Isolite BAL1400TD User manual

ISOLITE WWW.ISOLITE.COM
ISOLITE HEADQUARTERS 800.888.5483 31 WATERLOO AVENUE BERWYN, PA 19312
ISOLITE WEST 800.799.5343 3563 SUELDO SUITE M, SAN LUIS OBISPO, CA 93401
BAL1400TD P.1
INSTALLATION GUIDES ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION.
CONTACT ISOLITE FOR UP TO DATE DETAILS.
WHEN USING THIS LIGHTING DEVICE, SAFETY PRECAUTIONS SHOULD BE FOLLOWED AT ALL TIMES
READ THE INSTRUCTIONS BELOW CAREFULLY AND FOLLOW THEM FOR YOUR OWN SAFETY!
PLEASE SAVE THESE INSTRUCTIONS.
BAL1400TD
INSTALLATION INSTRUCTIONS
FLUORESCENT EMERGENCY BALLAST
1400 LUMENS (TIME DELAY)
1. Prior to installation, battery connector must be left open to prevent high voltage from
being present on output leads (red & yellow). It must be connected only after installation
is complete and A.C. Power is supplied to the unit.
2. This unit can operate commonly used linear and compact uorescent lamps. Please refer
to the “lamps list” label on the ballast for specic lamp information.
3. Please ensure the electricity connections conform to the National Electrical Code and local
regulations if applicable.
4. To avoid electric shock, please disconnect normal and emergency power supplies, and
battery connector of the emergency ballast before servicing.
5. This device is designed for factory or eld installation in either the ballast channel, or
on top of the xture, except air handling heated air outlets, wet or hazardous location
xtures. Do not install this device near gas or electric heaters.
6. AC power source of 120 VAC or 277 VAC is required.
7. The battery in this unit is sealed, and not replaceable in the eld. Please contact
manufacturer for information on servicing the battery.
8. Do not use accessory equipment that is not recommended by manufacturer. Failure to do
so may cause unsafe conditions. Servicing should only be performed by qualied service
personnel.
9. Do not use the product for other than it s intended purpose.
CAUTION: Verify that all replacement lamp types marked on the installed luminaire are also
identied as suitable for use with this inverter/charger pack.

ISOLITE WWW.ISOLITE.COM
ISOLITE HEADQUARTERS 800.888.5483 31 WATERLOO AVENUE BERWYN, PA 19312
ISOLITE WEST 800.799.5343 3563 SUELDO SUITE M, SAN LUIS OBISPO, CA 93401
BAL1400TD P.2
INSTALLATION GUIDES ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION.
CONTACT ISOLITE FOR UP TO DATE DETAILS.
INSTALLATION INSTRUCTIONS
CAUTION:Before installing, make certain the A.C.Power is off and the battery
connector is disconnected.
1. MOUNTING THE EMERGENCY BALLAST(BATTERY PACK)
2. WIRING
Refer to the wiring diagrams on the back page for the appropriate wiring of lamp(s)and ballast.Install in accordance
with the National Electrical Code and local regulations.For additional wiring diagrams consult Customer Service.
4. WIRING THE A.C.INPUT
A. The EMERGENCY BALLAST and A.C.Ballast must be on the same branch circuit.
B. The EMERGENCY BALLAST requires an unswitchedA.C.Power source of either 120 or 277 volts. Select
proper voltage lead and cap the unused lead.
C. When the EMERGENCY BALLAST is used with a switched fixture,the A.C.Input to the EMERGENCY BALLAST
must be connected ahead of the fixture switch.Refer to IIIustration 3 for switched and unswitched fixture wiring diagrams.
IIIustration 1 IIIustration 2
Recessed Troffer Fixture Strip Fixture
EMERGENCY
BALLAST
FIXTURE
BALLAST CHANNEL COVER
7/8”BUSHING
LCTS
PLASTIC TUBE
FIXTURE LENS
EMERGENCY
BALLAST
FIXTURE
BROWN(-)
LEAD
VIOLET(+)
LEAD
OBSERVE PROPER POLARITY
LCTS
Remove the ballast channel cover. Mount the EMERGENCY BALLAST in the ballast channel at least ”away from
the A.C.Ballast(s).
/
12
3. INSTALLING THE LED COMBO TEST SWITCH(LCTS)
Recessed Troffer Fixture - Select a convenient location with proper clearance in the ballast cover and drill or
punch a " hole( "knockout). Insert the " bushing into the hole. Push the plastic tube through the bushing.
Route the leads of the LCTS through the plastic tube. Connect the wires from the unit to the LCTS(VIOLET to
VIOLET, BROWN to BROWN). Push the entire assembly back into the tube until the lens collar rests against the plastic
tube. The plastic tube should be adjusted so that the LCTS is within "of the fixture lens. The LCTS must be
visible after installation. Refer to IIIustration 1.
/
78/
12/
78
/
14
Strip Fixture - Select a convenient location on the fixture so the LCTS can be seen after installation. Allow for
proper clearance inside the fixture and drill or punch a
"
hole. Remove the nut from the LCTS. Push the LCTS
housing into the
"
hole and secure with the nut. Connect the wires from the LCTS(VIOLET to VIOLET,
BROWN to BROWN). Refer to IIIustration2.
/
12
/
12
When battery packs are remote mounted, the remote distance can not exceed of the distance from ballast to
lamp specified by the A.C. ballast manufacturer. For example, if the A.C. ballast manufacturer recommends no
more than 25' remote distance, then the battery pack's remote mounting distance should not exceed 12 ' .
Under no circumstances should the battery pack exceed a distance of 50' from the lamp(s).
/
12
/
12

