Intellimeter I-METER MF Series User manual

Page 1
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
I-METER ® MF SERIES
INSTALLATION AND
USER MANUAL

Page 2
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
TABLE OF CONTENTS
1. PRODUCT DESCRIPTION.........................................................................................................................................4
1.1 Applications 4
1.2 Specifications 5
2. INSTALLATION............................................................................................................................................................6
3. OPERATION AND TROUBLE SHOOTING .....................................................................................................................7
3.1 Metering Rules ...................................................................................................................................................7
4. STEPS TO OPERATE THE METER.................................................................................................................................9
5. CONFIGURATION .....................................................................................................................................................11
6. i-meter®MF SERIES DISPLAY.....................................................................................................................................11
7. i-meter® MF SERIES COMMUNICATION ..................................................................................................................13
7.1 ModBus Module Connection……………………………………………………………………………………………………………………… 13
7.2 i-meter® ModBus RTU Registers Mapping…………………………………………………………………………………………………..14

Page 3
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
WARNING
Field electrical installers must follow proper safety precautions and all local electrical code requirements
during electrical installation, meter wiring, and CT installation. During normal operation of this device,
hazardous voltages are present which can cause severe injury or death. It is strongly recommended that
only qualified, properly trained personnel should perform installation and servicing.
DISCLAIMER
The information presented in this publication has been carefully checked; however, Intellimeter Canada
Inc. (ICI) assumes no responsibility for inaccuracies. The information provided in this document is subject
to change without notice.
CUSTOMER SUPPORT
To report any defect, please contact ICI at 905.839.9199. Prior to returning any merchandise to ICI, a
return material authorization (RMA) number should be obtained from ICI.
STATEMENT OF CALIBRATION
The accuracy and calibration of our instruments are traceable to Measurement Canada, a division of
Industry Canada.
CONFIGURATION
The i-meter®MF series are only to be configured by Intellimeter Canada Inc. at ICI’s Factory according to
the customers provided panel schedule.
INSTALLATION CHECKLIST
Make sure you have received the right meter as per your order and packing list.
INSTALLATION DISCLAIMER
INTELLIMETER does not accept any responsibility and will not be liable for any loss or damage or
expense of any kind whatsoever and howsoever caused by improper installation of its products, be it
indirect, special, incidental or consequential damages (including but not limited to damages for loss of
business, loss of profits, interruption or the like). Please refer to Intellimeter's Terms and Conditions of
Sale available at https://intellimeter.ca/pages/terms-of-service-privacy-statement
ELECTRICAL CODE
Installer is responsible for ensuring that all safety and local electrical codes are followed.

Page 4
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
1. PRODUCT DESCRIPTION
The i-meter®MF series are multifunctional meters, which read real time V, I, W,
VA, pf, THD and energy consumption; meeting LEED and billing requirements.
The meter is an auto ranging voltage input from 120V-347V L-N, and supports
80mA and 100mA outputs Current Transformers (CTs).
There are two models:
• i -meter®MF3 (1 3φ meter, with optional neutral current measurement)
• i -meter®MF6 (2 3φ meters, with optional neutral current measurement)
Measurement Canada, California (CTEP) and CSA approved.
i-meter® MF series
1.1 Applications
The i-meter®MF is designed for a wide variety of applications. In MCMS applications, property
managers can use the latest data for cost allocation and demand side management.
The i-meter®MF3 is configured for 1 point of metering
The i-meter®MF6 is configured for 2 points of metering
Note: Any changes to the original configuration will need to be coordinated with Intellimeter Canada

