Cables specifications
Inxpect SRE 100 and 200 Series
Copyright © 2023 Inxpect S.p.A. - All Rights Reserved
Revision
Author
Date
Notes
v01
B.Treachi
21/06/2018
Initial version
v02
B.Treachi
18/07/2018
Small changes
v03
B.Treachi
22/02/2019
Small changes
v04
B.Treachi
08/03/2019
Added caption to the connector pictures
v05
B.Treachi
01/04/2019
Added new lengths of the cable between sensors
v06
B.Treachi
11/07/2019
Added terminator resistor description
v07
I.Paderno
02/01/2020
Revised cable technical data, modified cable schemes, added
chapter “length of cables”, added purchase products code
v08
I.Paderno
09/01/2020
Added example of connection with the controller, minor fixing
v09
L. Nava
04/03/2020
Added mandatory cable specifications
v10
B.Treachi
14/08/2020
Added ISC-B01 controller
v11
B.Treachi
12/02/2021
Added SBV System BUS
v12
B.Treachi
08/03/2021
Changed AWG codes and cables material
v13
B.Treachi
07/04/2021
Changed description of max length
v14
B.Treachi
07/04/2021
Changed example picture
v15
B.Treachi
29/04/2021
Changed colors for the new cables
v16
B.Treachi
12/04/2022
Renamed products, removed LBK System
v17
B.Treachi
10/10/2022
Changed max allowed length for 200 Series
v18
B.Treachi
25/10/2022
Added new cable length (20 m)
v19
B.Treachi
13/01/2023
Added new cable length (30 m). Removed old product names.
V20
B.Treachi
09/02/2023
Added new products, removed 30 m length cable.

Cables specifications - Inxpect SRE 100 and
200 Series
Page 2/17
Revision
Approved by
Date
v01
GS
21/06/2018
v07
B.Treachi
03/01/2020
v08
B.Treachi
09/01/2020
v09
B.Treachi
04/03/2020
v11
L. Nava
04/03/2021
v13
I. Paderno
07/04/2021

Cables specifications - Inxpect SRE 100 and
200 Series
Page 3/17
1. Introduction
This document is related to Inxpect SRE 100 Series and 200 Series.
For LBK System, please have a look at the respective documentation.
1.1 Control units
Both Inxpect SRE 100 and 200 Series use one of the following control units:
•Type A control units:
oC201A-PNS
oC201A-F
oC202A
oC203A
•Type B control units:
oC201B-P
oC201B-F
oC202B
oC203B
Please download the Instruction Manual from Inxpect Tools (https://tools.inxpect.com/) to have details about the
differences between the control units.
1.2 Sensors
Each 100 Series control unit can handle up to six S101A sensors.
Each 200 Series can handle:
- up to six sensors type “5 meters range” (S201A, S201A-W, S203A-W), or
- up to six sensors type “9 meters range” (S201A-MLR, S201A-WL, S203A-WL)
Please download the Instruction Manual from Inxpect Tools (https://tools.inxpect.com/) to have details about the
differences between the sensors.
1.3 Cables
Both Inxpect SRE 100 and 200 Series require the use of cables with specific features.
The following chapters describe the technical details of these cables.

