Ista ultego III smart plus Parts list manual

ultego III smart plus
Technical description
32 22 101 001 a
Date: 07.04.2017
ista Middle East FZE
Ultrasonic heating and cooling meter
ultego III smart plus
Residential

Outstanding features 2/26
Outstanding features
Meter for measurement of flow and energy in a heat or cold circuit with water using the ultra-
sonic principle.
Important properties are:
Non-wearing due to non-moving parts
Compact, space-saving design
Robust all-metal measuring section
Exceptional robust DuraSurface™
Easy installation and read out
Fast and intelligent temperature measuring interval
Large, easy readable display
Flow measurement with maximum values
2 set days per month for 24 months (parameterizable)
Battery lifetime up to 11 years
Integrated communication for remote readout or system connection
Self-diagnosis

Contents 3/26
Contents
1General notes ____________________________________________________________4
Other available documents __________________________________________________4
2Safety information ________________________________________________________5
3Technical data ___________________________________________________________7
Dimensions (qp 0,6 –2,5 m³/h)_______________________________________________8
4Installation _____________________________________________________________10
Installation notes _________________________________________________________10
Examples of installation____________________________________________________11
Installation notes for sensor adapter set (sensors directly immersed) ________________12
4.1 Installation for cooling metering ___________________________________________12
5Dimension of electronic unit_______________________________________________13
6Operating elements ______________________________________________________15
6.1 Displaying current meter status ___________________________________________15
User loop “LOOP 0”_______________________________________________________15
Current values “LOOP 1”___________________________________________________16
Previous month's values “LOOP 2“ ___________________________________________16
General / Communication “LOOP 3“ __________________________________________17
Other “LOOP 4“ __________________________________________________________17
6.2 Monthly values ________________________________________________________17
7Resolution of the display__________________________________________________18
8Power supply ___________________________________________________________18
9Communication _________________________________________________________19
Electronic unit interfaces___________________________________________________19
9.1M-Bus_______________________________________________________________19
9.2 Pulse output __________________________________________________________19
9.3 Wireless M-Bus _______________________________________________________20
Predefined data telegrams _________________________________________________20
Data telegram F000 –stationary radio (sending interval 15 min) ____________________20
Data telegram F001 –mobile data reading (sending interval 20 sec, battery lifetime 6 years)
21
Data telegram F002 –mobile data reading (sending interval 34 sec, battery lifetime 11
years) 21
10 Error codes_____________________________________________________________ 22
11 Order codes (type number key) ____________________________________________23
12 Additional ordering information for wM-Bus__________________________________24
13 Pressure loss ___________________________________________________________ 25

General notes 4/26
1 General notes
Note:In the following text, the term meter refers to heat meter and
cooling meter, unless they are otherwise differentiated.
The meter is used as a meter for heating or cooling consumption measure-
ment in systems with water.
The meter consists of a volume measurement unit, two fixed temperature sen-
sors and an electronic unit that calculates the energy consumption from the
volume and temperature difference.
Other available documents
Operating and Installation Instructions T330
Respective module operating and installation instruction
Illustrated catalogue
Datasheet
Additional information is available on request.

Safety information 5/26
2 Safety information
The meter may only be used in building service engineering
systems and only for the applications described.
The local regulations (installation etc.) must be adhered to.
Adhere to the operating conditions according to the dial plate
during use. Non-adherence can cause hazards and the guaran-
tee will expire.
The meter is only suitable for circulating water in heating sys-
tems.
The meter is not suitable for drinking water.
Be aware of sharp edges on thread and measuring tube.
The meter is suitable for circulating water in heating systems.
Adhere to the AGFW requirements regarding circulating water
(FW510).
Do not lift the meter by the electronic unit or by the adapter
plate.
Only personnel, trained in the installation and operation of me-
ters in heating and cooling systems, may install and remove the
meter.
Only install or remove the meter when the pipes are pressure-
less.
After installing the meter, check the leak-tightness of the sys-
tem.
Guarantee and calibration validity will lapse if the calibration
relevant security seal is broken.
Only clean the meter from outside with a soft, lightly wetted
cloth. Do not use any spirit or cleaning solvent.
As far as disposal is concerned, the meter is a waste electronic
appliance in the sense of European Directive 2012/19/EU
(WEEE) and it must not be disposed of as domestic waste. The
relevant national, legal regulations must be observed as the
appliance must be disposed of via the channels provided for this
purpose. The local and currently valid legislation must be ob-
served.
The meter contains lithium batteries. Do not dispose of the
meter and the batteries with domestic waste. Observe the local
stipulations and laws on disposal.