Page 5
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
1.2 Specifications
Dimensions (Inches)
9.8 H x 7.3 W x 3.5 D
Dimensions (Millimeters)
275 H x 185 W x 89 D
Meter Constants (Kh)
10 Wh
Measurements1
Total Energy: kWh is accumulated in non-volatile memory on the meter;
Real Time Measurements: V (RMS) per phase, I (RMS) per phase, W per
phase, VA per phase, power factor per phase, frequency
Number of Meters
MF3:1/ MF6:2
Meter Elements (CTs)
MF3:1 to 3/ MF6 1 to 7 (1 Neutral)
Voltage Rating
Auto range 120 - 347VAC (L-N), -20% to +10% of rating
Rated VA
< 4 VA
Service Type
1Ø2W, 1Ø3W, 2Ø3W, 3Ø4W wye, 3Ø3W Delta*
Current Transformers
80/100 mA output, Self Shorting Protection
Current Range
0.08 –80mA, 1 –100mA
Instrument Transformers
Interface
Yes
Power Quality
Per phase V & I Total harmonic Distortion (THD), Per phase V & I
individual harmonic order up to 23rd
Memory
45 days (5 min intervals) kWh
Pulse Output
Wh / VAh
Communications
ModBus RTU or TCP/IP, BACnet MSTP or TCP/IP and pulse output.
Frequency
45 to 65 Hz
Accuracy Class
0.5 (Meets ANSI C12.20)
Real Time Measurements
V, I, kW, kVA, kVar, PF, Hz , THd (V/I)
Operating Temperature
-10°C to +53°C
Regulatory Compliance /
Approvals
Measurement Canada, CCSAUS CTEP (CA)
Patent
U.S. Patent No. 8,049,487
1
All instantaneous measurements and interval data must be with a wired/wireless communication
module.

Page 6
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
2. INSTALLATION
To get detailed information about the installation process, please visit:
https://intellimeter.ca/pages/downloads#videos: Intellimeter i-meter®MF6 Installation &
Troubleshooting and/or Intellimeter i meter®MF3 Installation & Troubleshooting.
Verify the number of breakers is the same as the number of meters assigned for that panel board.
Follow the installation drawings. Group the assigned modules to the identified panel board.
Referring to the diagram below, CTs can be embedded in the distribution panel. If the customer has
supplied a special compartment for the meter with their electrical panel, Intellimeter will install the
meter and have the SPE-1000 field evaluation completed. Otherwise, the meter will be installed in
an external enclosure to be mounted near the electrical panel for ease of servicing.
Install the modules into their appropriate position.
Voltage connectors are fixed to the meter PCB. Contractor has to wire to the meter board and use
the wire terminals (spade connectors) provided.
Terminate the voltage reference chain to the designated, 15Amp breaker and ensure the proper
phasing retained as per drawings.
Install the communication connectors to the meter modules and dress the wires they are protected
from damage during feeder and branch circuit installation. MF series can be provided with a pulse
output cable upon request.
Communication cable is to be terminated to a junction box outside of the panel board by the
electrical contractor.
Review general information and wiring diagram.
Carefully read all the WARNING signs and notes.
Check meter serial number and other information on the meter.
All meter modules are assigned within the panel board and are identified with respect to position,
or section of breakers.
A label on the top of each unit indicates meter assignment. Follow the installation drawings that are
supplied with the units.
Do not leave the secondary CT open when current is flowing through the primary circuit. This
applies to instrument CTs as ICI milliamp CTs are self-protected.
Contact ICI if there has been a change made to the layout or if the assigned drawings do not match
the actual distribution panel layout.

Page 7
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
3. OPERATION AND TROUBLE SHOOTING
3.1 Metering Rules
1. Current Transformers (CTs) are directional.
2. Voltage references must be in phase with the load being metered and from the same source.
Rule #1:
If the CTs are mounted in the opposite direction, the polarity of the CT will be opposite.
The arrow on the CT indicates the direction from LINE to LOAD.
Similarly, the “H1” is on the LINE SIDE.
All Intellimeter milli-Amp current transformers 100:0.8A, 200:0.1A, 400:0.1A and 600:0.1A have
self-shorting protection built into the device. They can safely be open circuited while under load.
External Current Transformers (CTs)
Twisted Pair #18-14 stranded colour code
#1
Intellimeter CTs
100A (ICI30CT108-B)
White (+)
Black (-)
#2
Intellimeter CTs
200A (ICI30CT21)
White (+)
Black (-)
#3
Intellimeter CTs
400A (ICI30CT41)
White (+)
Black (-)
#4
Intellimeter CTs
600A (ICI30CT61)
White (+)
Black (-)
#5
Instrument CTs
X000:5A + 20 Turn CTs
White (+)
Black (-)
The maximum length the CT leads can be extended is 30metres.
1 twisted pair wire only for each CT.

