Jandy POOL LINK User manual

Installation Data
Installation Manual
WARNING
FOR YOUR SAFETY - This product must be installed and serviced by a professional pool/
spa service technician. The procedures in this manual must be followed exactly. Failure to
follow warning notices and instructions may result in property damage, serious injury, or
death.
H0279900-
POOL LINK
Dual Timer Module
Control System


Page 3
Table of Contents
Section 1. Important Safety Instructions...........4
Section 2. System Overview .............................6
2.1 Package Contents............................6
2.2 System Component Specifications
and Dimensions...............................7
Section 3. Installation........................................8
3.1 Pool Link Control System
Mounting.........................................8
3.2 Attach Labels..................................8
3.2.1 Wiring Diagram Label..................8
3.2.2 "What The Switches Do" Label ...8
3.3 High Voltage Wiring .......................8
3.3.1 System Power...............................8
3.3.2 3HP (Standard) Relays.................8
3.3.3 Bonding the Pool Link .................8
3.4 Low Voltage Wiring .....................10
3.4.1 Wire Relays to Printed
Circuit Board................................10
3.4.2 In-Floor Cleaning System ............10
3.4.3 Wire Time Clock to Printed
Circuit Board................................10
3.4.4 Connect Heater to Printed
Circuit Board................................10
3.4.5 Connect Freeze Protection Sensor
to Printed Circuit Board ...............11
3.4.6 Set Jumpers and Diode.................11
3.4.7 Connect System Power to
Printed Circuit Board ................... 12
Section 4. System Startup..................................13
4.1 Set Time Clocks and Test
Equipment.......................................13
4.2 Single-Speed Filtration Pump Plus
Cleaner Booster Pump Operation...13
4.3 Two-Speed Filter Pump Operation .13
4.4 Heater Cool Down..........................13
4.5 Freeze Protection ............................13
Warranty ..........................................................16
DATE OF INSTALLATION
INSTALLER INFORMATION
INITIAL PRESSURE GAUGE READING (WITH CLEAN FILTER)
PUMP MODEL HORSEPOWER
FILTER MODEL SERIAL NUMBER
CONTROL PANEL MODEL SERIAL NUMBER
NOTES:
EQUIPMENT INFORMATION RECORD

Page 4
Section 1. Important Safety Instructions
READ AND FOLLOW ALL INSTRUCTIONS
Lire la notice technique.
All electrical work must be performed by a licensed electrician and conform to all national, state, and
local codes. When installing and using this electrical equipment, basic safety precautions should always be
followed, including the following:
WARNING
Prolonged immersion in hot water may induce hyperthermia. Hyperthermia occurs when the internal temperature
of the body reaches a level several degrees above the normal body temperature of 98.6° F. The symptoms of
hyperthermia include dizziness, fainting, drowsiness, lethargy, and an increase in the internal temperature of the
body. The effects of hyperthermia include: 1) unawareness of impending danger; 2) failure to perceive heat; 3)
failure to recognize the need to exit spa; 4) physical inability to exit spa; 5) fetal damage in pregnant women; 6)
unconsciousness resulting in a danger of drowning.
DANGER
To reduce the risk of injury, do not remove the suction fittings of your spa or hot tub. Never operate a spa or hot
tub if the suction fittings are broken or missing. Never replace a suction fitting with one rated less than the flow rate
marked on the equipment assembly.
WARNING
To Reduce the Risk of Injury -
a) The water in a spa should never exceed 104°F (40°C). Water temperatures between 100°F (38°C) and
104°F (40°C) are considered safe for a healthy adult. Lower water temperatures are recommended for young
children and when spa use exceeds 10 minutes.
b) Since excessive water temperatures have a high potential for causing fetal damage during the early months of
pregnancy, pregnant or possibly pregnant women should limit spa water temperatures to 100°F (38°C).
c) Before entering a spa or hot tub, the user should measure the water temperature with an accurate
thermometer since the tolerance of water temperature-regulating devices varies.
d) The use of alcohol, drugs, or medication before or during spa or hot tub use may lead to unconsciousness with
the possibility of drowning.
e) Obese persons and persons with a history of heart disease, low or high blood pressure, circulatory system
problems, or diabetes should consult a physician before using a spa.
f) Persons using medication should consult a physician before using a spa or hot tub since some medication
may induce drowsines while other medication may affect heart rate, blood pressure, and circulation.
WARNING
Risk of electric shock - Install the power center at least five (5) feet (152.4cm) from the inside wall of the pool
and/or hot tub using non-metallic plumbing. Canadian installations must be at least three (3) meters (10 feet) from
the water.
Children should not use spas or hot tubs without adult supervision.
Do not use spas or hot tubs unless all suction guards are installed to prevent body and hair entrapment.
People using medications and/or having an adverse medical history should consult a physician before using a spa
or hot tub.
AVERTISSEMENT
Danger d'electrocution - Les installations Canadiennes doivent se trouver à au moins trois (3) mètres de l’eau.
Ne pas laisser les enfants utiliser une cuve de relaxation sans surveillance.
Pour éviter que les cheveux ou une partie du corps puissent être aspirés, ne pas utiliser une cuve de relaxation si
les grilles de prise d'aspiration ne sont pas toutes en place.
Les personnes qui prennent des médicaments ou ont des problèmes de santé devraient consulter un médecin
avant d’utiliser une cuve de relaxation.

