Note: Before testing, ensure the LUX is set at right end
() and the TIME is set at left end ( ).
1. Aim sensor head at desired detection area. Apply
the mains power and wait about 30 seconds for
sensor to warm up. Light will be on during warm
up period and off once warm up finished.
2. Walk across within the detection area at normal
speed, light should be switched on when sensor
detects the motion. Stop and wait for light off,
repeat same process until the whole coverage is
identified and satisfied.
3. After walk test completed, adjust the LUX and
TIME trimmers as desired.
A. Range Adjustment
Maximum range can be obtained when the sensor
head is set horizontal. The range can be reduced
by tilting sensor head downward. The detection
zones can also be masked by applying the
provided masking label on the lens segments.
Firstly, refer to the detection pattern diagram and
locate the respective segments should be masked.
Cut the masking label and stick on the segments.
Range adjustment can eliminate the detections that
cause unwanted light switching.
B. TIME Adjustment
TIME trimmer controls light-off delay time after the
last motion is detected. Turn the trimmer clockwise
to increase the delay time.
C. LUX Adjustment
LUX trimmer controls the SenSwitch operation by
sensing the ambient light level. After testing
completed, adjusting LUX trimmer to the left end
( ), so that SenSwitch only switch on the light at
certain darkness.
To set proper darkness for SenSwitch operation,
rotate the trimmer clockwise from left end position
slowly when the ambient light level is preferred,
stop rotating once the light is on.
Power supply ........100-250 VAC
Maximum load ......10A resistive
Detection angle.....150wide
Detection range ....18 meter (60 ft) at 25C
Detection speed.... 0.15 ~ 3 m/sec.
Mounting height....1.8 ~ 3.0 m
Delay time .............8 seconds ~ 8 minutes (approx.)
Lux range ..............2 ~ 2000 lux (approx.)
Sensor head tilt..... 80vertical
Protection rate.......IP54
Op. temperature....-20C~50C (-4F ~122F)
Dimensions ...........125 x 105 x 62 mm
Specifications are subject to change without prior notice.
058-78002-002V4.0 2/6/17’