Intelligent Charging LSU80A User manual

LSU80A : Load Support Unit
Operators Manual
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 1 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19
LSU80A
LOAD SUPPORT UNIT
OPERATORS MANUAL

LSU80A : Load Support Unit
Operators Manual
Table of Contents
1 MANUAL REVISION HISTORY....................................................................................................3
2 DESCRIPTION..........................................................................................................................4
3 INSTALLATION.........................................................................................................................5
3.1 POSITIONING THE EQUIPMENT..........................................................................................5
3.2 CONTROLS AND INDICATORS............................................................................................6
3.2.1 Fron panel.................................................................................................................6
3.2.2 Rear panel..................................................................................................................7
4 OPERATION.............................................................................................................................8
5 CALIBRATION.........................................................................................................................10
5.1 CHECKING PROCEDURE...................................................................................................12
5.1.1 Vol age valida ion......................................................................................................12
5.1.2 Curren valida ion......................................................................................................12
5.2 ADJUSTMENT PROCEDURE...............................................................................................13
5.2.1 Vol age adjus men ...................................................................................................13
5.2.2 Curren adjus men ...................................................................................................13
6 SPECIFICATIONS....................................................................................................................15
7 PRODUCT DISPOSAL INSTRUCTIONS.......................................................................................16
8 PRODUCT WARRANTY.............................................................................................................17
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 2 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
1 MANUAL REVISION HISTORY
Rev Date Description
1 14-07-2014 First write.
2 21-07-2015 Rewritten with correct drawings and formatting changes
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 3 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
2 DESCRIPTION
The LSU80A is a general purpose load suppor uni designed o ac as a permanen power
supply o main ain backup ba ery sys ems whils al erna ive sources of power are ei her
imprac ical or unavailable, such as running diesel engines during main enance programs or
removal of main power sys ems during main enance.
The LSU80A can suppor bo h 12V and 24V sys ems by simple manual vol age adjus men ,
wi h a curren capaci y of up o 80 amperes.
7 segmen displays con inuously shows bo h se vol age and curren draw.
Vol age ou pu can be rimmed in approxima ely 0.1V s eps during opera ion o offse cable
drops and/or varia ions in demand which crea e excessive demand on he backup ba eries.
Ou pu is enabled or disabled by run and s op bu ons.
In ernal variable speed fans are employed o ensure he LSU80A opera es a a reasonable
empera ure.
The LSU80A is designed o opera e from a s andard domes ic 13A ou le .
The LSU80A has a simple user calibra ion procedure o ensure he displays show accura e
readings.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 4 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
INSTALLATION
.1 POSITIONING THE EQUIPMENT
The LSU80A should be moun ed on a level surface such as a workbench, s urdy shelf or a
rolley. The uni should be si ed so ha a leas 10cm of airspace is available all round he lef
and op of he uni and a leas 20cm on he righ hand side o allow free movemen of air
required for cooling.
The LSU80A is supplied fi ed wi h a s andard UK hree pin plug on 3m of lead.
The load is connec ed via wo rubber insula ed cables 3m in leng h. The cables are supplied
fi ed wi h 8mm ring crimps and keyed ma ing connec ors for connec ion o he LSU80A. The
cable has a cross sec ion of 25mm2 per conduc or. While opera ing he uni a very high
curren s he leads should be laid ou in such a manner as o aid cooling.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 5 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19
10 cm 10 cm
10 cm
Direction of Airflow
B40
MEM
B40
ON
OFF
I
O
MEM
ON
OFF
I
O
VOLTAGE CURRENT
OUT UT STATE
OFF
OUT UT TRIM
OWER
LSU80A
LOAD SUPPORT UNIT
ON
LOAD
SU #2
TRI
SU #1
TRI RUNNING STO ED
OUT UT 27V 80A MAXIMUM
OUT UT ROTECTION