Page 5
SAVE THESE INSTRUCTIONS
WARNING
People with infectious diseases should not use a spa or hot tub.
To avoid injury, exercise care when entering or exiting the spa or hot tub.
Do not use drugs or alcohol before or during the use of a spa or hot tub to avoid unconsciousness and possible
drowning.
Pregnant or possibly pregnant women should consult a physician before using a spa or hot tub.
Water temperature in excess of 100°F/38°C may be injurious to your health.
Before entering a spa or hot tub measure the water temperature with an accurate thermometer.
Do not use a spa or hot tub immediately following strenuous exercise.
Prolonged immersion in a spa or hot tub may be injurious to your health.
Do not permit any electric appliance (such as a light, telephone, radio, or television) within 5 feet (1.5 m) of a spa
or hot tub.
The use of alcohol, drugs or medication can greatly increase the risk of fatal hyperthermia in hot tubs and spas.
Water temperature in excess of 100°F/38°C may be hazardous to your health.
AVERTISSEMENT
Les personnes atteintes de maladies infectieuses ne devraient pas utiliser une cuve de relaxation.
Pour éviter des blessures, user de prudence en entrant dans une cuve de relaxation et en sortant.
Pour éviter l’évanouissement et la noyade éventuelle, ne prendre ni drougue ni alcool avant d’utiliser une cuve de
relaxation ni quand on s’y trouve.
Les femmes enceintes, que leur grossesse soit confirmée ou non, devraient consulter un médecin avant d’utiliser
une cuve de relaxation.
Il peut être dangereux pour la santé de se plonger dans de l’eau à plus de 38°C/100°F.
Avant d’utiliser une cuve de relaxation mesurer la témperature de l’eau à l’aide d’un thermomètre précis.
Ne pas utiliser une cuve de relaxation immédiatement après un exercice fatigant.
L’utilisation prolongée d’une cuve de relaxation peut être dangereuse pur la santé.
Ne pas placer d'appareil électrique (luminaire, téléphone, radio, téléviseur, etc) à moins de 1.5m de cette cuve de
relaxation.
La consommation d’alcool ou de drogue augmente considérablement les risques d’hyperthermie mortelle dans
une cuve de relaxation.
Il peut etrê dangereux pour la santé de se plonger dans de l’eau à plus de 38°C/100°F.
Attention installer: Install to provide drainage of compartment for electrical components.
CAUTION
A ground-fault circuit-interrupter must be provided if this device is used to control underwater lighting fixtures. The
conductors on the load side of the ground-fault circuit-interrupter shall not occupy conduit, boxes, or enclosures
containing other conductors unless the additional conductors are also protected by a ground-fault circuit-
interrupter. Refer to local codes for complete details.
CAUTION
A terminal bar marked "GROUND" is provided within the power center. To reduce the risk of electrical shock,
connect this terminal bar to the grounding terminal of your electric service or supply panel with a continuous
copper conductor having green insulation and one that is equivalent in size to the circuit conductors supplying this
equipment, but no smaller than no. 12 AWG (3.3mm). In addition, a second wire connector should be bonded with
a no. 8 AWG (4.115mm) copper wire to any metal ladders, water pipes, or other metal within five (5) feet (1.52m)
of the tub.
WARNING
To avoid injury ensure that you use this control system to control only packaged pool/spa heaters which have built-
in operating and high limit controls to limit water temperature for pool/spa applications. This device should not be
relied upon as a safety limit control.

