ITE K-225 User manual

r
*
.
7
r
-
.
••
>
IB
-
5721
>
WARNING
:
KEEP
HANDS
CLEAR
OF
ALL
OPERATING
PARTS
.
THE
CLOSING
SPRINGS
ON
ELECTRICALLY
OPERATED
CIRCUIT
BREAKERS
ARE
CHARGED
WHEN
THE
CIRCUIT
BREAKER
IS
IN
THE
OPEN
POSITION
.
DE
-
ENERGIZE
THE
PRIMARY
CIRCUIT
BEFORE
MAKING
ANY
INSPECTIONS
,
ADJUSTMENTS
,
OR
REPLACEMENT
OF
PARTS
.
Discharging
Closing
Springs
The
closing
springs
of
manually
operated
circuit
breakers
are
discharged
by
each
closing
operation
.
The
closing
springs
of
electrically
operated
circuit
breakers
are
charged
whenever
the
con
-
tacts
are
open
,
the
charging
power
switch
is
''
ON
"
,
and
control
power
is
available
.
Two
methods
of
discharging
the
closing
springs
are
necessary
;
one
,
for
the
circuit
breaker
when
the
control
circuit
is
energized
;
and
the
second
,
when
the
control
circuit
is
de
-
energized
.
With
the
control
circuit
energized
,
discharge
the
closing
springs
as
follows
:
1
.
Close
the
circuit
breaker
with
the
local
"
CLOSE
"
'
button
(
4
,
Fig
.
9
)
.
2
.
.
Place
charging
power
switch
(
9
,
Fig
.
9
)
in
the
"
OFF
"
position
.
3
.
Open
the
circuit
breaker
by
means
of
the
manual
"
TRIP
"
button
(
5
,
Fig
.
9
)
.
4
.
The
closing
springs
are
now
discharged
.
If
the
control
circuit
is
de
-
energized
,
discharge
the
closing
springs
as
follows
:
1
.
Lift
lever
(
3
,
Fig
.
6
)
on
the
control
device
to
manually
release
latch
and
close
the
circuit
breaker
.
2
.
Open
the
circuit
breaker
by
means
of
the
manual
"
TRIP
"
button
(
5
,
Fig
.
9
)
.
3
.
The
closing
springs
are
now
discharged
.
4
.
Place
charging
power
switch
(
9
,
Fig
.
9
)
in
the
"
OFF
"
position
.
<
cc
CC
<
c
o
c
:
c
c
X
tx
1
Spring
Char
?
*
Indicator
2
Racking
Shutter
3
Visual
Indicator
4
Electric
Cloaa
Button
3
.
MTrip
Button
6
Duet
Plata
7
Eacutchaon
8
Txx
-
king
Hasp
9
Charging
Power
Switch
10
Automatic
Trip
r
-
i
.
Fig
.
9
—
Front
View
of
Escutcheon
Assembly
for
Electrically
Operated
Circuit
Breaker
RENEWAL
PARTS
To
order
renewal
parts
,
address
the
nearest
Sales
Office
of
the
I
-
T
-
E
Circuit
Breaker
Company
.
Specify
the
complete
of
parts
,
and
quantity
required
.
To
facilitate
the
ordering
of
renewal
parts
,
a
copy
of
RP
-
5801
will
be
furnished
on
request
.
eplate
data
,
description
nam
•
v
These
instructions
do
not
purport
to
cover
all
details
or
variations
in
equipment
nor
to
provide
for
every
possible
contingency
to
be
met
in
connection
with
installation
,
operation
,
or
maintenance
.
Should
further
ihformation
be
desired
or
should
particular
problems
arise
which
are
not
covered
sufficiently
for
the
purchaser
'
s
purposes
,
the
matter
should
be
referred
to
the
/
-
T
-
£
Circuit
Breaker
Company
.
1
s
.
'
y
&
•
•
vi
v
*
'
•
>
.
•
General
Offices
and
Factory
:
PHILADELPHIA
7900
Hamilton
Street
,
Phila
.
30
,
Pa
.
I
7
.
U
4
A
\
*
r
Courtesy of NationalSwitchgear.com