LSU80A : Load Support Unit
Operators Manual
.2 CONTROLS AND INDICATORS
.2.1 Front panel
A) Main inpu supply swi ch and circui breaker.
B) Off push bu on. Pressing his while he uni is running and providing ou pu power will
s op he ou pu power.
C) This indica or will be illumina ed when he uni is s opped and no ou pu ing power.
D) This indica or will be illumina ed when he uni is running and ou pu ing power.
E) ON push bu on. Pressing his when he uni is s opped will cause he uni o provide he
ou pu power.
F) Nega ive ou pu erminal.
G) Posi ive ou pu erminal.
H) Ou pu pro ec ion circui breakers.
I) Up/Down push bu on. Pressing while he uni is running and providing ou pu power
will cause he ou pu vol age o be increased. Pressing while he uni is s opped will
cause he display brigh ness o be increased. Pressing while he uni is running and
providing ou pu power will cause he ou pu vol age o be reduced. Pressing while
he uni is s opped will cause he display brigh ness o be increased.
J) Vol age indica ion. While he uni is swi ched on i will show he vol age presen a he
ou pu erminals in 0.1V s eps.
K) When he uni is running and providing ou pu power i will show he number of amps
being provided in 1A s eps.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 6 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19
A
B
CD
E
F
G
HIJK
B40
MEM
B40
ON
OFF
I
O
MEM
ON
OFF
I
O
VOLTAGE CURRENT
OUT UT STATE
OFF
OUT UT TRIM
OWER
LSU80A
LOAD SUPPORT UNIT
ON
LOAD
SU #2
TRI
SU #1
TRI RUNNING STO ED
OUT UT 27V 80A MAXIMUM
OUT UT ROTECTION

LSU80A : Load Support Unit
Operators Manual
.2.2 Rear panel
L) Power cord inle .
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 7 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19
SERIAL No:
INTELLIGENT CHARGING
CasC Systems Ltd
Ford House, Dewing Road,
Rackheath Ind. Est. Norwich,
Norfolk, NR13 6 S, ENGLAND.
TEL: +44-1603-722770
FAX: +44-1603-722771
MAIL: sales@intelligent-charging com
CHARGING
INTELLIGENT
FROM
MODEL :
/N :
MADE IN ENGLAND
C A S C S Y S T E M S L T D
MAINS 115V/240V 50Hz/60Hz
16A Maximum
L

LSU80A : Load Support Unit
Operators Manual
4 OPERATION
Before connec ing o he load for he firs ime he LSU80A has o be se o he nominal vol age of
he load sys em i is going o supply. The following s eps mus be followed prior o connec ing o
he load.
Apply power o he LSU80A wi h load unconnec ed. Power swi ch pressed o he down
posi ion.
Press he RUN bu on and check he ou pu s a e RUN LED is li GREEN and he STOPPED LED
is no li .
The VOLTAGE display will show he value of ou pu vol age ha is curren ly se .
Use he OUTPUT TRIM push bu ons o se he ou pu vol age display o he load
vol age required. This se ing will be remembered when power is removed. No e if you press
and hold ei her he push bu ons he adjus men will be con inuous.
Press he s op bu on and check he RUN LED is no li and he STOPPED LED is li .
The vol age display will slowly reduce o zero, or will fall o zero very rapidly if he load is
connec ed.
A his poin he load can be connec ed.
If any residual vol age is shown on he VOLTAGE display his will reduce very rapidly o zero.
If he load already has a vol age presen , such as a ba ery main ained sys em hen he
VOLTAGE display will show his value.
The following s eps are followed upon equipmen connec ion.
Press he START push bu on and verify he RUN LED is li and he STOPPED LED is no li .
The VOLTAGE display will show he ou pu vol age.
The CURRENT display will show he ou pu amps being drawn from he uni .
When he ou pu vol age is no longer required press he STOP push bu on.
A very high curren s he vol age drop in he leads may no provide enough vol age a he
equipmen .
To overcome his high vol age drop he ou pu vol age can be rimmed by pressing he
OUTPUT TRIM push bu ons o se he desired ou pu . This se ing will be remembered
when power is removed. No e if you press and hold ei her he push bu ons he
adjus men will be con inuous.
On ba ery main ained sys ems cau ion mus be observed when using he rim fea ure as no
o overcharge he ba ery as high vol ages will cause some of he curren o be passed o he
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 8 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
ba ery.
Af er long erm use a very high curren i is wise o follow his procedure o enable he uni o
safely cool down prior o moving.
Af er pressing STOP o remove he ou pu disconnec he load.
I will be no ed ha he fans will reduce o a low se ing and hen s op.
Press he START push bu on, he display will show he vol age ha was se .
I will be no ed ha he fans will hen s ar up again and run slowly while he PSU uni s are
cooled.
Once he fans have s opped i is safe o remove power from he uni by moving he swi ch o
he up off posi ion.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 9 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
5 CALIBRATION
The LSU80A has wo displays which show Vol age and Curren . These are elec ronic displays
which will require regular checking for heir accuracy. In elligen Charging recommends ha he
calibra ion check procedure is followed annually.
To calibra e he uni he following equipmen will be required.
1.Calibra ed vol me er capable of reading 24V o one decimal place.
2.Calibra ed amme er capable of reading up o 80A o one significan digi , or a calibra ed
amme er shun and millivol me er combina ion.
The equipmen will need o be connec ed as shown in he following figures.
VOLTAGE MEASUREMENT
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 10 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19
1705 TRUE RMS ROGRAMMBLE MULTIMETER
+VE
COMMON
2A
10A
0.00V
0.00V
B40
MEM
B40
ON
OFF
I
O
MEM
ON
OFF
I
O
VOLTAGE CURRENT
OUT UT STATE
OFF
OUT UT TRIM
OWER
LSU80A
LOAD SUPPORT UNIT
ON
LOAD
SU #2
TRI
SU #1
TRI RUNNING STO ED
OUT UT 27V 80A MAXIMUM
OUT UT ROTECTION