Page 6
Section 2. System Overview
2.1 Package Contents
Pool Link Control System Sub-Assemblies
Power Centers (required and sold separately)
6613 Standard Power Center
(with mounting brackets) 6614 Sub-Panel Power Center
(with mounting brackets) 6613AP and 6614AP PureLink
Sub-Panel Power Center (with
mounting brackets) (6614AP shown).
Requires purchase of Purelink Cell Kit
either PLC700 or PLC1400.

Page 7
2.2 System Component Specifications and Dimensions
Table 1
Specifications (USA and Canada)
Power Supply 120 VAC; 60 Hz; 3 A
Contact Rating High voltage - 25 A; 3HP @ 240 VAC
1½ HP @ 120 VAC
1500 Watts Incandescent
Low Voltage - Class Two, 1 A @ 24 VAC
Service Switch All Circuits (located at Power Center)
Dimensions
Pool Link Control System
6613/6613AP
Standard Power
Center
14½"
13¾"
6614/6614AP
Sub-Panel
Power Center
20"
14½"
5½"
2½"
3"
10½" 5"
2"
Power Centers (required and sold separately)

Page 8
3.2 Attach Labels
3.2.1 Wiring Diagram Label
The Wiring Diagram label covers the existing
wiring diagram label on the inside of the power
center door. Attach the label by removing the
backing and placing it over the existing wiring
diagram.
NOTE Be careful to only cover the wiring diagram, not
the warning label or the installation instruction
portion of the label.
3.2.2 "What The Switches Do" Label
The "What The Switches Do" label covers the
existing printing on the dead panel. Attach the label
by removing the backing and placing it over the
existing "What The Buttons Do" printing.
NOTE For the Purelink 6614AP Power Center, align
the top portion of the label with the top printed
line of the text box and fold the bottom portion
under the edge.
3.3 High Voltage Wiring
3.3.1 System Power
Section 3. Installation
3.1 Pool Link Control System Mounting
1. The Pool Link and Power Center should be
located at or near the equipment pad. Locate
the Pool Link and Power Center at least five
(5) feet or more away from pool/spa and
five (5) feet off the ground.All national,
state, and local codes are applicable.
NOTE For Canadian installations, the Power Center
must be at least three (3) meters (9.8 feet)
away from the pool/spa and 1.5 meters (5 feet)
above the ground.
2. Use the mounting brackets and instructions
provided with the Standard Power Center or
Sub-Panel Power Center.
3. Sub-Panel Power Centers have special
code requirements. Be sure to follow all
applicable local and state codes to insure
safe installation.
NOTE The Pool Link is not to be considered as
suitable for use as Service Equipment.
Therefore, it is required to have the appropriate
means of disconnection, circuit isolation, and/or
branch circuit protection installed upstream of
the Power Center.
Depending on which equipment is being controlled,
run ½" or ¾" conduit from the power supply panel
to the bottom of the Pool Link Control System.
If you are using the Sub-Panel Control System,
wire power to the appropriate breakers. Pull in
appropriate wire for equipment. Each piece of
equipment requires its own high voltage relay.
Connect 120 volts to the transformer and Pool
Link Timer Motor terminals. Connect equipment
ground(s). See Figures 1 and 2.
3.3.2 3HP (Standard) Relays
For each piece of 120 volt equipment, connect
power to a line terminal and connect equipment
to a load terminal on the same relay. Refer to the
wiring diagram on the inside of the control center
door. For common Pool Link Control installations,
refer to Figures 3 and 4.
NOTE The following are the contact ratings for 3HP
(Standard) Relay. DO NOT exceed any ratings.
3 HP @ 240 VAC; 1½ HP @ 120 VAC; 25
Amps; 1500 Watts.
3.3.3 Bonding the Pool Link
Install a bonding lug to the Pool Link enclosure.
Do not use sheet metal screws to attach the bonding
lug; use the appropriate hardware to securely
and positively install it. Connect the bond lug,
using a #8 solid copper core wire, to an approved
earth ground (an approved ground stake, grid, or
conducting metal water pipe buried to a sufficient
depth). See Figure 5.
WARNING
Potentially high voltages in the Pool Link Control
System can create dangerous electrical hazards,
possibly causing death, serious injury or property
damage. Turn off power at the main circuit of the
Pool Link Control System to disconnect the Pool
Link from the system. To properly and safely
wire the system, be sure to carefully follow the
applicable requirements of the National Electrical
Code (NEC), NFPA 70 or the Canadian Electrical
Code (CEC), CSA C22.1. All applicable local
installation codes must also be adhered to.