(
ffl
)
IB
-
5721
TABLE
II
—
Methods
of
Operation
Manually
Operated
Breakers
Electrically
Operated
Breakers
Position
Position
•
8
8
Operation
Operation
and
Method
and
1
a
8
8
Method
1
1
Q
§
s
J
a
1
S
o
o
OO
H
E
-
*
CHARGING
AND
CLOSING
:
1
.
Manual
Closing
Handle
TRIPPING
:
1
.
Electrical
(
If
shunt
trip
or
under
-
voltage
trip
is
provided
)
—
Remote
"
TRIP
"
switch
.
2
.
Manual
—
Manual
"
TRIP
"
button
CHARGING
:
1
.
Electrical
—
®
Motor
2
.
Manual
—
^
Removable
maintenance
handle
CLOSING
:
1
PI
Apfnoal
—
’
a
.
Remote
"
CLOSE
"
switch
b
.
Local
"
CLOSE
"
button
2
.
Manual
—
®
Lever
on
control
device
TRIPPING
:
1
.
Electrical
—
Remote
"
TRIP
"
switch
2
.
Manual
—
Manual
"
TRIP
"
button
x
z
z
©
X
X
z
X
z
zz
z
z
z
z
©
zz
X
X
X
X
z
©
Operation
requires
compartment
door
to
be
open
and
therefore
is
not
recommended
when
the
circuit
breaker
is
energized
.
O
The
charging
power
switch
(
9
,
Fig
.
9
)
must
be
in
the
"
ON
"
position
.
®
Place
maintenance
handle
as
shown
in
Fig
.
6
,
and
operate
with
a
ratchet
type
motion
®
Lift
lever
(
3
,
Fig
.
6
)
,
at
front
-
right
of
control
device
,
to
manually
release
latch
and
close
circuit
breaker
.
o
i
r
-
*
m
3
'
O
a
*
4
*
¥
%
<
o
CO
^
7
o
co
co
6
*
°
Q
M
o
/
A
(
X
,
I
J
i
X
"
A
"
•
a
*
0
T
IHHMTCMAMCe
V
.
POStTlOH
or
MMHTCMMCe
HAMDLf
TO
W
>
C
MOTOK
CftAMK
AIM
I
Manual
Cloaing
Hanoi
*
5
Dust
Plata
2
Racking
Similar
1
Eatchat
Wheel
.
2
Pawl
Carriax
3
Motor
Crank
Arm
4
Rem
or
able
Maintananca
Handle
5
Control
Device
6
Escutcheon
3
Visual
7
Locking
Hasp
'
^
4
Manual
Trip
Button
8
A
Fig
.
7
—
Method
of
Applying
Maintenance
Handle
for
Charging
Closing
Springs
Fig
.
8
—
Front
View
of
Escutcheon
Assembly
for
Manually
Operated
Circuit
Breaker
7
Courtesy of NationalSwitchgear.com