Safety information 6/26
You can return the lithium batteries to the manufacturer for
appropriate disposal following use. When shipping please ob-
serve legal regulations, in particular, those governing the label-
ling and packaging of hazardous goods.
Do not open the batteries. Do not bring batteries into contact
with water or expose to temperatures above 80 °C.
The meter does not have any lightning protection. Ensure light-
ning protection by the house installation.

Technical data 7/26
3 Technical data
General
Measuring accuracy
Class 2 or 3 (EN 1434)
Environment class
A (EN 1434) for indoor installation
Mechanical class
M1 / M2 *)
Electromagnetic class
E1 *)
*) acc. to 2014/32/EU Directive on Measuring Instruments
Ambient humidity
< 93 % relative humidity at 25 °C,
without condensation
Max. height
2000 m above sea level
Storage temperature
-20 … 60 °C
Electronic unit
Ambient temperature
5 … 55 °C
Housing protection rating
IP 54 acc. to EN 60529
Power supply
Battery for 6 or 11 years
Operation threshold for T
0.2 K
Temperature difference T
3 K … 80 K
Temperature measurement range
0 ... 180 °C
LCD
7 digit
Optical interface
Standard, EN 62056-21
Communication
Optional
Separability
Always, cable length 1.5 m
Temperature sensor
Type
Pt500 acc. to EN 60751, not detachable
Connection type
Pt500, 2 wire technology
Cable length
1,5 m
Construction type
Bulb sensor ø 5.2 × 45 mm,
DS direct short, M10 x 27.5 mm
Temperature range
0 ... 105 °C
Volume measurement unit
Protection class
IP 54 acc. to EN 60529, optional IP 65
Mounting place
Hot side / cold side
Installation position
Any, horizontal or vertical
Flow straightening
None
Measuring range
1:100
Temperature range
5 … 105 °C
Maximum overload
qs = 2 x qp, permanent
Nominal pressure
PN16 (1.6 MPa; PS16)
PN25 (2.5 MPa; PS25)
qp
Overall length and connection
m³/h
0.6
110 mm (3/4 '')
190 mm (1 '')
1.5
110 mm (3/4 '')
130 mm (1 '')
190 mm (1 '')
2.5
130 mm (1 '')
190 mm (1 '')

Technical data 8/26
Nominal flowrate
qp
Overall length
Connection
Maximum flowrate
qs
Minimum flowrate
qi
Response
threshold
(variable)
Pressure loss at
qp
Kv-value ati Δp
1 bar
Kv-value at Δp
100 mbar
Pack size (LxBxH)
Weight
m3/h
mm
G
m3/h
l/h
l/h
mbar
m3/h
m3/h
cm
kg
0.6
110
G 3/4
1.2
6
1.2
150
1.5
0.5
15.5 x 13.5 x
12.0
0.8
0.6
190
G1
1.2
6
1.2
150
1.5
0.5
22.5 x 18.5 x
11.3
1.1
1.5
110
G 3/4
3
15
3
150
3.9
1.2
15.5 x 13.5 x
12.0
0.8
1.5
130
G1
3
15
3
160
3.8
1.2
15.5 x 13.5 x
12.0
0.8
1.5
190
G1
3
15
3
160
3.8
1.2
22.5 x 18.5 x
11.3
1.1
2.5
130
G1
5
25
5
200
5.6
1.8
15.5 x 13.5 x
12.0
0.8
2.5
190
G1
5
25
5
210
5.3
1.7
22.5 x 18.5 x
11.3
1.1
Tolerance of pressure loss: +/- 5%
Dimensions (qp 0.6 –2.5 m³/h)
Fig. 1: Overview dimensions overall length 110 mm
Fig. 2: Overview dimensions overall length 130 mm (thread)

Technical data 9/26
Abb. 3: Overview dimensions overall length 190 mm (thread)
Order-
No.
qp
PN
Overall
length
m³/h
bar
mm
UH30-x05
0.6
16
110
UH30-x06
0.6
25
110
UH30-x07
0.6
16
190
UH30-x09
0,6
25
190
UH30-x21
1.5
16
110
UH30-x22
1.5
25
110
UH30-x23
1.5
16
190
UH30-x25
1.5
25
190
UH30-x26
1.5
16
130
UH30-x27
1.5
25
130
UH30-x36
2.5
16
130
UH30-x37
2.5
25
130
UH30-x38
2.5
16
190
UH30-x40
2.5
25
190

