iSMA CONTROLLI SfAR-S-8TO User manual

www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
SfAR-S-8TO
User Manual
Expansion Module - 8 Triac Outputs

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 2 of 20
Table of Contents
1 Introduction ............................................................................................................................. 3
1.1 Revision History................................................................................................................................3
2 Safety Rules.............................................................................................................................. 4
3 Module Features..................................................................................................................... 5
3.1 Purpose and Description of the Module ...................................................................................5
3.2 Technical Specification ...................................................................................................................5
3.3 Dimensions .......................................................................................................................................6
4 Communication....................................................................................................................... 7
4.1 Grounding and Shielding...............................................................................................................7
4.2 Network Termination......................................................................................................................7
4.3 Types of Modbus Functions..........................................................................................................9
4.4 Communication Settings................................................................................................................9
4.4.1 Default Settings..........................................................................................................................9
4.5 Restoring Default Configuration ..................................................................................................9
4.6 Configuration Registers............................................................................................................... 10
4.7 Watchdog........................................................................................................................................ 10
5 Indicators................................................................................................................................ 11
6 Connections........................................................................................................................... 12
6.1 Block Diagram ............................................................................................................................... 12
6.2 Power Supply Connection .......................................................................................................... 12
6.2.1 DC Power Connection ........................................................................................................... 12
6.2.2 AC Power Connection............................................................................................................ 13
6.3 Communication Bus Connection.............................................................................................. 13
6.4 Connection of Triac Outputs ..................................................................................................... 13
6.4.1 Connection of Electrovalve................................................................................................... 13
6.4.2 Connection of Resistive Load .............................................................................................. 14
6.5 Quick Connector........................................................................................................................... 14
7 DIP Switch............................................................................................................................... 15
8 Module Registers.................................................................................................................. 16
8.1 Registered Access......................................................................................................................... 16
8.2 Bit Access........................................................................................................................................ 18
9 Configuration Software ....................................................................................................... 20

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 3 of 20
1 Introduction
Thank you for choosing our product.
This manual will help you with proper handling and operating of the device.
The information included in this manual have been prepared with utmost care by our
professionals and serve as a description of the product without incurring any liability for
the purposes of commercial law. This information does not discharge you from the
liability of your own judgement and verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations concluded
therein.
1.1 Revision History
Rev. Date Description
3.2 25 May 2022 Rebranded
Table 1. Revision history
WARNING!
Failure to follow instructions can result in equipment damage or impede the use of
the hardware or software.

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 4 of 20
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2 Safety Rules
Improper wiring of the product can damage it and lead to other hazards. Make sure
that the product has been correctly wired before turning the power on.
Before wiring or removing/mounting the product, make sure to turn the power off.
Failure to do so might cause an electric shock.
Do not touch electrically charged parts such as power terminals. Doing so might cause
an electric shock.
Do not disassemble the product. Doing so might cause an electric shock or faulty
operation.
Use the product only within the operating ranges recommended in the specification
(temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure
to do so might cause a fire or faulty operation.
Firmly tighten the wires to the terminal. Failure to do so might cause a fire.
Avoid installing the product in close proximity to high-power electrical devices and
cables, inductive loads, and switching devices. Proximity of such objects may cause an
uncontrolled interference, resulting in an instable operation of the product.
Proper arrangement of the power and signal cabling affects the operation of the entire
control system. Avoid laying the power and signal wiring in parallel cable trays. It can
cause interferences in monitored and control signals.
It is recommended to power controllers/modules with AC/DC power suppliers. They
provide better and more stable insulation for devices compared to AC/AC transformer
systems, which transmit disturbances and transient phenomena like surges and bursts
to devices. They also isolate products from inductive phenomena from other
transformers and loads.
Power supply systems for the product should be protected by external devices limiting
overvoltage and effects of lightning discharges.
Avoid powering the product and its controlled/monitored devices, especially high
power and inductive loads, from a single power source. Powering devices from a single
power source causes a risk of introducing disturbances from the loads to the control
devices.
If an AC/AC transformer is used to supply control devices, it is strongly recommended
to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects,
which are dangerous for devices.
Long monitoring and control lines may cause loops in connection with the shared
power supply, causing disturbances in the operation of devices, including external
communication. It is recommended to use galvanic separators.
To protect signal and communication lines against external electromagnetic
interferences, use properly grounded shielded cables and ferrite beads.
Switching the digital output relays of large (exceeding specification) inductive loads can
cause interference pulses to the electronics installed inside the product. Therefore, it
is recommended to use external relays/contactors, etc. to switch such loads. The use
of controllers with triac outputs also limits similar overvoltage phenomena.
Many cases of disturbances and overvoltage in control systems are generated by
switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they
do not have appropriate built-in noise reduction circuits, it is recommended to use
external circuits such as snubbers, varistors, or protection diodes to limit these effects.