w
IB
-
5721
5
.
Insert
racking
handle
and
crank
counter
-
clockwise
as
far
as
the
stops
will
allow
.
6
.
Pull
circuit
breaker
forward
until
tracks
(
4
,
Fig
.
3
)
are
in
the
fully
extended
and
latched
position
.
7
.
Using
a
lifting
yoke
,
just
pick
up
the
circuit
breaker
weight
.
8
.
With
a
positive
pull
,
release
positioning
pins
from
cut
-
out
sections
of
the
tracks
.
9
.
Remove
circuit
breaker
from
tracks
by
means
of
lifting
yoke
.
10
.
Release
latch
(
3
,
Fig
.
3
)
on
each
track
,
push
tracks
into
the
compartment
,
and
close
com
-
partment
door
.
8
.
Remove
racking
crank
,
place
charging
power
switch
(
electrically
operated
circuit
breakers
only
)
in
the
"
ON
"
position
,
energize
the
pri
-
mary
circuit
,
and
the
circuit
breaker
is
ready
for
service
.
REMOVING
THE
CIRCUIT
BREAKER
To
move
the
circuit
breaker
to
the
"
TEST
'
posi
-
tion
or
to
remove
it
from
the
compartment
,
proceed
as
follows
:
1
.
With
the
compartment
door
closed
,
trip
the
circuit
breaker
by
means
of
the
remote
mounted
control
switch
or
manual
"
TRIP
"
button
(
4
,
Fig
.
8
)
on
the
escutcheon
.
2
.
Lift
racking
shutter
(
2
,
Fig
.
8
)
,
insert
racking
crank
and
turn
counter
-
clockwise
until
posi
-
tion
indicator
(
6
,
Fig
.
3
)
on
the
right
-
hand
side
of
the
escutcheon
shows
"
TEST
"
posi
-
tion
.
(
NOTE
:
The
circuit
breaker
may
be
tested
in
this
position
—
primary
contacts
are
disconnected
and
the
control
contacts
are
connected
.
)
3
.
Continue
turning
the
racking
crank
counter
-
clockwise
until
the
position
indicator
(
6
,
Fig
.
3
)
on
the
right
-
hand
side
of
the
escutcheon
shows
"
DISCONNECTED
"
position
.
4
.
Open
compartment
door
and
discharge
clos
-
ing
springs
(
electrically
operated
breakers
only
)
by
lifting
the
emergency
close
lever
(
3
,
Fig
.
6
)
on
the
control
device
and
then
pushing
the
manual
trip
button
on
the
escutcheon
.
Place
charging
power
switch
(
9
,
Fig
.
9
)
in
the
"
OFF
"
position
.
OPERATION
The
circuit
breakers
are
designed
for
either
manual
or
electrical
operation
.
Electrically
oper
-
ated
circuit
breakers
may
be
closed
manually
for
maintenance
purposes
by
using
the
maintenance
handle
(
2
,
Fig
.
6
)
to
manually
charge
the
closing
springs
,
and
the
emergency
close
lever
(
3
,
Fig
.
6
)
to
close
the
circuit
breaker
.
EMERGENCY
OPERATION
Electrically
operated
circuit
breakers
may
be
closed
manually
by
a
removable
maintenance
handle
(
4
,
Fig
.
7
)
for
emergency
operation
.
The
removable
maintenance
handle
(
4
)
is
first
positioned
in
two
slots
in
the
pawl
carrier
{
2
)
.
The
handle
is
then
raised
and
lowered
in
a
~
pumping
motion
until
the
pawl
carrier
(
2
)
no
longer
rotates
the
ratchet
wheel
(
1
)
.
The
breaker
closing
springs
now
fully
charged
are
ready
for
a
closing
opera
-
tion
which
is
done
by
raising
the
emergency
close
lever
(
6
)
on
the
control
device
(
5
)
.
The
motor
crank
arm
(
3
)
will
stop
occasionally
in
such
a
position
as
to
prevent
a
full
racking
stroke
.
Should
this
happen
,
the
motor
crank
aim
(
3
)
will
have
to
be
rotated
manually
.
Insert
the
pointed
end
of
the
handle
"
A
"
through
the
lower
slot
of
pawl
carrier
(
2
)
and
against
the
motor
crank
arm
(
3
)
.
Hook
the
handle
on
slot
of
pawl
carrier
at
"
B
"
and
bear
down
so
as
to
force
the
motor
crank
arm
(
3
)
to
move
.
The
circuit
breaker
closing
springs
may
then
be
charged
as
described
in
paragraph
above
.
Refer
to
TABLE
II
for
the
possible
means
of
charging
,
closing
,
and
tripping
the
circuit
breaker
.
2
3
O
co
o
o
*
6
-
a
a
,
MAINTENANCE
It
is
recommended
that
a
maintenance
program
be
established
for
inspecting
the
circuit
breaker
at
least
once
every
six
months
and
,
as
soon
as
possible
,
after
a
short
circuit
or
severe
overload
interruption
.
For
maintenance
instructions
,
request
copies
of
IB
-
5724
from
the
nearest
Sales
Office
of
the
I
-
T
-
E
Circuit
Breaker
Company
.
1
Escutcheon
AIMMHLY
2
Removable
Maintenance
Handle
3
Emergency
Close
Lever
4
Motor
5
Carrier
6
Qvorcurmnt
Trip
Device
7
Control
Device
Fig
.
6
—
Portia
/
Bottom
Viow
of
Electrically
Operated
Circuit
Breaker
,
Showing
Removable
Maintenance
Handle
Positioned
for
Closing
6
Courtesy of NationalSwitchgear.com