Cables specifications - Inxpect SRE 100 and
200 Series
Page 4/17
2. Technical specifications
2.1 Cable technical data
2.1.1 Inxpect SRE 100 Series
The minimum requirements for the cables are the following:
●Number of conductors: 4 wires and 1 drain wire (or shield)
●Conductor cross-sections (nominal): 0.22 mm² (AWG24) for data signal and 0.22 mm² (AWG24) for
power supply
●Impedance: 120 Ω ± 10% (f = 1MHz).
The recommended cable technical data are the following:
●Signal type/category: CAN bus, CANopen®, DeviceNetTM.
●Number of conductors: 4 wires (twisted pair) and 1 drain wire (or shield)
●Conductor cross-sections (nominal): 0.22 mm² (AWG24) for data signal and 0.34 mm² (AWG22) for
power supply
●Cable Material: PVC (depending on final site of application)
●Cable operating temperature: from -20°C to +80°C
●Impedance: 120 Ω ± 10% (f = 1MHz).
●Others specifications: cable and connectors totally shielded with copper braid tin plated
2.1.2 Inxpect SRE 200 Series
The recommended cable technical data are the following:
●Signal type/category: CAN bus, CANopen®, DeviceNetTM.
●Number of conductors: 4 wires (twisted pair) and 1 drain wire (or shield)
●Conductor cross-sections (nominal): 0.22 mm² (AWG24) for data signal and 0.50 mm² (AWG21) for
power supply
●Cable Material: TPU (depending on final site of application)
●Cable operating temperature: from -20°C to +80°C
●Impedance: 120 Ω ± 10% (f = 1MHz).
●Others specifications: cable and connectors totally shielded with copper braid tin plated
2.2 Length of the CAN bus cables
2.2.1 Inxpect SRE 100 Series
The maximum cable length allowed is 30 metres for each bus line (maximum two bus lines allowed), regardless
of the conductor section of the CAN bus cable.
This value can be reached with a cable only or with multiple cables in case of multiple S101A sensors installed
(chain of sensors). In other words the sum of all the cables used in a single bus line does not have to exceed the
maximum length allowed.
Examples:
●Only a sensor installed

Cables specifications - Inxpect SRE 100 and
200 Series
Page 5/17
●Multiple S101A on the same bus line (chain of sensors)
The sum of the length of each cable must be equal or lower than 30 metres.
)
●Multiple sensors in two different bus lines with the control unit inside of the chain (*)
The sum of each cable’s length on the same bus line must be equal or lower than 30 metres, and the overall
length must be at maximum 60 metres.
, where 6 ). Each bus line may
have between 1 and 5 sensors. The maximum number of S101A sensors managed by a single control unit is 6.
(*) When the control unit is inside of the chain, it is necessary to exclude the termination resistance on the control
unit itself using the DIP Switch “A”.

Cables specifications - Inxpect SRE 100 and
200 Series
Page 6/17
2.2.2 Inxpect SRE 200 Series
The maximum length allowed of the whole CAN bus line (from termination to termination) is 100 metres,
regardless of the conductor section of the CAN bus cable.
A maximum number of two bus lines is allowed. Then, the sum of the length of the two lines must be lower (or
equal to) 100 metres.
Please use the Inxpect SRE 200 Series Cable Validator tool to check and validate your desired cable
configuration.
The tools is going to request the following parameters:
- number of BUS lines (one/two)
- number of sensor for each line (up to six)
- length of each cable*
- Power Supply cable section**
* See sections 3.1.2 and 4.1.2 to know the standard lengths provided by Inxpect
** Standard cables provided by Inxpect have a power supply section of 0.50 mm² (AWG21)
2.2.2.1 Examples (Inxpect SRE 200 Series)
●Example 1 - Multiple sensors on the same bus line (chain of sensors), a valid configuration
In the following example we have:
- number of BUS lines: 1
- number of sensor for each line: 3
- length of each cable: 10+5+10 [m]
- Power Supply cable section: 0.50 mm²

Cables specifications - Inxpect SRE 100 and
200 Series
Page 7/17
●Example 2 - Multiple sensors on the same bus line (chain of sensors), a not valid configuration
In the following example we have:
- number of BUS lines: 1
- number of sensor for each line: 6
- length of each cable: 15+5+10+3+2+2 [m]
- Power Supply cable section: 0.50 mm²

Cables specifications - Inxpect SRE 100 and
200 Series
Page 8/17

Cables specifications - Inxpect SRE 100 and
200 Series
Page 9/17
●Example 3 - Multiple sensors in two different bus lines with the control unit inside of the chain (*), a
valid configuration
In the following example we have:
- number of BUS lines: 2
- number of sensor for each line: 3+3
- length of each cable: 10+5+10 [m] and 5+5+5 [m]
- Power Supply cable section: 0.34 mm²

Cables specifications - Inxpect SRE 100 and
200 Series
Page 10/17
●Example 4 - Multiple sensors in two different bus lines with the control unit inside of the chain (*), a not
valid configuration
In the following example we have:
- number of BUS lines: 2
- number of sensor for each line: 4+2
- length of each cable: 15+5+7+10 [m] and 10+5 [m]
- Power Supply cable section: 0.34 mm²