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 5 of 20
3 Module Features
3.1 Purpose and Description of the Module
The SFAR-S-8TO module is an innovative device that provides a simple and cost effective
extension of the number of lines of output in many popular PLCs.
The module has 8 triac outputs. All of the outputs are isolated from the logic using
optocouplers.
The module is connected to the RS485 bus with a twisted-pair wire. Communication is via
Modbus RTU or Modbus ASCII. The use of 32-bit ARM core processor provides fast
processing and quick communication. The baud rate is configurable from 2400 to
115200.
The module is designed for mounting on a DIN rail in accordance with DINEN5002.
The module is equipped with a set of LEDs to indicate the status of inputs and outputs,
which is useful for diagnostic purposes and helping to find errors.
Module configuration is done via USB by using a dedicated computer program. It also
allows for changing the parameters using the Modbus protocol or set the Modbus
address using the DIP switches under the front panel.
3.2 Technical Specification
Power Supply Voltage 10-38 V DC; 10-28 V AC
Power consumption (with active
Modbus transmission, all outputs
on)
4 W at 24 V DC
3 VA at24 V AC
Triac Outputs No. of outputs 8
Switching voltage 20 to 250 V AC
Continuous load per channel 0.5 A (1.5 A peak 30 s)
Temperature Work -10 °C to +50°C (14°F to 122°F)
Storage -40 °C to +85°C (-40°F to 185°F)
Connectors Power supply 2 pins
Communication 3 pins
Outputs 10 pins
Quick connector IDC10
Configuration mini USB

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 6 of 20
Size Height 119.1 mm (4.689 in)
Length 110.9 mm (4.366 in)
Width 22.7 mm (0.894 in)
Interface RS485 Up to 128 devices
Table 2. Technical specification
3.3 Dimensions
The appearance and dimensions of the module are shown below. The module is
mounted directly to the rail in the DIN industry standard. Power connectors,
communication and IOs are at the bottom and top of the module. USB connector
configuration and indicators are located on the front of the module.
Figure 1. Dimensions

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 7 of 20
•
•
•
•
4 Communication
4.1 Grounding and Shielding
In most cases, I/O modules will be installed in an enclosure along with the other devices,
which generate electromagnetic radiation. Relays, contactors, transformers, motor
invertors, etc., are examples of such devices. Radiation can induce electrical noise into
both power and signal lines, as well as direct radiation into the module. Whether or not
the SfAR modules are immune to such effects, the interferences must be suppressed at
their source if possible to ensure the proper functioning of the entire system.
Appropriate grounding, shielding and other protective steps should be taken at the
installation stage to prevent these effects. It is recommended to at least follow the rules
below:
line power cables must be routed with spatial separation from signal and data
transmission cables;
aAnalog and digital signal cables should also be separated;
it is recommended to use shielded cables for analog signals, cable shields should not
be interrupted by intermediate terminals;
the shielding should be earthed directly after the cable enters the cabinet.
It is recommended to install interference suppressors when switching inductive loads
(e.g., coils of contactors, relays, solenoid valves). RC snubbers or varistors are suitable for
AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must
be connected as close to the coil as possible.
4.2 Network Termination
Transmission line effects often present problems for data communication networks.
These problems include reflections and signal attenuation. To eliminate the presence of
reflections of signal from the end of the cable, the cable must be terminated at both ends
with a resistor across the line adequate to its characteristic impedance. Both ends must
be terminated since the propagation is bidirectional. In case of an RS485 twisted pair
cable, this termination is typically 120 Ω.
Setting Module Address in RS485 Modbus Network
The following table shows how to set switch to determine the address of the module. The
module address is set with the switches in the range of 0 to 31. Addresses from 32 to 255
can be set via RS485 or USB.
Addr SW1 SW2 SW3 SW4 SW5
0 OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF
2 OFF ON OFF OFF OFF
3 ON ON OFF OFF OFF
4 OFF OFF ON OFF OFF