w
IB
-
5721
OVERCURRENT
TRIP
DEVICES
Type
OD
-
3
Dual
Overcurrent
Trip
Device
The
type
OD
-
3
overcurrent
trip
device
,
for
gen
-
eral
purpose
applications
,
provides
long
-
time
delay
tripping
on
moderate
overcurrents
which
are
above
the
long
-
time
pickup
setting
;
and
instantaneous
tripping
on
fault
currents
above
the
instantaneous
trip
setting
.
This
device
must
be
properly
set
to
provide
adequate
protection
for
an
electrical
sys
-
tem
.
Three
adjustment
screws
(
See
Fig
.
4
)
on
the
bottom
of
the
device
provide
independent
control
of
the
long
-
time
pickup
,
instantaneous
pickup
,
and
amount
of
time
delay
.
The
nameplate
of
this
device
shows
the
settings
of
these
adjustments
and
the
range
of
settings
which
are
available
.
For
informa
-
tion
on
the
time
-
current
characteristics
of
this
device
,
request
a
copy
of
TD
-
5523
.
will
automatically
release
the
two
latches
(
3
,
Fig
.
3
)
.
This
allows
the
circuit
breaker
to
move
toward
the
compartment
until
the
racking
cams
(
2
,
Fig
.
3
)
stop
against
their
guides
on
the
cradle
(
1
,
Fig
.
3
)
.
5
.
Lift
shutter
(
9
,
Fig
.
3
)
covering
the
racking
opening
,
insert
racking
crank
,
and
turn
crank
clockwise
,
pass
through
the
"
DISCON
-
NECTED
"
position
,
until
the
position
indica
-
tor
on
the
cradle
shows
'
TEST
"
position
.
6
.
Perform
all
steps
in
TABLE
I
,
A
or
B
.
TABLE
I
—
Pre
-
Operational
Inspection
A
—
Electrically
Operated
Breakers
a
.
Manually
reset
automatic
trip
indicator
(
7
,
Fig
.
3
)
,
if
required
.
b
.
Charge
closing
power
springs
by
means
of
removable
maintenance
handle
(
2
,
Fig
.
6
)
.
(
See
NOTE
under
section
OPERATION
)
.
Close
circuit
breaker
by
operating
lever
(
3
,
Fig
.
6
)
on
control
device
.
Trip
by
push
-
ing
manual
"
TRIP
1
button
on
escutcheon
.
c
.
Refer
to
instruction
card
on
type
OD
overcurrent
trip
device
.
-
d
.
Megger
out
all
circuits
.
e
.
Energize
the
control
circuit
,
turn
charging
power
switch
(
10
,
Fig
.
1
)
to
"
ON
"
,
and
elec
-
trically
close
and
manually
trip
the
circuit
breaker
from
the
push
buttons
on
the
escutcheon
.
f
.
Close
and
trip
the
circuit
breaker
from
the
remote
mounted
control
switch
,
and
check
each
auxiliary
device
,
such
as
under
-
voltage
trip
,
for
proper
operation
.
Type
OD
-
4
Dual
Selective
Overcurrent
Trip
Device
The
type
OD
-
4
overcurrent
trip
device
,
for
selec
-
tive
tripping
applications
,
provides
long
-
time
delay
and
short
-
time
delay
tripping
.
Independent
adjust
-
ment
(
See
Fig
.
5
)
of
both
pickup
and
time
delay
is
provided
for
both
types
of
tripping
.
The
nameplate
of
this
device
shows
the
settings
which
are
avail
-
able
.
For
information
on
the
tune
-
current
character
-
istics
of
this
device
,
request
a
copy
of
TD
-
5524
-
A
,
B
,
or
C
for
the
minimum
,
intermediate
,
and
maxi
-
mum
long
-
time
bands
,
respectively
.
INSTALLATION
CAUTION
:
FOR
INITIAL
INSTALLATION
,
DE
-
ENERGIZE
THE
PRIMARY
AND
CONTROL
CIR
-
CUITS
BEFORE
INSERTING
THE
CIRCUIT
BREAKER
INTO
THE
'
COMPARTMENT
.
B
—
Manually
Operated
Breakers
INSERTING
CIRCUIT
BREAKER
To
insert
the
circuit
breaker
into
its
compart
-
ment
,
proceed
as
described
below
:
1
.
The
circuit
breaker
must
be
in
the
"
OPEN
"
position
,
the
racking
crank
turned
in
the
counter
-
clockwise
direction
fully
against
its
stop
,
and
the
charging
power
switch
(
10
,
Fig
.
1
)
(
electrically
operated
circuit
breakers
only
)
in
the
"
OFF
"
position
.
2
.
Open
the
compartment
door
and
pull
out
the
right
-
hand
and
left
-
hand
tracks
(
4
,
Fig
.
3
)
to
the
fully
extended
and
latched
position
.
3
.
Using
a
lifting
yoke
,
lower
the
circuit
breaker
so
that
the
positioning
pins
(
5
,
Fig
.
3
)
(
two
each
side
of
circuit
breaker
)
rest
in
the
cut
-
out
sections
of
each
track
(
4
,
Fig
.
3
)
.
4
.
Remove
the
lifting
yoke
and
push
the
circuit
breaker
toward
the
compartment
The
circuit
breaker
will
slide
in
the
cut
-
out
sections
of
the
tracks
until
the
positioning
pins
reach
the
end
of
the
cutouts
.
An
additional
positive
push
a
.
Manually
reset
automatic
trip
indicator
(
7
,
Fig
.
3
)
,
if
required
.
b
.
Close
circuit
breaker
by
means
of
manual
closing
handle
(
10
,
Fig
.
3
)
.
Trip
by
pushing
manual
"
TRIP
"
button
on
escutcheon
.
c
.
Refer
to
instruction
card
on
type
OD
over
-
current
trip
device
d
.
Megger
out
all
circuits
.
e
.
If
the
circuit
breaker
has
a
shunt
trip
device
,
energize
the
control
circuit
and
manually
close
and
electrically
trip
the
circuit
breaker
from
the
remote
mounted
"
TRIP
"
switch
.
.
r
7
.
With
the
circuit
breaker
in
the
"
OPEN
"
posi
-
tion
and
the
charging
power
switch
(
10
,
Fig
.
1
)
in
the
"
OFF
'
position
,
insert
the
racking
crank
and
turn
clockwise
until
the
position
indicator
on
the
cradle
shows
"
CONNECTED
"
position
.
5
Courtesy of NationalSwitchgear.com

