janitza Procont LMC-008-IO Instruction manual

Doc. no. 2.100.131.1.a 02/2023
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau | Germany
Support tel. +49 6441 9642-22
User manual and technical data
www.janitza.de
Extension module for load management
Procont®-LMC-008-IO

2
www.janitza.de
Procont®-LMC-008-IO
Procont®-LMC-008-IO
Extension module for load management
Doc. no.: 2.100.131.1.a
Date: 02/2023
The German version is the original edition of the documentation

3
www.janitza.de Procont®-LMC-008-IO
Subject to technical alterations.
The contents of our documentation have been compiled with great care and reflect the current state of
the information available to us. Nonetheless, we wish to point out that updates of this document are not
always possible at the same time as technical refinements are implemented in our products. Information
and specifications are subject to change at any time.
Please check for the latest version at www.janitza.de.

4
www.janitza.de
Procont®-LMC-008-IO
TABLE OF CONTENTS
1. Information on the device and the user manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Disclaimer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Copyright notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.3 Technical changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.4 About this user manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Defective device/disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2. Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 Display of warning notices and safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Hazard levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Product safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Dangers when handling the device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5 Electrically qualified personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.6 Warranty in the event of damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3. Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Incoming goods inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.3 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 EU conformity declaration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4. Structure of the device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 Display and connection assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2 Operation and key functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Rating plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5. Assembly and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6. Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.1 Connecting the expansion module via a network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.2 Connecting to the master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7. Instantaneous values on the display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8. System settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9. Alarms on the display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
10. Network settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

5
www.janitza.de Procont®-LMC-008-IO
11. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
11.1 Dimensional drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
11.2 Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
11.2.1 Example Procont®-LMC-008-IO and boiler semiconductor contactor up to 4 . . 25
11.2.2 Example Procont®-LMC-008-IO and relay contactor up to 8. . . . . . . . . . . . . . . . 26
12. Maintenance and service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
12.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
12.2 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

6
www.janitza.de
Procont®-LMC-008-IO
1. Information on the device and the user manual
1.1 Disclaimer
Compliance with the usage information for the
devices is a prerequisite for safe operation and
attaining the stated performance characteristics
and product features.
Janitza electronics GmbH assumes no liability for
bodily injury, material damage or financial losses
which result from disregard of the usage informa-
tion.
Make sure that your usage information is readily
available and legible.
1.2 Copyright notice
© 2022 - Janitza electronics GmbH - Lahnau.
All rights reserved.
Any reproduction, processing, distribution or other
use, in whole or in part, is prohibited.
All trademarks and the rights arising from them
are the property of the respective owners of these
rights.
1.3 Technical changes
· Make sure that your device matches the user
manual.
· This user manual is valid for the Procont®-LMC-
008-IO. Separate validities and distinctions are
marked.
· First make sure you have read and understood
the usage information accompanying the prod-
uct.
· Keep the usage information associated with the
product available for the entire service life and
pass it on to any possible subsequent users.
· Find out about device revisions and the associat-
ed modifications of the usage information associ-
ated with your product at www.janitza.de.
1.4 About this user manual
If you have questions, suggestions or ideas for im-
provement of the user manual, please let us know
INFORMATION
This manual is valid for devices of the type:
Procont®-LMC-008-IO
The settings for the expansion module can be
made directly on the device or also via the Procon-
t®Vis load management software, which provides
an easier and better overview of the settings.
In addition to this user manual, please refer to ad-
ditional usage information for your device, such as:
• Installation instructions.
• Data sheet
INFORMATION
Our usage information uses the grammatical mas-
culine form in a gender-neutral sense! This form
always refers equally to women, men and diverse.
In order to make the texts more readable, distinc-
tions are not made. We ask for your understand-
ing for these simplifications.

7
www.janitza.de Procont®-LMC-008-IO
1.5 Defective device/disposal
Before sending defective devices, modules or
components back to the manufacturer for testing:
· Contact the manufacturer's Support department.
· Send devices, modules or components complete
with all accessories.
· When doing so, please bear the terms for trans-
portation in mind.
INFORMATION
Please return defective or damaged devices to
Janitza electronics GmbH in accordance with the
shipping instructions for air or road freight (complete
with accessories).
Do not attempt to open or repair the device (the
component) on your own because otherwise all
warranty claims become invalid!
For the Disposal of the device please observe
national regulations! Dispose of individual parts, as
applicable, depending on their composition and
existing country-specific regulations, e.g. as
· Electronic waste,
· Batteries and rechargeable batteries.
· Plastics.
· Metals.
Engage a certified disposal company to handle
scrapping as needed.
Information on service and maintenance of your
device can be found in chapter „12. Maintenance
and service“ on page 27.