Installation 10/26
4 Installation
To install the meter proceed as follows:
Determine the place of installation in line with the inscription on the meter.
Note: For a heat meter the mounting place of the cold side is
equivalent to return and the mounting place hot side is equiv-
alent to flow .
Note: For a cooling meter the mounting place of the hot side is
equivalent to return and the mounting place of the cold side is
equivalent to flow .
Observe the dimensions of the meter and check whether there is sufficient
space available.
Rinse the system thoroughly before installing the meter.
Fit the meter vertically or horizontally between two slide valves so that the
arrow on the housing and the flow direction match. Also observe the instal-
lation situations and the following examples of installation.
Fit the temperature sensors in the same circuit as the meter.
Observe in addition the admixtures.
Seal the temperature sensor and the fittings to protect against manipula-
tion.
If you install the meter for cooling metering, follow the respective notes.
Recommendation: If you are installing several meters, the same installation
conditions must be consistent for all meters.
Installation notes
Note: Observe the local valid installation instructions mounting the
meter.
Inlet or outlet sections are not necessary. If you install the meter in the com-
mon return of two circuits, determine a place of installation with a minimum
distance of 10 × DN from the T-piece. This distance ensures a good thorough
mixing of the different water temperatures. You can install the temperature
sensors in T-pieces, ball valves, directly immersed or in pockets depending on
the version. The temperature sensor ends must reach to at least the middle of
the pipe cross section.
Note: Protect the meter against damage through mechanical
shocks or vibrations at the place of installation.
Note: Ensure the electronic unit is protected against any ingress of
water.

Installation 11/26
Examples of installationYou can install the meter in any position e.g. vertically or horizontally. In order
to avoid accumulation of air and disruption in operation, fit the meter in a verti-
cal installation position and not in the uppermost area of a pipeline.
*This position is not permitted for cold
meters and in cases where moisture can
enter the electronic unit due to conden-
sation (e.g. during an interruption in the
summer).
Fig. 4: Mounting position
Fig. 5: Example for installation
Fig. 6: Installation for circulation with admixing; placement of temperature sensors
Fig. 7: Installation for circulation with throttling configuration (flow sensor in flow direction before control
valve / differential pressure regulating valve)
*

Installation 12/26
Installation notes for sensor adapter set (sensors directly immersed)
A mounting set is included for meters with 5.2 × 45 mm temperature sensor.
With this you can fit the temperature sensor directly immersed into an insert or
a ball valve for example.
1. Install with O-ring at the point of installation with the fit-up aid/pen provided.
2. Place both halves of the plastic bolting round the 3 notches of the tempera-
ture sensor.
3. Press the bolting together and screw the bolting hand tight into the point of
installation until it comes to a stop (tightening torque 3 ... 5 Nm).
Fig. 8: Mounting adapter set
4.1 Installation for cooling metering
Observe the following installation instructions to avoid condensation:
Mount the cooling meter so that the black covering on the measuring sec-
tion points sideward or downwards.
Mount the electronic unit separated from the volume measuring unit
e. g. on the wall.
Form with the connected cables a loop downwards.
Mount the protection pocket so that the temperature sensor is oriented ver-
tically downwards or horizontally.
Mount the temperature sensor horizontally or vertically in the pipe from be-
low.
Transducer cover
Fig. 9: Recommended installation orientation for cooling measuring

Dimension of electronic unit 13/26
5 Dimension of electronic unit
Fig. 10: Electronic unit
Fig. 11: Wall adapter (view from above and side)
Fig. 12: Maximum screw head height (if using the wall bracket)

Dimension of electronic unit 14/26
Fig. 13: Wall mounting

Operating elements 15/26
6 Operating elements
Fig. 14: LCD
No.
Description
1
Identification previous year value
2
Previous year value
3
Maxima
4
Previous month value
5
Identification previous month value
6
Activity display at flow
7
Calibrated value
6.1 Displaying current meter status
The meter displays the current meter status in kWh, MWh, MJ or GJ.
Note: In order to prevent reading errors, the decimal places of
the values displayed are marked with a frame.
Note: Calibrated values can be recognized by an additionally
displayed star symbol.
Note: Both display range and data displayed can differ from
the description depending on the appliance parameterization.
Certain button functions can also be blocked.
User loop “LOOP 0”
User loop
Energy quantity
Volume
Segment test
In case of error: error code