w
IB
-
5721
r
co
a
>
04
CD
03
6
o
04
2
Ranking
Cam
Assembly
3
Latch
4
Track
5
Pin
7
Automatic
Trip
Indicator
8
Locking
Hasp
9
Racking
Shatter
10
Manaal
Closing
Handle
CD
a
CO
CO
CO
CO
Hg
.
3
—
Type
AC
-
600
Circuit
Breaker
on
Tracks
Ready
to
be
Placed
in
Compartment
di
di
6
»
6
0
"
0
o
\
o
H
1
LONG
TIME
DELAY
PICKUP
ADJUSTMENT
SHORT
TIME
DELAY
PICKUP
ADJUSTMENT
-
LONG
TIME
DELAY
PICKUP
ADJUSTMENT
LONG
TIME
DELAY
ADJUSTMENT
INSTANTANEOUS
ADJUSTMENT
-
SHORT
TIME
OELAY
ADJUSTMENT
LONG
TIME
DELAY
ADJUSTMENT
V
%
:
-
*
Fig
.
4
—
Type
00
-
3
Overcurrent
Trip
Device
,
Partial
View
Showing
Adjustable
Features
Fig
.
5
—
Type
OD
-
4
Overcurrent
Trip
Device
,
Partial
View
Showing
Adjustable
Features
4
Courtesy of NationalSwitchgear.com

