the Ethernet cable through the cabling ports on the bottom of the
housing (Figure 3).
9. Connect the other end of the RJ45 Ethernet cable to an RJ45 Ethernet
jack connected to your LAN.
10. To relieve stress on the Ethernet and power cabling, secure it to the
cabling tie loop with a tie (Figure 3).
2.4 Mount the EN6080 Area Control Gateway
Caution: Mount the EN6080 area control gateway in a location removed
from metal. Metal objects (duct work, wire mesh screens, boxes) will
reduce RF range.
Caution: Per FCC RF exposure requirements, the EN6080 should be
mounted in a location where it will be no closer than 100cm from nearby
persons.
Note: To meet UL 2560 requirements, the EN6080 area control gateway
must be mounted in a manner that allows the cable openings to face
downward.
The EN6080 area control gateway includes a wall tamper. If the EN6080
area control gateway is removed from the wall, the cutout on the back of
the housing will detach, activating a tamper alarm. The wall tamper will only
work if the EN6080 area control gateway is properly installed. To ensure
the EN6080 is properly installed, carefully follow the mounting instructions:
11. If mounting the EN6080 area control gateway to drywall, install the
drywall anchors included in the installation packet.
Caution: If the EN6080 area control gateway is mounted to drywall, the
drywall anchors must be used. Without the drywall anchors, the back
tamper will not activate if the device is removed from the wall.
12. Use four of the provided screws to mount the EN6080 area control
gateway, making sure the EN6080 area control gateway is flush with
the wall (Figure 3).
13. Attach one of the provided screws to the wall through the wall tamper
mounting hole (Figure 3).
AWall mount holes BHousing cover release
screw CPower connection
terminal block
DRJ45 Ethernet jack EOperation LEDs FDiagnostic LEDs
GReset button HCabling port IWall tamper
mounting hole
JHousing tamper switch KCabling tie loop LBattery holder