Cables specifications - Inxpect SRE 100 and
200 Series
Page 11/17
(*) Each bus line may have between 1 and 5 sensors. The maximum number of S201A sensors managed by a
single control unit is 6.
When the control unit is inside of the chain, it is necessary to exclude the termination resistance on the control
unit itself using the DIP Switch “A”.
3. Cable between the control unit and the first
sensor
The cable between the control unit and the first sensor must have an M12 female connector “A-coded” in order to
plug into the first sensor, and free wires to plug in the control unit screw terminal.
The connector may be straight or 90° angled. In case of installation with the sensor anchored to a vertical plane
the 90° angled version is suggested (example: wall installation).
Example picture:
In the case of purchased cable from Inxpect the cable schematics and colour association is the following.

Cables specifications - Inxpect SRE 100 and
200 Series
Page 12/17
Notes:
●the shield wire must be connected to EARTH in the electrical cabinet
●in Inxpect cable with conductor section of 0.50 mm² (AWG21) for power supply, a light-blue cap is
present at the end of the shield wire to better distinguish it from all the other wires.

Cables specifications - Inxpect SRE 100 and
200 Series
Page 13/17
Example of connection of C201A-PNS control unit with an S101A sensor:
Example of connection of C201A-PNS control unit with S201A sensor:

Cables specifications - Inxpect SRE 100 and
200 Series
Page 14/17
3.1 Product purchase code for the cable between control unit
and first sensor
3.1.1 SRE 100 Series sensor
It is possible to order the following lengths of cable from Inxpect:
Image
Purchase Code
Length
Description
08000003
5 metres
cable between sensor
and control unit, PVC,
connector M12 90°
angled, A-coded
08000004
10 metres
08000006
15 metres
3.1.2 SRE 200 Series sensor
It is possible to order the following lengths of cable from Inxpect:
Image
Purchase Code
Length
Description
08000110
5 metres
cable between sensor
and control unit, TPU,
connector M12 90°
angled, A-coded
08000111
10 metres
08000112
15 metres
08000113
20 metres

Cables specifications - Inxpect SRE 100 and
200 Series
Page 15/17
4. Cable between two sensors
The cable between two sensors (both SRE 100 Series or both SRE 200 Series) has the following schematic
Example picture
4.1 Product purchase code for the cable between two sensors
4.1.1 SRE 100 Series sensor
It is possible to order the following lengths of cable from Inxpect:
Image
Purchase Code
Length
Description
08000007
3 metres
cable between a sensor
and another sensor,
PVC, connectors M12
90° angled, A-coded
08000013
5 metres
08000014
10 metres

Cables specifications - Inxpect SRE 100 and
200 Series
Page 16/17
08000016
15 metres
4.1.2 SRE 200 Series sensor
It is possible to order the following lengths of cable from Inxpect:
Image
Purchase Code
Length
Description
08000120
3 metres
cable between a sensor
and another sensor,
TPU, connectors M12
90° angled, A-coded
08000121
5 metres
08000122
10 metres
08000123
15 metres
5. Bus terminator
For the last sensor in the CAN bus a termination resistor of 120 Ω must be installed between the signals CAN_H
and CAN_L, as indicated in the following picture.
It is possible to order an M12 male connector A-coded including the bus terminator resistor.

Cables specifications - Inxpect SRE 100 and
200 Series
Page 17/17
Image
Purchase Code
Description
07000003
Bus terminator M12, straight 180°,
male, 5 poles, A-coded.
1 resistance of 120Ω 1/2W
between pole 4 and 5.
This manual suits for next models
9
Table of contents
Popular Control Unit manuals by other brands

INOXPA
INOXPA INNOVA F Installation, service & maintenance instruction

LEPARD
LEPARD AM.011 Series Installation and operation manual

quiko
quiko QK-CE220CTN Installation and operation manual

Bosch
Bosch D113 installation manual

Bosch
Bosch Rexroth M SED 10 XN Series operating instructions

CLA-VAL
CLA-VAL 81-02 installation instructions