w
IB
-
5721
INSTRUCTIONS
FOR
t
TYPE
K
-
225
,
K
-
600
AND
K
-
1600
CIRCUIT
BREAKERS
DRAWOUT
MOUNTED
The
control
device
contains
three
electrical
ponents
,
the
limit
switch
(
LS
)
,
the
lockout
relay
(
52
Y
)
,
and
the
latch
release
relay
(
52
X
)
.
The
schematic
diagram
of
the
closing
circuit
(
Fig
.
2
)
clearly
illustrates
the
function
of
thi
.
g
device
.
In
addition
to
its
electrical
functions
,
the
base
of
the
device
provides
a
terminal
block
for
the
circuit
breaker
wiring
.
INTRODUCTION
com
-
These
instructions
apply
to
the
type
K
-
225
,
K
-
600
,
and
K
-
1600
circuit
breakers
(
K
-
Line
)
.
These
circuit
breakers
can
be
furnished
as
a
two
-
pole
or
three
-
pole
circuit
breaker
having
either
a
manually
or
electrically
operated
mechanism
.
A
three
-
pole
manually
operated
circuit
breaker
is
shown
on
the
cover
,
and
an
electrically
operated
circuit
breaker
is
shown
in
Fig
.
1
.
Two
-
pole
construction
is
similar
except
that
the
center
pole
is
omitted
.
RACKING
MECHANISM
The
racking
mechanism
may
be
used
to
move
the
circuit
breaker
to
any
one
of
its
three
positions
(
"
CONNECTED
,
"
"
TEST
"
or
"
DISCONNECTED
"
)
.
All
of
these
positions
are
attainable
with
the
cubicle
door
closed
.
The
racking
shutter
(
15
,
Fig
.
1
)
,
which
must
be
lifted
to
gain
access
to
the
rack
-
ing
mechanism
,
is
interlocked
with
the
circuit
breaker
so
that
the
circuit
breaker
contacts
must
be
open
before
the
shutter
may
be
lifted
to
rack
the
circuit
breaker
to
another
position
.
The
circuit
breaker
can
not
be
closed
when
the
shutter
is
open
.
The
circuit
breaker
may
be
padlocked
open
by
means
of
the
locking
hasp
.
This
automatically
locks
the
racking
mechanism
.
With
*
the
"
TRIP
"
button
(
13
,
Fig
.
1
)
depressed
,
the
locking
hasp
(
11
,
Fig
.
1
)
may
be
pulled
outward
,
accommodat
-
ing
from
one
to
three
padlocks
,
when
the
shutter
is
closed
and
the
circuit
breaker
is
tripped
.
The
^
hutter
can
not
be
lifted
and
the
breaker
contacts
ilhn
not
be
closed
when
the
locking
hasp
is
re
-
strained
by
one
or
more
padlocks
.
TRANSPORTATION
DAMAGE
If
damage
or
loss
is
evident
,
file
a
claim
at
once
with
the
carrier
and
promptly
notify
the
I
-
T
-
E
Circuit
Breaker
Company
.
rv
STORAGE
It
is
recommended
that
the
circuit
breakers
be
installed
in
their
permanent
location
even
though
they
may
not
be
placed
in
service
for
some
time
.
The
circuit
breaker
may
be
stored
and
locked
in
the
"
DISCONNECTED
"
position
in
its
compart
-
ment
with
the
door
closed
.
Both
the
primary
and
control
separable
contacts
are
disconnected
in
this
position
.
If
the
circuit
breakers
cannot
be
installed
in
their
permanent
location
,
they
can
be
stored
in
their
shipping
cartons
as
protection
against
dust
,
dirt
,
and
damage
.
AUTOMATIC
TRIP
INDICATOR
(
Alarm
and
Lockout
)
The
automatic
trip
indicator
(
9
,
Fig
.
1
)
extends
through
the
escutcheon
and
provides
a
positive
indication
when
overcurrent
or
undervoltage
trip
-
ping
has
occurred
.
The
indicator
should
be
manu
-
ally
reset
after
each
indication
by
pushing
the
indicator
to
its
normal
position
.
The
alarm
con
-
tacts
and
/
or
lockout
attachment
,
if
provided
,
are
manually
reset
by
this
indicator
.
Reset
is
manda
-
tory
if
these
features
are
provided
.
GENERAL
INFORMATION
The
following
sections
are
pertinent
to
the
basic
.
operation
of
the
circuit
breaker
.
OPERATING
MECHANISM
Two
types
of
operating
mechanism
are
available
;
either
the
manually
operated
mechanism
as
shown
on
the
circuit
breaker
in
the
cover
photo
or
the
electrically
operated
mechanism
as
shown
on
the
circuit
breaker
in
Fig
.
1
.
The
manually
and
elec
-
trically
operated
mechanism
are
interchangeable
on
circuit
breakers
having
the
same
designation
.
"
type
"
PADLOCKING
DEVICE
The
padlocking
device
(
11
,
Fig
.
1
)
,
when
with
-
drawn
and
padlocked
,
prevents
unauthorized
closing
of
the
circuit
breaker
.
To
withdraw
the
locking
hasp
,
the
manual
trip
button
(
13
,
Fig
.
1
)
must
be
depressed
.
The
locking
hasp
will
accom
-
modate
from
one
to
three
padlocks
.
CONTROL
DEVICE
The
control
device
(
7
,
Fig
.
6
)
.
is
furnished
on
electrically
operated
circuit
breakers
.
The
device
is
mounted
below
and
to
the
left
of
the
mechanism
.
*
3
Courtesy of NationalSwitchgear.com