ISOLITE WWW.ISOLITE.COM
ISOLITE HEADQUARTERS 800.888.5483 31 WATERLOO AVENUE BERWYN, PA 19312
ISOLITE WEST 800.799.5343 3563 SUELDO SUITE M, SAN LUIS OBISPO, CA 93401
BAL1400TD P.3
INSTALLATION GUIDES ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION.
CONTACT ISOLITE FOR UP TO DATE DETAILS.
5. BALLAST WIRING BLOCK DIAGRAM
6. LABELS
Attach the appropriate labels adjacent to the LCTS. Annotate Re-lamping label for lamp type and wattage. The
'Caution' and the 'Re-lamping' labels must be on the fixture in a readily visible location to anyone attempting to
service the fixture.
7. COMPLETING INSTALLATION
When the installation is complete, switch the A.C. power ON and join the EMERGENCY BALLAST S unit connector.
'
BLACK
WHITE
WHT/BLK
WHITE
(277V) ORG
(120V)BLK
VIOLET(+)
BROWN(-)
HOT A.C.LINE
COMMON
LCTS
1
A.C.BALLAST
EMERGENCY
BALLAST
1Select proper voltage lead.Cap unused lead.
IIIustration 3 Switched Fixture Unswitched Fixture
BLACK
WHITE
WHT/BLK
WHITE
(277V) ORG
(120V)BLK
1Select proper voltage lead.Cap unused lead.
A.C.BALLAST
EMERGENCY
BALLAST
HOT A.C.LINE
COMMON
LCTS
1
BROWN(-)
VIOLET(+)
BROWN(-) BROWN(-)
VIOLET(+) VIOLET(+)
OPERATION
TESTING & MAINTENANCE
Normal Mode - A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The LCTS will be
lit providing a visual indication that the EMERGENCY BALLAST is in the standby charging mode.
Emergency Mode - A.C. power fails. The EMERGENCY BALLAST senses the A.C. power failure and automatically
switches to the Emergency Mode. One or two lamps illuminate at reduced output, for a minimum of 90 minutes. When
A.C. Power is restored, the EMERGENCY BALLAST switches the system back to the Normal Mode and resumes battery
charging.
Initial Testing - Allow the unit to charge for approximately 1 hour, then press the LCTS to conduct a short discharge test.
Allow a 24 hour charge before conducting a 1 hour test.
This EMERGENCY BALLAST is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101,
Life Safety Code, outlines the following schedule:
Monthly - Insure that the LCTS is illuminated. Conduct a 30 second discharge test by depressing the LCTS. One lamp
should operate at reduced output.
Annually - Insure that the LCTS is illuminated. Conduct a full 1 hour discharge test. The unit should operate as
intended for the duration of the test.
/
12
/
12
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Pressing the red lens on the LCTS turns off the light on it, interrupts power to the designated A.C. ballast and forces the
unit into emergency mode. The emergency lamp (s) is (are) now lit by the EMERGENCY BALLAST. On releasing the
lens, fixture returns to normal mode after a momentary delay. To simulate a “BLACK OUT” use the circuit breaker to
turn off the AC power.