8
www.janitza.de
Procont®-LMC-008-IO
The chapter on Safety contains information which
must be observed to ensure your personal safety
and avoid material damage.
2.1 Display of warning notices and safety
information
The warning notices shown below
· are found throughout all of the documentation,
· can be found on the devices themselves.
· indicate potential risks and hazards,
· underscore aspects of the information provided
that clarifies or simplifies procedures.
The additional symbol onthedevice itself indi-
cates anelectrical danger that can result in serious
injuries or death.
This general warning symbol draws attention to a
possible risk of injury. Be certain to observe all of
the information listed under this symbol in order to
avoid possible injury or even death.
2. Safety
2.2 Hazard levels
Warning and safety information is marked by a
warning symbol, and the hazard levels are shown
as follows, depending on the degree of hazard:
DANGER
Warns of an imminent danger which, if not avoid-
ed, results in serious or fatal injury.
WARNING
Warns of a potentially hazardous situation which, if
not avoided, could result in serious injury or death.
CAUTION
Warns of an immediately hazardous situation
which, if not avoided, can result in minor or mod-
erate injury.
ATTENTION
Warns of an immediately hazardous situation
which, if not avoided, can result in material or envi-
ronmental damage.
INFORMATION
Indicates procedures in which there is no hazard
of personal injury or material damage.
2.3 Product safety
The device reflects current engineering practice
and accepted safety standards, but hazards can
arise nonetheless.
Observe the safety regulations and warning no-
tices. If notices are disregarded, this can lead to
personal injury and/or damage to the product.
Every type of tampering with or use of this device,
· which goes beyond the mechanical, electrical or
other operating limits can lead to personal injury
and/or damage to the product;
· constitutes “misuse” and/or “negligence” under
the product’s warranty and thus voids the war-
ranty for any possible resulting damage.
Read and understand the user manual before
installing, operating, maintaining and using the
device.
Only operate the device when in perfect condition
and in compliance with this user manual and the
usage information that is included. Send defective
devices back to the manufacturer in compliance
with proper transport conditions.
Retain the user manual throughout the service life
of the device and keep it at hand for consultation.
When using the device, also observe the legal and
safety regulations for your system that are applica-
ble for the respective use case.

9
www.janitza.de Procont®-LMC-008-IO
WARNING
Risk of injury due to electrical voltage!
Severe bodily injury or death can result! Therefore
please abide by the following:
· Switch off your installation before commenc-
ing work! Secure it against being switched on!
Check to be sure it is de-energized! Ground and
short circuit! Cover or block off adjacent live
parts!
· During operation and troubleshooting (espe-
cially for DIN rail devices), check your system
for dangerous voltages and switch these off if
necessary!
· Wear protective clothing and protective equip-
ment in accordance with applicable guidelines
when working on electrical systems!
· Before making connections to the device/the
component, ground the device by means of the
ground wire connection, if present.
· Do not touching bare or stripped leads that are
energized! Equip stranded conductors with wire
ferrules!
· Hazardous voltages can be present in all circuit-
ry parts that are connected to the power supply.
· Protect wires, cables and devices with a suitable
line circuit breaker/fuse!
· Never switch off, remove or tamper with safety
devices!
· There can still be hazardous voltages present
in the device or in the component even after it
has been disconnected from the supply voltage
(capacitor storage).
· Do not operate equipment with current trans-
former circuits when open.
· Only connect screw terminals with the same
number of poles and design!
· Do not exceed the limit values specified in the
user manual and on the rating plate! This must
also be observed during testing and commis-
sioning.
· Take note of the safety and warning notices in
the documents that belong to the device!
2.4 Dangers when handling the device
When operating electric devices, it is unavoid-
able for certain parts of these devices to conduct
hazardous voltage. Consequently, severe bodily
injury or material damage can occur if they are not
handled properly.
Therefore, when handling our devices, always
observe the following:
· do not exceed the limit values specified in the
user manual and on the rating plate! This must
also be observed during testing and commission-
ing!
· Take note of the safety and warning notices in all
usage information that belongs to the device!
WARNING
Disregarding the connection conditions of the
Janitza measurement devices or their compo-
nents can lead to injuries and even death or to
material damage!
• Do not use Janitza measurement devices or
components for critical switching, control or pro-
tection applications where the safety of persons
and property depends on this function.
• Do not carry out switching operations with the
Janitza measurement devices or components
without prior inspection by your plant manager
with specialist knowledge! In particular, the safe-
ty of persons, material assets and the applicable
standards must be taken into account!