LSU80A : Load Support Unit
Operators Manual
CURRENT MEASUREMENT
5.1 CHECKING PROCEDURE
5.1.1 Voltage validation
Wi h no load connec ed o he LU80A swi ch on and press he START push bu on.
Using he OUTPUT TRIM push bu ons se he ou pu vol age o 24.0V. No e if
you press and hold ei her he push bu ons he adjus men will be con inuous.
Wi h he calibra ed vol me er connec ed o he ou pu erminals verify ha he vol age
reading is 24.0V +/- 0.2V
If he vol age is ou side of olerance follow he ADUSTMENT PROCEDURE for vol age.
5.1.2 Current validation
Wi h a load which will give a s eady 50A connec ed o he LU80A swi ch on and press
he START push bu on.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 11 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19
MADE IN ENGLAND
SERIAL No:
INTELLIGENT CHARGING
from
CasC Systems Ltd
Ford House, Dewing Road,
Rackheath Ind. Est. Norwich,
Norfolk, NR13 6 S, ENGLAND.
TEL: +44-1603-722770
FAX: +44-1603-722771
MAIL: chargi ng@casc-ltd com
CHARGING
INTELLIGENT
FROM
C A S C S Y S T E M S L T D
SHUNT60A
1705 TRUE RMS ROGRAMMBLE MULTIMETER
+VE
COMMON
2A
10A
0.00mV
0.00V
LOAD RESISTOR
B40
MEM
B40
ON
OFF
I
O
MEM
ON
OFF
I
O
VOLTAGE CURRENT
OUT UT STATE
OFF
OUT UT TRIM
OWER
LSU80A
LOAD SUPPORT UNIT
ON
LOAD
SU #2
TRI
SU #1
TRI RUNNING STO ED
OUT UT 27V 80A MAXIMUM
OUT UT ROTECTION