Page 9
Transformer
Earth Ground
Breaker Panel
To 120 VAC
Breaker
Neutral
Black
White
Wire nut to
120 VAC power
Low voltage raceway, do not run high voltage in this compartment
Primary
Figure 1. Control System with Power Center, 6613,
6613AP
To "Motor"
Terminals
of Filter
Time Clock
(See
Figure 6)
Figure 2. Control System with Power Center, 6614,
6614AP
Transformer
Earth Ground
Black
White
Primary
Low voltage raceway, do not run high voltage in this compartment
From Main
Power
Ground
White
White Black
Black
To "Motor"
Terminals
of Filter
Time Clock
(See
Figure 6)
Two-Speed Pump Wiring
Relay 1 (P2 socket) Relay 2 (P1 socket)
Two Speed
Filter Pump
sub-
panel
high
com
low
Line 2
Line 1
Load 1
Load 2
Line 3
Load 3
Line 4
Load 4
Figure 4. Two-Speed Pump Wiring Diagram
Relay 1 (P1 socket) Relay 2 (P2 socket)
Single Speed
Filter Pump
sub-
panel
Line 3
Load 3
Line 4
Load 4
Line 2
Line 1
Load 1
Load 2
Single-Speed Pump and
Cleaner Booster Pump Wiring
Cleaner
Booster Pump
Figure 3. Single-Speed Pump and Cleaner Booster
Pump Wiring Diagram

Page 10
Figure 5. Standard Power Center- Bonding
Bonding Lug
Earth
Ground
Breaker
Panel
Blower (120
VAC)
Filter
Pump (240
VAC)
Primary
24 VAC
Transformer
3.4 Low Voltage Wiring
3.4.1 Wire Relays to Printed Circuit Board
Connect the coil connectors of the equipment
relays to their appropriate sockets on the printed
circuit board. Make sure coil connector wires are
wired through the mouse hole between the low and
high voltage compartment.
3.4.2 In-Floor Cleaning System
For the Pool Link, plug the in-floor cleaning
system JVAinto P6 (refer to Figure 6). Note: The
JVAis activated when the filter pump time clock
turns the system on. The JVA will rotate every 20
minutes until the time clock turns the filter pump
off.
3.4.3 Wire Time Clock to Printed Circuit
Board
Connect the Filter Pump Time Clock to the P3
socket on the printed circuit board according to the
wiring diagram on the inside of the control center
door.
3.4.4 Connect Heater to Printed Circuit Board
Connect two 18-gauge wires, designed for use in
hot environments, to terminals 5 and 6 on the print-
ed circuit board as shown in Figure 6. Run the two
heater wires from the printed circuit board over to
the heater and wire nut in series with the heater cir-
cuitry as if you were wiring a Fireman’s Switch or
a heater delay. Turn the heater thermostat to desired