10
www.janitza.de
Procont®-LMC-008-IO
WARNING
Warning against unauthorized manipulation or
improper use of the device or its components!
Opening, dismantling or unauthorized manipula-
tion of the device and its components which goes
beyond the mechanical, electrical or other operat-
ing limits indicated can lead to material damage or
injury, up to and including death.
· Only electrically qualified personnel are permit-
ted to work on the devices and their compo-
nents, assemblies, systems and current circuits.
· Always use your device or component only in
the manner described in the associated docu-
mentation.
· If there is discernible damage, send the device
or the component back to the manufacturer!
2.5 Electrically qualified personnel
To avoid bodily injury and material damage, only
electrically qualified personnel are permitted to
work on the devices and their components, mod-
ules, assemblies, systems and current circuits who
have knowledge of:
· The national and international accident preven-
tion regulations.
· Safety technology standards.
· Installation, commissioning, operation, discon-
nection, grounding and marking of electrical
equipment.
· The requirements concerning personal protective
equipment.
Electrically qualified persons within the scope
of the technical safety information of all usage
information associated with the device and its
components are persons who can furnish proof of
qualification as an electrically skilled person.
2.6 Warranty in the event of damage
Any unauthorized tampering with or use of the
device constitutes "misuse" and/or "negligence"
under the product’s warranty and thus voids the
warranty for any possible resulting damage. In this
regard, please take note of chap. „3.3 Intended
use“ on page 11.

11
www.janitza.de Procont®-LMC-008-IO
3. Product description
3.1 Device description
Intelligent, network-capable expansion module for
Procont®-LMC, for an additional 4 digital inputs
and 8 relay outputs for consumer control.
Performance characteristics:
· Expansion for up to 12 load groups
· Integration of up to 4 pulse counters
· 8 relay outputs for consumer control
· 8 manual switches for relay outputs manual/au-
tomatic
· LCD display with backlight
· Operation via 2-axis joystick
· 12 LEDs for status display
· DIN rail mounting 35 mm
3.2 Incoming goods inspection
Safe and trouble-free operation of this device and
its components presupposes proper transport,
proper storage, set-up and assembly as well as
operation and maintenance in addition to com-
pliance with the safety information and warning
notices.
Exercise due caution when unpacking and packing
the device, do not use force and only use suitable
tools.
Before installing the device, please check the
following:
· Its flawless mechanical condition by visual in-
spection.
· The scope of delivery for completeness.
If it can be assumed that safe operation of the
device is no longer possible:
· Disconnect the device from operation immediate-
ly!
· Secure the device against being switched on
again!
It can be assumed that safe operation is no longer
possible if the device, for example:
· Has visible damage.
· No longer functions despite an intact power
supply.
· Was subjected to extended periods of unfavor-
able conditions (e.g. storage outside of the per-
missible climate thresholds without adjustment to
the room climate, condensation, etc.) or transport
stress (e.g. falling from an elevated position, even
without visible external damage, etc.).
3.3 Intended use
The device is:
· Only for use in the industrial sector.
· Intended for installation in switchboard cabinets
and small distribution boards.
· Intended for mounting on a DIN rail.
· Not intended for installation in vehicles! Use of
the device in non-stationary equipment consti-
tutes an exceptional environmental condition and
is only permissible by special agreement.
· Not intended for installation in environments with
harmful oils, acids, gases, vapors, dusts, radia-
tion, etc.
· Designed as an indoor device.
Safe and trouble-free operation of the device
requires proper transport, storage, assembly,
installation, operation and maintenance.
3.4 EU conformity declaration
Please see the EU declaration of conformity post-
ed at www.janitza.de for the laws, standards and
directives applied by Janitza electronics GmbH for
the devices. The CE conformity marking require-
ments for the device arise from the EU conformity
declaration and the laws, standards and directives
mentioned therein.
·
3.5 Scope of delivery
Quantity Part. no. Designation
1 60.00.303 Procont®-LMC-008-IO
1 33.03.843 Installation instructions

12
www.janitza.de
Procont®-LMC-008-IO
4. Structure of the device
4.1 Display and connection assignments
Item Function/Designation
1Display (4 lines, background illumination)
2LEDs for inputs
3Relay outputs A8-A5,
Outputs (load groups)
4Digital inputs/outputs
Supply voltage
5
Status LED for relay outputs A1-A8
LED on -> output is active
LED off -> output is inactive
6Manual switches for the relay outputs
7TCP port
8Joystick
9Reserved
10 Gnd, D+, D-
11 Relay outputs A1-A4
1
4
3
2
6
7
8
91011
5

13
www.janitza.de Procont®-LMC-008-IO
4.2 Operation and key functions
Interaction Description
ENTER - Press joystick to the
right for at least 1 second.
ESC - Press joystick to the
left for at least 1 second.
Joystick briefly to the right
Joystick briefly to the left
+ Joystick up
- Joystick down
The device is operated via a joystick.
· Navigation within the menus.
· Device configuration.
Menu access:
To access the settings menu, press the joystick to
the right (ENT) for at least 1 second; to return to
the main menu press the joystick to the left (ESC)
for at least 1 second.
Navigation:
To enter the next menu, press the joystick briefly
to the right; to return to the previous menu press it
briefly to the left.
Change parameters:
To change a parameter, press the joystick down
or up; to save it or to return to the previous menu,
press to the right for at least 1 second.
The relays can be operated manually by switches.
1 s
1 s