ISOLITE WWW.ISOLITE.COM
ISOLITE HEADQUARTERS 800.888.5483 31 WATERLOO AVENUE BERWYN, PA 19312
ISOLITE WEST 800.799.5343 3563 SUELDO SUITE M, SAN LUIS OBISPO, CA 93401
BAL1400TD P.4
INSTALLATION GUIDES ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION.
CONTACT ISOLITE FOR UP TO DATE DETAILS.
For One Lamp Emergency Operation
A. One (1) Lamp Instant Start AC Ballast
VIOLET(+)
RED
RED
WHITE
BROWN(-)
BROWN
BROWN
WARNING
LCTS
YELL/BLK
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
WIRE DIAGRAMS FOR LAMP EMERGENCY OPERATION
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
B. Two (2) Lamp Instant Start AC Ballast
WHT/BLK
RED
RED
WHITE
VIOLET(+)
BROWN(-)
BROWN
BROWN
WARNING
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
C. Three (3)Lamp Instant Start AC Ballast
WHT/BLK
RED
RED
WHITE
VIOLET(+)
BROWN(-)
BROWN
BROWN
WARNING
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
WHT/BLK
D. Four (4)Lamp Instant Start AC Ballast
VIOLET(+)
BROWN(-)
RED
RED
WHITE
BROWN
WARNING
BROWN
YELL/BLK
E. One (1) Lamp Rapid Start AC Ballast
RED
RED
WHITE
VIOLET(+)
BROWN(-)
BROWN
BROWN
WARNING
YELL/BLK
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
2
WHT/BLK
2
22
2
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
SWITCHED OR
UNSWITCHED
LINE
F. Two (2) Lamp Rapid Start AC Ballast
RED
RED
WHITE
VIOLET(+)
BROWN(-)
BROWN
WARNING
BROWN
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
2
WHT/BLK
G.Three (3) Lamp Rapid Start AC Ballast
BLACK
WHITE
BLUE BLUE
BLUE/WHITE
YELLOW
RED
LAMP 1
LAMP 2
AC BALLAST
LAMP 3(EMERGENCY)
EMERGENCY
BALLAST
INVERTER
CONNECTOR
RED
BLUE
YELLOW
YELLOW
RED
BLUE/WHITE
BLUE/WHITE
BROWN
BROWN
RED
WHITE
VIOLET(+)
BROWN(-)
WARNING
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
1
COMMON
UNSWITCHED
2
WHT/BLK
WHT/BLK
H.Four (4) Rapid Start AC BallastLamp
BLACK
WHITE
BLUE
BLUE/WHITE
YELLOW
LAMP 1
LAMP 3
AC BALLAST
LAMP 4(EMERGENCY)
EMERGENCY
BALLAST
RED
LAMP 2
YELLOW
YELLOW
RED
RED
BLUE
BLUE
BROWN
BROWN
BLUE/WHITE
BLUE/WHITE
INVERTER
CONNECTOR
RED
WHITE
BROWN
BROWN
VIOLET(+)
BROWN(-)
WARNING
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
WHT/BLK
NOTE: Use the proper tap to unswitched AC leadcap
2
LCTS
LCTS
LCTS
LCTS LCTS
LCTS
LCTS
See Table 1 before connecting See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting

ISOLITE WWW.ISOLITE.COM
ISOLITE HEADQUARTERS 800.888.5483 31 WATERLOO AVENUE BERWYN, PA 19312
ISOLITE WEST 800.799.5343 3563 SUELDO SUITE M, SAN LUIS OBISPO, CA 93401
BAL1400TD P.5
INSTALLATION GUIDES ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION.
CONTACT ISOLITE FOR UP TO DATE DETAILS.
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
WIRE DIAGRAMS FOR LAMP EMERGENCY OPERATION
EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
SELECT PROPER VOLTAGE
LEAD. CAP UNUSED LEAD.
DO NOT MATE CONNECTOR
UNTIL INSTALLATION IS
COMPLETE AND AC POWER
IS SUPPLIED
1
2
NOTE: Use the proper tap to unswitched AC leadcap
For Two Lamps Emergency Operation
A. Two (2)Lamp Instant Start AC Ballast
VIOLET(+)
BROWN(-) RED
RED
WHITE
BROWN
BROWN
WARNING
LCTS
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
WHT/BLK
2
B. Three (3)Lamp Instant Start AC Ballast
VIOLET(+)
BROWN(-)
RED
RED
WHITE
BROWN
BROWN
WARNING
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
2
WHT/BLK
C. Four (4)Lamp Instant Start AC Ballast
VIOLET(+)
BROWN(-) RED
RED
WHITE
BROWN
WARNING
BROWN
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
2
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
WHT/BLK
D. Two (2)Lamp Rapid Start AC Ballast
VIOLET(+)
BROWN(-) RED
RED
WHITE
BROWN
WARNING
BROWN
YELL/BLK
SWITCHED OR
UNSWITCHED
LINE
ORANGE(277V)
WHITE
BLACK
(120V)
1
COMMON
UNSWITCHED
WHT/BLK
2
Emergency only Operation
A. One (1) Lamp Without AC Ballast
RED
RED
WHITE
VIOLET(+)
BROWN(-)
BROWN
BROWN
WARNING
YELL/BLK
WHT/BLK
ORANGE(277V)
WHITE
BLACK
(120V)
2
B. Two (2) Lamp Without AC Ballast
VIOLET(+)
BROWN(-) RED
RED
WHITE
BROWN
WARNING
BROWN
YELL/BLK
YELLOW
WHT/BLK
1
COMMON
UNSWITCHED
ORANGE(277V)
WHITE
BLACK
(120V)
LCTS
LCTS
LCTS
LCTS
LCTS
2
See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting
See Table 1 before connecting