Page 8
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
Rule #2:
Check to verify that the voltage potential used, as a reference voltage, is the same phasing as the
loads being metered. ABC is ABC not CBA. The reference voltage must come from the same source.
Voltage reference from another transformer is incorrect and causes inaccurate readings.
Connect the voltage reference to the meters disconnect or terminals making sure it is the same phase
sequence.
Usually:
Line 1 = Red or ‘A’ phase
Line 2 = Black or ‘B’ phase
Line 3 = Blue or ‘C’ phase
Neutral = White
Note: Colour sequence may vary depending on the country and region.
Rule #3:
When the metering system is tested at Intellimeter’s factory, the CT’s are assigned to a meter
and to a specific element of that meter. The CTs are recommended to be installed and used only
with the meter and element that they have been tested with.
Each CT has been identified so it can be easily installed by following the installation drawing that
was designed for that particular distribution.
Follow the Installation Drawing! If there is a discrepancy with the drawing in comparison to your
distribution panel, call us for assistance.

Page 9
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
4. STEPS TO OPERATE THE METER
Step 1: Connect three phase voltage to Voltage Inputs terminals;
Step 2: Connect all CTs to CT Inputs according to Figures below;
Step 3: Power the meter
i-meter®MF3 wiring diagram

Page 10
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
i-meter®MF6 series wiring diagram

Page 11
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 © MF Series Manual
5. CONFIGURATION
The i-meter® MF series meter is a mA meter, which uses any Measurement Canada approved mA
current transformers. In order to have the same meter constants, the i-meter® MF series meter must be
configured in the factory to match with the CT supplied with the meter. If the requirement changes, the
meter will need to be reconfigured at our factory.
6. i-meter®MF SERIES DISPLAY
The i-meter®MF3 and the i-meter®MF6 have a three-line LCD that shows both energy consumption and
real-time measurements.
Three-line LCD (3x9 character)
i-meter®MF3 is a single three-phase meter. It displays energy consumptions and instantaneous
measurements, such as voltage, current, wattage etc. It is a multifunctional meter. See all screens below.
Note: The “i_meter®1” indicates meter 1 measurements on this screen. The “i_meter45®2” indicates
meter 2 measurements on this screen. See below for all display functions.
Screen #1
I C I
ICI
i_meter® 123456 $$$
→
←
1
2
3
4
5
6
7.
8
9
k W hL1
L2 L3
1
2
3
4
5
6
7.
8
9
k VAh
L1 L2 L3
0
0
0
5
6
7.
0
0
0
k W
L1 L2 L3

Page 12
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 MF Series Manual
Line 1 –Total kWh
Line 2 –Total kVAh
Line 3 –Total kW (Three Phase Watts)
Screen #2
I C I
ICI
i_meter® 123456 $$$
→
←
1
2
1.
4
-
-
0.
9
5
V
Pf
L1
1
2
3.
6
-
-
0.
9
2
V
Pf
L2
1
2
4.
8
-
-
0.
9
8
V
Pf
L3
Line 1 –Phase A Voltage –Power Factor
Line 2 –Phase B Voltage –Power Factor
Line 3 –Phase C Voltage –Power Factor
Screen #3
I C I
ICI
i_meter® 123456 $$$
→
←
0
3
1
5.
1
-
6
0.
5
A
Hz
L1
0
2
9
5.
7
-
6
0.
5
A
Hz
L2
0
1
2
6.
5
-
6
0.
5
A
Hz
L3
Line 1 –Phase A Current –System Frequency
Line 2 –Phase B Current –System Frequency
Line 3 –Phase C Current –System Frequency

Page 13
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 MF Series Manual
Screen #4
I C I
ICI
i_meter® 123456 $$$
→
←
0
3
-
1
2
-
0
2
V
%
L1 L2 L3
0
8
-
1
2
-
0
2
A
%
L1 L2 L3
n
E
U
L
-
1
0
6.
8
A
Line 1 –Phase A, B and C Voltage THD
Line 2 –Phase A, B and C Current THD
Line 3 –Neutral Current
7. i-meter® MF SERIES COMMUNICATION
The i-meter®MF series ModBus module enables the meter to communicate on a ModBus system. It presents
real time measurements, such as voltage, current, THD etc. The module supports ModBus RTU communication
over an RS-485 network. By default, the module communicates at 9600 bps, 8 data bits, no parity and 1 stop
bit (8N1). The communication parameters and ModBus ID may be changed through the ModBus registers.
7.1 ModBus Module Connection
RJ45 Connection