w
IB
-
5721
16
CO
CM
(
O
CD
CM
15
6
o
ft
*
14
13
12
V
9
Automatic
Trip
Indicator
Arc
Canto
10
Charging
Power
Switch
Auxiliary
Switch
11
Locking
Ha
«
p
Primary
Separable
Contact
12
Electric
QOM
Button
Racking
Cam
Assembly
13
Mannal
Trip
Button
Oxarcnrrent
Trip
Doric
•
14
Viaoal
Indicator
Pori
tinning
Pin
13
Racking
Shuttar
Motor
16
Spring
Charge
Indicator
Eacatchaoa
Aaaambly
Fig
.
1
—
Type
K
-
600
Electrically
Operated
Circuit
Breaker
as
CD
t
90
«
£
2
CM
Q
•
LEGEND
M
—
Charging
Motor
CPS
—
Charging
Pownr
Switch
LS
/
1
,
LS
/
3
—
Limit
Switch
Contact
*
Posed
Whan
Springs
am
Discharged
,
Opan
Whan
Springs
am
Charged
.
LS
/
2
—
Limit
Switch
Contact
Opan
Whan
Springs
am
Discharged
,
Closed
When
Springs
am
Charged
.
32
/
b
—
Contact
Opan
Whan
Breaker
is
Closed
S
2
X
—
Latch
Release
Coil
52
Y
—
Control
Coil
52
T
/
1
—
Lockout
Relay
Contact
,
Normally
Open
52
T
/
2
—
Lockout
Relay
Contact
,
Normally
Closed
JL
REMOTE
T
CLOSE
<
»
>
o
O
52
Y
LS
<
>
2
I
JL
LS
T
2
52
Y
±
LS
CPS
-
Z
3
I
52
52
b
b
©
©
©
V
,
-
7
Fig
.
2
—
Schematic
Diagram
of
Closing
Circuit
2
Courtesy of NationalSwitchgear.com
This manual suits for next models
2
Table of contents
Other ITE Circuit Breaker manuals
Popular Circuit Breaker manuals by other brands

GE
GE AM-13.8-500-5C INSTRUCTIONS AND RECOMMENDED PARTS FOR MAINTENANCE

LEGRAND
LEGRAND DMX-SP 4000 manual

Siemens
Siemens SIMATIC PN Installation and operating manual

HUYU
HUYU H8M Series Installation and operation instruction

Allen-Bradley
Allen-Bradley 140G-R Series Getting started

Siemens
Siemens 3VL9431-6 30 Series operating instructions