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 8 of 20
Addr SW1 SW2 SW3 SW4 SW5
5 ON OFF ON OFF OFF
6 OFF ON ON OFF OFF
7 ON ON ON OFF OFF
8 OFF OFF OFF ON OFF
9 ON OFF OFF ON OFF
10 OFF ON OFF ON OFF
11 ON ON OFF ON OFF
12 OFF OFF ON ON OFF
13 ON OFF ON ON OFF
14 OFF ON ON ON OFF
15 ON ON ON ON OFF
16 OFF OFF OFF OFF ON
17 ON OFF OFF OFF ON
18 OFF ON OFF OFF ON
19 ON ON OFF OFF ON
20 OFF OFF ON OFF ON
21 ON OFF ON OFF ON
22 OFF ON ON OFF ON
23 ON ON ON OFF ON
24 OFF OFF OFF ON ON
25 ON OFF OFF ON ON
26 OFF ON OFF ON ON
27 ON ON OFF ON ON
28 OFF OFF ON ON ON
29 ON OFF ON ON ON
30 OFF ON ON ON ON

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 9 of 20
Addr SW1 SW2 SW3 SW4 SW5
31 ON ON ON ON ON
Table 3. Setting module address in RS485 Modbus network
4.3 Types of Modbus Functions
There are 4 types of Modbus functions supported by the SfAR modules.
Type Beginning Address Variable Access Modbus Command
1 00001 Digital Outputs Bit
Read/write
1, 5, 15
2 10001 Digital Inputs Bit
Read
2
3 30001 Input Registers Registered
Read
3
4 40001 Output Registers Registered
Read/write
4, 6, 16
Table 4. Types of Modbus functions supported by the module
4.4 Communication Settings
The data stored in the module's memory is given in the 16-bit registers. The access to
registers is via Modbus RTU or Modbus ASCII.
4.4.1 Default Settings
The default configuration can be restored with the DIP switch, SW6.
Baud Rate 19200
Parity No
Data Bits 8
Stop Bits 1
Reply Delay [ms] 0
Modbus Mode RTU
Table 5. Default settings
4.5 Restoring Default Configuration
To restore the default configuration, follow the steps below:

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 10 of 20
•
•
•
•
turn the power off;
turn the switch SW6 on;
turn the power on;
when power and communication LED are lit, turn the switch SW6 off.
WARNING! After restoring the default configuration, all values stored in the registers will
be cleared as well.
4.6 Configuration Registers
Modbus Address Decimal Address Hex Address Name Values
40003 2 0x02 Baud Rate 0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005 4 0x04 Parity 0 – none
1 – odd
2 – even
3 – always 0
4 – always 1
40004 3 0x03 Stop Bits 1 – one stop bit
2 – two stop bits
40004 3 0x03 Data Bits 7 – 7 data bits
8 – 8 data bits
40006 5 0x05 Response Delay Time in ms
40007 6 0x06 Modbus Mode 0 – RTU
1 – ASCII
Table 6. Configuration registers
4.7 Watchdog
This 16-bit register specifies the time in milliseconds to watchdog reset. If module does
not receive any valid message within that time, all digital and analog outputs will be set to
the default state.
This feature is useful if there is an interruption in data transmission and for security
reasons. Output states must be set to the appropriate state in order to assure the safety
of persons or property.
The default value is 0 milliseconds, which means the watchdog function is disabled.