LSU80A : Load Support Unit
Operators Manual
Using he OUTPUT TRIM push bu ons se he ou pu vol age o 24.0V. No e if
you press and hold ei her he push bu ons he adjus men will be con inuous.
Wi h he calibra ed amme er or shun and millivol me er combina ion connec ed in-
line wi h he load curren reading is +/- 2.0A of he displayed value.
If he curren is ou side of olerance follow he ADUSTMENT PROCEDURE for curren ..
5.2 ADJUSTMENT PROCEDURE
5.2.1 Voltage adjustment
Wi h no load connec ed o he LSU80A swi ch on and press he START push bu on.
To ge he uni in o calibra ion adjus men mode press he START push bu on and
he OUTPUT TRIM push bu on bo h a he same ime.
Then release he push bu ons.
The GREEN RUN LED should hen flash a a s eady ra e.
By using he OUTPUT TRIM push bu ons adjus he displayed vol age so ha i
ma ches as near as possible he vol age measured on he calibra ed vol me er
connec ed o he ou pu erminals. No e if you press and hold ei her he push
bu ons he adjus men will be con inuous.
Once comple e press he START push bu on once and verify ha i s ops flashing and
remains s eady.
Press he STOP push bu on.
Calibra ion vol age adjus men is comple e.
5.2.2 Current adjustment
Wi h a load which will give a s eady 80A connec ed o he LU80A swi ch on and press
he START push bu on.
To ge he uni in o calibra ion adjus men mode press he START push bu on and
he OUTPUT TRIM push bu on bo h a he same ime.
Then release he push bu ons.
The GREEN RUN LED should hen flash a a s eady ra e.
By using he OUTPUT TRIM push bu ons adjus he displayed curren so ha i
ma ches as near as possible he curren measured on he calibra ed amme er
connec ed o he ou pu erminals. No e if you press and hold ei her he push
bu ons he adjus men will be con inuous.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 12 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
Once comple e press he START push bu on once and verify ha i s ops flashing and
remains s eady.
Press he STOP push bu on.
Calibra ion curren adjus men is comple e.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 13 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
6 SPECIFICATIONS
INPUTS:
Mains Supply 110-240VAC 50-60Hz 2.5KW Max.
OUTPUTS:
Vol age 10.0V Minimum
27.0V Maximum
Curren 80A Maximum
OVERLOAD PROTECTION:
105-125% of ou pu power.
Cons an power o 75% of se ou pu vol age
hen ou pu shu s down, recycle AC o rese
SHORT CIRCUIT PROTECTION:
Ou pu la ches off, recycle AC o rese .
METER ACCURACY:
Vol age accuracy ±0.2V
Curren Accuracy ±1.0A
ENVIRONMENTAL:
Temp Opera ing 0°C ~ 40°C
Temp S orage -10°C ~ 60°C
Humidi y 20% - 90% Non condensing
Al i ude 0 o 3000 Me res.
IP Ra ing:
Opera ing IP33
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 14 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
7 PRODUCT DISPOSAL INSTRUCTIONS
The symbol shown here and on he produc means ha he
produc is classed as Elec rical or Elec ronic Equipmen and should
no be disposed wi h o her household or commercial was e a he
end of i s working life.
The Was e of Elec rical and Elec ronic Equipmen (WEEE) Direc ive
(2002/96/EC) has been pu in place o recycle produc s using bes
available recovery and recycling echniques o minimise he impac
on he environmen , rea any hazardous subs ances and avoid he
increasing landfill.
Produc disposal ins ruc ions for residen ial users.
When you have no fur her use for i , please remove any ba eries and dispose of hem and he
produc as per your local au hori y’s recycling processes. For more informa ion con ac your
local au hori y or he re ailer where he produc was purchased.
Produc disposal ins ruc ions for business users.
Business users should con ac heir suppliers and check he erms and condi ions of he
purchase con rac and ensure ha his produc is no mixed wi h o her commercial was e for
disposal.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 15 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
8 PRODUCT WARRANTY
Your In elligen Charging Limi ed produc is guaran eed agains faul y workmanship ma erials
and malfunc ion for a period of 12 mon hs from he da e of purchase, unless agreed o herwise
by In elligen Charging Limi ed. Wi hin his warran y period In elligen Charging Limi ed will
under ake o repair or replace he produc proved o be faul y.
We recommend you keep all packaging for he dura ion of he 12 mon h warran y, af er which
you should dispose of all was e packaging in accordance wi h your local legisla ion
Produc s which have become faul y wi hin he 12 mon h warran y period mus be re urned o
In elligen Charging Limi ed, where In elligen Charging Limi ed will hen inves iga e he
warran y claim.
In elligen Charging Limi ed produc s, when properly used, will render excellen service.
Therefore, users mus read he User Manual and any o her li era ure supplied wi h he produc
carefully, and fully comply wi h all procedures shown in he li era ure and produc raining /
familiarisa ion sessions, as misuse or failure o follow he ins ruc ions may render his
warran y void.
This warran y is no ransferable and excludes rou ine main enance, consumables, par s
subjec o normal wear and ear, service main enance ki s and damage caused by misuse or
negligence. Warran y claims a ribu able o improper, or careless, use or handling, and o
normal wear, are excluded from his warran y.
In elligen Charging Limi ed only obliga ion shall be o repair or replace such produc s ha
have proved o be faul y. In elligen Charging Limi ed shall no be liable for any injury, loss or
damage, direc or consequen ial, arising ou of he use, or he inabili y o use he produc . The
cus omer shall de ermine he sui abili y of his produc for i s in ended use, and he cus omer
assumes all risks and liabili y wha soever in connec ion herewi h.
Intelligent Charging Limited reserves the right to improve or modify this product
without prior notice.
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 16 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19

LSU80A : Load Support Unit
Operators Manual
This page is in en ionally lef blank
Doc: DWG1061-11-R2 LSU80A Operators manual.odt age 17 of 17 Copyright Material of Intelligent Charging Limited © 2018
Printed On : 17/07/19
Table of contents
Other Intelligent Charging Power Supply manuals
Popular Power Supply manuals by other brands

Dukane
Dukane iQ Auto-Plus 20AT060-U Series user manual

ETC
ETC 99070017EF Replacing

Osram
Osram OPTOTRONIC OT Wi 35/220-240/1A0 NFC CA L manual

Avocent
Avocent SPC1600 - Installation & user guide

M-system
M-system Mini-M M2DYH instruction manual

Matsusada Precision
Matsusada Precision Xpg Series instruction manual

mini-box