Operating elements 16/26
Current values “LOOP 1”
Current values
Current flow
Current heat power
Current temperature hot side / cold side alternating in 2 s
cycles
Temperature difference
Operating time
Missing time
Time with flow
Previous month's values “LOOP 2“
Monthly values
Log date
Energy quantity and volume on set day
Missing time on set day
Max. flow in 2 s cycles with date stamp
Max. power in 2 s cycles with date stamp
Max. temperature hot side in 2 s cycles with date stamp
Max. temperature cold side in 2 s cycles with date stamp

Operating elements 17/26
General / Communication “LOOP 3“
General / Communication
Device number, 7-digit
Optional interface
Primary address (only for M-Bus)
Secondary address
7-digit - for M-Bus
Yearly set day
Monthly set day
Firmware version
CRC-Code
Other “LOOP 4“
Other
Date
Time
Code entry for test / para operation
6.2 Monthly values
The meter stores the following values for 24 months on the monthly set day
Missing time
Volume
Energy
and maxima with date stamp for
Flow
Power
Temperature hot side
Temperature cold side
The monthly values can be read via optical interface.
Note: Central European Time (CET) applies as the standard time.
During summer time the storage takes place at the corresponding
times.

Resolution of the display 18/26
7 Resolution of the display
8 Power supply
The meter is according to the configuration equipped with 1 –3 lithium batter-
ies.
Options:
6 years battery
11 years battery
kWh
MWh
MJ
GJ
m³/h
m³
1.5 2.5
0.001 MWh
1 kWh
1 MJ
0.001 GJ
Nominal flow rate in m³/h
0.01 m³
0.001 m³/h
0.6

Communication 19/26
9 Communication
Electronic unit interfaces
The meter is equipped with an optical interface in accordance with EN 62056-
21:2002 as standard.
Note: You can find further information in their respective documen-
tation.
9.1 M-Bus If the meter is equipped with the option M-Bus, it is supplied with a 2-wire ca-
ble which you can extend by fitting a junction box.
Standard EN 13757-2 and -3
Reading interval >1 min @ 2400 baud
Note: Frequent turning on and off of the M-Bus voltage can lead to
reduction of battery lifetime.
9.2 Pulse output
The pulse output permits the transmission of energy or volume equivalent
pulses.
Two channels are available. Their functions can be parameterized with the
service software or can be adapted in the “Para menu” of the meter.
Available are standard pulses or high-definition pulses.
The pulse duration is identical for channel 1 and channel 2.
Cable labelling
passive pulse output
Cable
1.5 m; 4-wired, LL84201 4xAWG28 /
0.2 mm²
Cable diameter
4 mm
Output type
open drain
Voltage
max. 30 V
Current
max. 30 mA
Dielectric strength
500 Veff against ground
Classification
OB/OC (acc. to EN 1434-2)
ON/OFF resistance
<74 Ω / 6 MΩ
Output connection

Communication 20/26
9.3 Wireless M-Bus
The wireless M-Bus function enables the meter to communicate with a sta-
tionary unit (e. g. radio concentrator, smartphone with radio adapter) using
868 MHz radio frequency (unlicensed).
The function supports the OMS1)-compliant data transfer.
Standard
Open Metering System Specification
(Issue 3.0.1); EN 13757-4
Frequency
868.95 MHz (min. 868.90 MHz to
max. 869.00 MHz)
Transmission power
Min. 3.16 mW (5 dBm) to
max. 25 mW (13.9 dBm)
Range2)
- Free field
Up to max. 400 m
Power supply
max. 3 batteries type AA
Sending interval
- Mobile data reading
- Stationary data reading
- User defined data reading
Acc. to configuration 20 –34 sec
15 min
Acc. to telegram length 12 –900 sec
1) Open Metering System
2) May vary depending on terrain and building structure
Predefined data telegrams
Note: Please tell us if encryption needs to be set at factory. The
unique encryption key for every meter will be created and you will
get a file by email (meter number <> encryption key).
Data telegram F000 –stationary radio (sending interval 15 min)
Following data are available by default for data reading:
Current energy
Current volume
Current flowrate
Current power
Current temperature hot side
Current temperature cold side
Error (manufacturer specific)
Current timestamp (type I)
Table of contents
Other Ista Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Kobold
Kobold KSM-**001 operating instructions

Fieldpiece
Fieldpiece ASX14 Operator's manual

Lutron Electronics
Lutron Electronics SP-8001 Operation manual

Flex
Flex ALR 512 operating instructions

Baumer
Baumer HUBNER POG 10 + ESL Mounting and operating instructions

Tektronix
Tektronix KEITHLEY 8606 instruction sheet