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 11 of 20
5 Indicators
Figure 2. Indicators
Indicator Description
Power Supply The LED indicates that the module is correctly powered
Communication The LED lights up when the unit received the correct packet and sends
the answer
Outputs State The LED indicates that the output is on
Table 7. Description of indicators

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 12 of 20
6 Connections
6.1 Block Diagram
Figure 3. Block diagram
6.2 Power Supply Connection
6.2.1 DC Power Connection
Figure 4. DC power connection

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 13 of 20
6.2.2 AC Power Connection
Figure 5. AC power connection
6.3 Communication Bus Connection
Figure 6. Communication bus connection
6.4 Connection of Triac Outputs
6.4.1 Connection of Electrovalve
Figure 7. Connection of electrovalve

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 14 of 20
6.4.2 Connection of Resistive Load
Figure 8. Connection of resistive load
6.5 Quick Connector
The Quick Connector is a unique feature of modules that allows for quickly connecting a
group of devices with a flat ribbon cable. Thanks to this solution, it is enough to connect
power an RS485 communication to one of the devices in the group, and the others will be
powered and communicated with ribbon cable.
The Quick Connector is sufficient to connect up to 10 devices next to each other. It is
important that the various types of modules in the SfAR-S family can be connected with
the ribbon cable.
Figure 9. Quick Connector

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 15 of 20
7 DIP Switch
Figure 10. DIP switch
Switch Function Description
1 Module address +1 Setting module address from 0 to 31
2 Module address +2
3 Module address +4
4 Module address +8
5 Module address +16
6 Restoring default settings Restoring default settings
Table 8. Description of switches

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 16 of 20
8 Module Registers
8.1 Registered Access
Modbus
Address
Decimal
Address
Hex
Address
Register Name Access Description
30001 0 0x00 Version/Type Read Version and type of
the device
30002 1 0x01 Switches Read Switches state
40003 2 0x02 Baud Rate Read/write RS485 baud rate
40004 3 0x03 Stop Bits & Data Bits Read/write No. of stop bits &
data bits
40005 4 0x04 Parity Read/write Parity bit
40006 5 0x05 Response Delay Read/write Response delay in
ms
40007 6 0x06 Modbus Mode Read/write Modbus mode (ASCII
or RTU)
40009 8 0x08 Watchdog Read/write Watchdog
40013 12 0x0C Default Outputs State Read/write Default outputs
state
40019 18 0x12 PWM Output Read/write PWM output state
40020 19 0x13 DefaultDuty Cycle
Output 1
Read/write Value default duty
cycle output 1
From 0 to 100%
20021 20 0x14 DefaultDuty Cycle
Output 2
Read/write Value default duty
cycle output 2
From 0 to 100%
20022 21 0x15 DefaultDuty Cycle
Output 3
Read/write Value default duty
cycle output 3
From 0 to 100%
20023 22 0x16 DefaultDuty Cycle
Output 4
Read/write Value default duty
cycle output 4
From 0 to 100%
20024 23 0x17 DefaultDuty Cycle
Output 5
Read/write Value default duty
cycle output 5
From 0 to 100%
20025 24 0x18 DefaultDuty Cycle
Output 6
Read/write Value default duty
cycle output 6
From 0 to 100%