Page 14
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 MF Series Manual
7.2 i-meter® ModBus RTU Registers Mapping
The ModBus module has a plethora of registers that present the metering data, as well as diagnostic
information for the module itself. The bulk of the registers are available using the Read Holding Register
ModBus command, while the Read Input Registers provides direct read access to the non-volatile memory.
The system registers provide general information about the meter and the ModBus module. This
information is the identification data and it generally remains constant with the exception of the up time.
Configuration Parameters:
Modbus
Address
Name
Format
Access
Default
40003
Firmware Version
UINT16
41002
Address
UINT16
R/W
1
41003
Baud Rate
Enumated
R/W
3 = 9600 bps
Note
1. Address - 41002: Changes to the ModBus address takes effect
immediately. The next command must use the changed address,
otherwise the module will not respond.
2. Baud Rate - 41003: 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 =
57600 bps; 7 = 115200 bps. The Baud Rate takes effect after power
cycling.
3. Firmware Version: V4.64 (the same firmware as the i-45)
4. Hardware Version: 101-1357 REV-A

Page 15
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 MF Series Manual
Meter 1 Information:
Modbus
Address
Name
Format
Unit
Default
41100
Active Phases
Bit map
x1
41101
Voltage A
UINT32
x0.001V
41103
Voltage B
UINT32
x0.001V
41105
Voltage C
UINT32
x0.001V
41107
Current A
UINT32
x0.001A
41109
Current B
UINT32
x0.001A
41111
Current C
UINT32
x0.001A
41113
Watts A
INT32
W
41115
Watts B
INT32
W
41117
Watts C
INT32
W
41119
Volt-Amp A
INT32
VA
41121
Volt-Amp B
INT32
VA
41123
Volt-Amp C
INT32
VA
41131
Power Factor A
INT32
0.001 Units
41133
Power Factor B
INT32
0.001 Units
41135
Power Factor C
INT32
0.001 Units
41143
kWh
UINT32
X0.001kWh
41145
kVAh
UINT32
X0.001kVAh
41149
Frequency
UINT32
0.01 Hz
Note
1. Active Phases - 41100: 0x0001 - Meter uses phase A; 0x0002 -
Meter uses phase B; 0x0004 - Meter uses phase C.

Page 16
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 MF Series Manual
Meter 2 Information:
Modbus
Address
Name
Format
Unit
Default
41200
Active Phases
Bit map
x1
41201
Voltage A
UINT32
x0.001V
41203
Voltage B
UINT32
x0.001V
41205
Voltage C
UINT32
x0.001V
41207
Current A
UINT32
x0.001A
41209
Current B
UINT32
x0.001A
41211
Current C
UINT32
x0.001A
41213
Watts A
INT32
W
41215
Watts B
INT32
W
41217
Watts C
INT32
W
41219
Volt-Amp A
INT32
VA
41221
Volt-Amp B
INT32
VA
41223
Volt-Amp C
INT32
VA
41231
Power Factor A
INT32
0.001 Units
41233
Power Factor B
INT32
0.001 Units
41235
Power Factor C
INT32
0.001 Units
41243
kWh
UINT32
X0.001kWh
41245
kVAh
UINT32
X0.001kVAh
41249
Frequency
UINT32
0.01 Hz
Note
1. Active Phases - 41100: 0x0001 - Meter uses phase A; 0x0002 -
Meter uses phase B; 0x0004 - Meter uses phase C.

Page 17
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 MF Series Manual
Harmonic Distortion :
Modbus
Address
Name
Format
Unit
Default
47001
THD (IA, Meter 1)
UINT16
0.01%
47021
THD (IB, Meter 1)
UINT16
0.01%
47041
THD (IC, Meter 1)
UINT16
0.01%
47061
THD (IA, Meter 2)
UINT16
0.01%
47081
THD (IB, Meter 2)
UINT16
0.01%
47101
THD (IC, Meter 2)
UINT16
0.01%
47001
THD (VA, Meter 1)
UINT16
0.01%
47001
THD (VB, Meter 1)
UINT16
0.01%
47001
THD (VC, Meter 1)
UINT16
0.01%
Note
The THD is for reference only

Page 18
Intellimeter Canada Inc.
1125 Squires Beach Road, Pickering, ON, L1W 3T9 • Tel: (905) 839-9199
Copyright 2020 MF Series Manual
Thank you for giving us the opportunity to serve you. We
appreciate your business and the confidence you have
placed in us.
Please visit us @ https://intellimeter.ca
or call us @ 905-839-9199 if you need any further
assistance.
This manual suits for next models
2
Table of contents
Other Intellimeter Measuring Instrument manuals