ISOLITE WWW.ISOLITE.COM
ISOLITE HEADQUARTERS 800.888.5483 31 WATERLOO AVENUE BERWYN, PA 19312
ISOLITE WEST 800.799.5343 3563 SUELDO SUITE M, SAN LUIS OBISPO, CA 93401
BAL1400TD P.6
INSTALLATION GUIDES ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION.
CONTACT ISOLITE FOR UP TO DATE DETAILS.
(8')
95 W,110,160,215
75W
(5' 8')/
20,25,30,34,40W
(2'-4')
20,25,34,40W
(2 4')'-
86W
(8')
17,25 W
(
,28,32,40
2'-3'-4')
(
51,59W
5'-8')
17,25,28,32,40W
14,21,28W
(2'-3'-4')
24,39,54W
(3' )-4'
24,39,54W
(3'-4')
14,21
(
,28,35W
2'-3'-4')
G24q-1(4pin)
G24q-3(4pin) G24q-4(4pin)
G24q-5 (4pin)
G24q-2(4pin)
G24q-1(4pin)
G24q-3(4pin) G24q-4(4pin)
G24q-2(4pin)
LAMP
DIAMETER
(2'-3'-4'-4'/5')
BASE TYPE WATTAGE
(LENGTH)
NO.OF LAMPS
(EMERGENCY
MODE)
BROWN
CONNECTOR
T5 SINGLE OR BIPIN 1
T5 HO SINGLE OR BIPIN 1
T5 HO SINGLE OR BIPIN 2
CLOSE
T8 SINGLE OR BIPIN
2
T12 SINGLE OR BIPIN 2OPEN
Compact 13,18,21,26,32,42,57W 1
Circular T9 4-pin 20,32,40W
U-bend T8 Bi-pin 32W
CLOSE
OPEN
T5 SINGLE OR BIPIN 2OPEN
T8 SINGLE OR BIPIN 1CLOSE
OPEN
T12 SINGLE OR BIPIN 1CLOSE
CLOSE
OPEN
Compact 13,18,21,26,32,42W 2
Compact GR10q-4(4pin) 10,16,21,28,38,55W 1 CLOSE
Compact 10,16,21,28,38W 2 OPEN
1CLOSE
Circular T9 4-pin 20,32,40W 2 OPEN
1CLOSE
U-bend T12 Bi-pin 34,40W 1 CLOSE
U-bend T12 Bi-pin 34,40W 2OPEN
U-bend T8 Bi-pin 32W OPEN
2
TABLE 1 (FOR BROWN CONNECTOR)
T8HO SINGLE OR BIPIN
1
44W CLOSE
T8HO SINGLE OR BIPIN
1
OPEN
T12HO SINGLE OR BIPIN 1OPEN
2G11(4pin)
Compact 18,24,36,40,50,55W 1CLOSE
OPEN
Compact 18,24,36,40,50W 2
2G11(4pin)
GR10q-4(4pin)
Circular T5
Circular T5
22,40,55W 1 CLOSE
22,40W 2 OPEN
T8 SINGLE OR BIPIN 1OPEN
T12 SINGLE OR BIPIN 1OPEN
4-pin
4-pin
Table of contents
Other Isolite Security Sensor manuals
Popular Security Sensor manuals by other brands

C.P. Electronics
C.P. Electronics EBDHS-SR manual

IR-Tec
IR-Tec DUOGUARD DP-550 installation instructions

TECHNO-AC
TECHNO-AC Success AG-309.15 N operating instructions

C & K Systems
C & K Systems DUAL TEC DT-900 Series quick start guide

Abus
Abus FUBW50010 manual

C.P. Electronics
C.P. Electronics EBDSPIR-CB System manual