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 17 of 20
Modbus
Address
Decimal
Address
Hex
Address
Register Name Access Description
20026 25 0x19 DefaultDuty Cycle
Output 7
Read/write Value default duty
cycle output 7
From 0 to 100%
20027 26 0x1A DefaultDuty Cycle
Output 8
Read/write Value default duty
cycle output 8
From 0 to 100%
40033 32 0x20 Received Packets LSR
(Least Significant
Register)
Read/write No. of received
packets
40034 33 0x21 Received Packets MSR
(Most Significant
Register)
Read/write
40035 34 0x22 Incorrect Packets LSR Read/write No. of received
packets with error
40036 35 0x23 Incorrect Packets MSR Read/write
40037 36 0x24 Sent Packets LSR Read/write No. of sent packets
40038 37 0x25 Sent Packets MSR Read/write
40052 51 0x33 Outputs Read/write Outputs state
40133 132 0x84 Period PWM Output 1 Read/write Range adjustment
period:
0-65535 [s]
40134 133 0x85 Period PWMOutput 2 Read/write Range adjustment
period:
0-65535 [s]
40135 134 0x86 Period PWM Output 3 Read/write Range adjustment
period:
0-65535 [s]
40136 135 0x87 Period PWM Output 4 Read/write Range adjustment
period:
0-65535 [s]
40137 136 0x88 Period PWM Output 5 Read/write Range adjustment
period:
0-65535 [s]
40138 137 0x89 Period PWM Output 6 Read/write Range adjustment
period:
0-65535 [s]
40139 138 0x8A Period PWM Output 7 Read/write Range adjustment
period:
0-65535 [s]

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 18 of 20
Modbus
Address
Decimal
Address
Hex
Address
Register Name Access Description
40140 139 0x8B Period PWM Output 8 Read/write Range adjustment
period:
0-65535 [s]
40141 140 0x8C Duty Cycle Output 1 Read/write Value duty cycle
output 1
From 0 to 100%
40142 141 0x8D Duty Cycle Output2 Read/write Value duty cycle
output 2
From 0 to 100%
40143 142 0x8E Duty Cycle Output3 Read/write Value duty cycle
output 3
From 0 to 100%
40144 143 0x8F Duty Cycle Output4 Read/write Value duty cycle
output 4
From 0 to 100%
40145 144 0x90 Duty Cycle Output5 Read/write Value duty cycle
output 5
From 0 to 100%
40146 145 0x91 Duty Cycle Output6 Read/write Value duty cycle
output 6
From 0 to 100%
40147 146 0x92 Duty Cycle Output7 Read/write Value duty cycle
output 7
From 0 to 100%
40148 147 0x93 Duty Cycle Output 8 Read/write Value duty cycle
output 8
From 0 to 100%
Table 9. Registered access
8.2 Bit Access
Modbus
Address
Dec Address Hex
Address
Register Name Access Description
193 192 0x0C0 Default Output 1
State
Read/write Default output 1
state
194 193 0x0C1 DefaultOutput
2State
Read/write Default output 2
state
195 194 0x0C2 DefaultOutput
3State
Read/write Default output 3
state

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 19 of 20
Modbus
Address
Dec Address Hex
Address
Register Name Access Description
196 195 0x0C3 DefaultOutput
4State
Read/write Default output 4
state
197 196 0x0C4 DefaultOutput
5State
Read/write Default output 5
state
198 197 0x0C5 DefaultOutput
6State
Read/write Default output 6
state
199 198 0x0C6 DefaultOutput
7State
Read/write Default output 7
state
200 199 0x0C7 DefaultOutput
8State
Read/write Default output 8
state
817 816 0x330 Output 1 Read/write Output 1 state
818 817 0x331 Output 2 Read/write Output 2 state
819 818 0x332 Output 3 Read/write Output 3 state
820 819 0x333 Output 4 Read/write Output 4 state
821 820 0x334 Output 5 Read/write Output 5 state
822 821 0x335 Output 6 Read/write Output 6 state
823 822 0x336 Output 7 Read/write Output 7 state
824 823 0x337 Output 8 Read/write Output 8 state
Table 10. Bit access

SfAR-S-8TO User Manual
www.ismacontrolli.com
DMP277en | 3rd Issue rev. 2 | 05/2022
page 20 of 20
9 Configuration Software
The SfAR Configurator is the type of software, which is designed to set the communication
module registers over Modbus network as well as to read and write the current value of
other registers of the module. It is a convenient way to test the system as well as to
observe real-time changes in the registers.
Communication with the module is via the USB cable. The module does not require any
drivers.
Figure 11. PC connection
The SfAR Configurator is a universal software, where it is possible to configure all available
modules.
Figure 12. The SfAR Configurator
Table of contents
Other iSMA CONTROLLI Computer Hardware manuals