Page 11
pool temperature and the heater toggle switch on.
Do not disconnect high limit or pressure switches.
The heater will only fire when time clock turns on
the filter pump.
3.4.5 Connect Freeze Protection Sensor to
Printed Circuit Board
Carefully uncoil copper tube and feed it through
bottom of the enclosure without kinking the
capillary tube. Expose the capillary tube to outside
air. Ensure that wires from sensor are connected to
Pins 1 and 2 on the terminal block. Set sensor to
38°. Refer to Figure 6.
3.4.6 Set Jumpers and Diode
The system default from the factory is set up for
a single-speed filter pump. Set jumpers according
to your pump setup by following Figure 7 below.
A diode stored in pin 3 of the terminal block
must be placed into the diode location for two-
speed filtration pump installation.
Figure 7. Jumper Settings Diagram
Figure 6. Pool Link Wiring Diagram
To
Heater.
Connect in
Series with
Thermostat
FLTR/
HI CLNR/
LO
Contacts
Motor
Filter
Time Clock
120
VAC To
Freeze
Sensor
P5
P1 P2 P3
123
Move Jumper to
pins 1 & 2 to disable
heater cooldown
To JVA for In-Floor
Cleaning System or
Water Feature
FLTR
TCLK
24 VAC from
Transformer
P6 JP1
(Refer to figures
3 and 4)
Both jumpers are
in the A position.
Filter Pump
must be a single
speed.
NOTE:
P3
P2
P1
A
B
Move jumper to
pins 1 & 2 to
disable heater
cooldown 321
P5 To24VAC
Power Supply
To F r e e z e
Sensor
To
Heater
123456
Time Clock:
P3 - Main Filter
Pump
P6
diode
Single - Speed Filter
Pump and Pool Cleaner
Booster Pump Setting:
(Factory Default)
AB
Diode is stored
here for future
use.
Time Clock:
P3 - Main Filter
Pump
P3
diode
P2
P1
A
B
Move jumper to
pins1&2to
disable heater
cooldown 321
P5 To 2 4 VA C
Power Supply
To F r e e z e
Sensor
To
Heater
123456
P6
Two - Speed Filter
PumpSetting:
AB
Move both jumpers to
the B position. Remove
diode from storage
location (TB1) and install
as indicated with the white
band towards the bottom.

Page 12
3.4.7 Connect System Power to Printed
Circuit Board
Plug the three-pin 24 VAC plug from the
transformer into the three-pin terminal P5 on the
back of the Control System PCB (see Figure 8).
Mount the Bezel to the Control System using the
screws provided.
Figure 8. Pool Link Control Panel (Back View)
24 VAC Power Plug
Connection

Page 13
Section 4. System Startup
4.1 Set Time Clocks and Test Equipment
Follow the instructions on the faceplate to set
Timers. Turn the Filter Pump Timer dial clockwise
only. Test equipment by moving each of the Service
Switches to MANUAL and confirming that the
corresponding equipment turns on. Return both
switches to AUTO after testing is complete.
4.2 Single-Speed Filter Pump Plus Cleaner
Booster Pump Operation
The Filter Pump Timer represents the total duration
of filtration. Each tab equals 30 minutes of filter
time. The Secondary Timer (DIP Switches)
represents the amount of time a Cleaner Booster
Pump will run. DIP Switch 0 equals 2 minutes of
operation. All other DIP Switches equal the number
of hours. Turn on one and only one DIP Switch for
cleaner timing.
4.3 Two-Speed Filter Pump Operation
The Filter Pump Timer represents the total duration
of filtration. Each tab equals 30 minutes of filter
time. The Secondary Timer (DIP switches)
represents the amount of time the filter pump will
be in high speed. DIP switch 0 equals 2 minutes of
high speed operation. All other DIP switches equal
the number of hours (e.g., DIP switch 4 equals 4
hours of high speed.) Turn on one and only one DIP
switch for high speed.
4.4 Heater Cool Down
Whenever the time clock turns on, then off, the
filter pump will remain on for 5 to 8 minutes. This
is a cool down cycle which will occur even if a
heater is not installed. Figure 9. Freeze Protection
Freeze
Protection
4.5 Freeze Protection
When freeze conditions exist, the filter pump will
turn on and run until the time clock duration is
reached. If freeze conditions still exist after the
time has passed, the pump will remain on. Refer to
Figure 9.
Important Information on Freeze Protection
Freeze protection is intended to protect equipment
and plumbing for short periods of freezing only. It does
this by activating the filtration pump and circulating the
water to prevent freeze inside equipment or plumbing.
Freeze protection does not guarantee that equipment
will not be damaged by extended periods of freezing
temperatures or power outages. In these conditions,
the pool and spa should be shut down completely
(e.g. drained of water and closed for the winter) until
warmer weather exists.
Important
Freeze sensor’s capillary tube must be exposed to
outside air at the bottom of the power center enclosure.

Page 14
Notes

Page 15
Notes

LIMITED WARRANTY
Thank you for purchasing Jandy®pool and spa products. Jandy Pool Products, Inc. warrants all parts to be free
from manufacturing defects in materials and workmanship for a period of one year from the date of retail
purchase, with the following exceptions:
•AquaLink®RS units installed with Jandy Surge Protection Kits will be covered for two years.
•NeverLube®valves are warranted for the life of pool and/or spa on which they were originally installed.
•AquaPureTM Electronic Chlorine Generator Electrolytic Cells carry a 5 year limited warranty on a prorated basis.
This warranty is limited to the first retail purchaser, is not transferable, and does not apply to products that have
been moved from their original installation sites. The liability of Jandy Pool Products, Inc. shall not exceed the
repair or replacement of defective parts and does not include any costs for labor to remove and reinstall the
defective part, transportation to or from the factory, and any other materials required to make the repair. This
warranty does not cover failures or malfunctions resulting from the following:
1. Failure to properly install, operate or maintain the product(s) in accordance with our published Installation,
Operation and Maintenance Manuals provided with the product(s).
2. The workmanship of any installer of the product(s).
3. Not maintaining a proper chemical balance in your pool and/or spa [pH level between 7.2 and 7.8, Total
Alkalinity (TA) between 80 to 120 ppm, Total Dissolved Solids (TDS) less than 2000 not including salt ppm].
4. Abuse, alteration, accident, fire, flood, lightning, rodents, insects, negligence or acts of God.
5. Scaling, freezing, or other conditions causing inadequate water circulation.
6. Operating the product(s) at water flow rates outside the published minimum and maximum specifications.
7. Use of non-factory authorized parts or accessories in conjunction with the product(s).
8. Chemical contamination of combustion air or improper use of sanitizing chemicals, such as introducing
sanitizing chemicals upstream of the heater and cleaner hose or through the skimmer.
9. Overheating; incorrect wire runs; improper electrical supply; collateral damage caused by failure of O-Rings,
DE grids, or cartridge elements; or damage caused by running the pump with insufficient quantities of water.
LIMITATION OF LIABILITY:
This is the only warranty given by Jandy Pool Products, Inc. No one is authorized to make any other warranties
on behalf of Jandy Pool Products, Inc. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES,
EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF FITNESS
FOR A PARTICULAR PURPOSE AND MERCHANTABILITY. JANDY POOL PRODUCTS, INC. EXPRESSLY
DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL, INCIDENTAL, INDIRECT OR
PUNITIVE DAMAGES FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY. This warranty gives
you specific legal rights. You may also have other rights which vary by state or province.
WARRANTY CLAIMS:
For prompt warranty consideration, contact your dealer and provide the following information: proof of purchase,
model number, serial number and date of installation. The installer will contact the factory for instructions
regarding the claim and to determine the location of the nearest designated service center. If the dealer is not
available, you can locate a service center in your area by visiting www.jandy.com or by calling our technical
support department at (707) 776-8200 extension 260. All returned parts must have a Returned Material
Authorization number to be evaluated under the terms of this warranty.
6000 Condor Drive • Moorpark, CA USA 93021 • 707.776.8200 • Fax 707.763.7785
Jandy Pool Products, Inc.
H0279900-
Litho in U.S.A. © 2006 Jandy Pool Products, Inc. 0604
For technical support call 707-776-8200, ext. 260
Table of contents
Other Jandy Control System manuals
Popular Control System manuals by other brands

Carson
Carson Reflex Stick PRO 3.1 LCD instruction manual

Xantrex
Xantrex Freedom e-GEN Checklist

Siemens
Siemens SINUMERIK 840D sl Commissioning manual

ENTRYPASS
ENTRYPASS EP.S3150 Configuration guide

Sutter Instrument
Sutter Instrument Lambda SC USB Installation & Configuration

Conviron
Conviron CMP6050 Operator's manual