14
www.janitza.de
Procont®-LMC-008-IO
4.3 Rating plate
Item Designation Description
1Designation
of origin Country of origin and address of the manufacturer
2Operational data Supply voltage, DC in V
Power consumption in VA
3Device type Device designation
4Part number Manufacturer’s part number
5Data matrix code Coded manufacturer data
6Manufacturer’s logo Logo of the device manufacturer
7CE conformity marking See section "3.5 EU Declaration of Conformity" on page 16
8Manufacturer-
specific data Manufacturer data
9Hardware version Hardware version of your device
10 Type/serial number Number for identification of the device
3
1
2
4
56 7
9
10
8
Smart Energy &
Power Quality Solutions
Janitza electronics GmbH / Germany • www.janitza.com
Blatt / Page : 1 / 1
Ausgabe : 04.04.2022
Vorschlag: Typenschild PROCONT-Serie
Hinweis: Janitza Typenschilder gibt es in zwei Größen-Varianten.
Diese Vorschlags-Variante ist 50,8 mm breit und 25,4 mm hoch.
Typenschild PROCONT-Serie Datum Dok.-Nr.:
Erstellt: Th. Braun 18.10.2021 2.100.087.0.a
Korrigiert: Th. Braun 27.10.2021 2.100.087.0.b
Korrigiert: Th. Braun 02.12.2021 2.100.087.0.c
Korrigiert: Th. Braun 04.04.2022 2.100.087.0.d
Korrigiert: Th. Braun 04.01.2023 2.100.087.0.e
Category supply voltage
Item number
Type
2D code (DataMatrix)
with device name
and item number.
CE
Date of manufacture or delivery month / year
Hardware or firmware index
Country of manufacture
Address (quasi-manufacturer)
Imprint (manufacturer-specific),
serial number
Aux: 100..240V, 50/60Hz .9-15VA
PROCONT-LMC • 6000300 10/2021 • 16.0f
Aux: 230V, 50Hz .9VA
PROCONT-LMC-008-IO • 6000303 10/2021 •002
Aux: 100..240V, 50/60Hz .9-15VA
PROCONT-LMC-LITE • 6000301 10/2021 • 16.0f
Aux: 100..240V, 50/60Hz .9-15VA
PROCONT-EMC • 6000302
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
10/2021 • 16.0f
Typenschild PROCONT-LMC-LITE Typenschild PROCONT-EMC
Typenschild PROCONT-LMC-008-IOTypenschild PROCONT-LMC
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
UK importer
Aux: 100..240V, 50/60Hz .9-15VA
PROCONT-LMC-LITE • 1402025 10/2021 • 16.0f
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
Category supply voltage
Item number
Type
2D code (DataMatrix)
with device name
and item number.
CE
Date of manufacture or delivery month / year
Hardware or firmware index
Country of manufacture
Address (quasi-manufacturer)
Imprint (manufacturer-specific),
serial number
Aux: 100..240V, 50/60Hz .9-15VA
PROCONT-LMC • 6000300 10/2021 • 16.0f
Aux: 230V, 50Hz .9VA
PROCONT-LMC-008-IO • 6000303 10/2021 •002
Aux: 100..240V, 50/60Hz .9-15VA
PROCONT-LMC-LITE • 6000301 10/2021 • 16.0f
Aux: 100..240V, 50/60Hz .9-15VA
PROCONT-EMC • 6000302
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
10/2021 • 16.0f
Typenschild PROCONT-LMC-LITE Typenschild PROCONT-EMC
Typenschild PROCONT-LMC-008-IOTypenschild PROCONT-LMC
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Made in Austria
UK importer
Aux: 100..240V, 50/60Hz .9-15VA
PROCONT-LMC-LITE • 1402025 10/2021 • 16.0f
UK: Represented by
Authorised Rep Compliance Ltd.
ARCHouse
Thurnham
Lancaster
LA2 0DT
UK
Aux: 24 VDC ∙4 VA

15
www.janitza.de Procont®-LMC-008-IO
5. Assembly and installation
DANGER
Risk of injury due to electrical voltage!
Severe bodily injury or death can result from:
·Touching bare or stripped leads that are ener-
gized.
·Device inputs that pose a hazard when
touched.
Switch off your installation before commencing
work! Check to be sure it is de-energized!
Proceed as follows to mount the Procont®-LMC-
008-IO expansion module:
1. Mount the device in switchboard cabinets or
small distribution boards according to DIN
43880 (any mounting orientation) on a 35mm
(1.38in) DIN rail.
2. Check the device for a firm fit. The mounting
orientation is arbitrary.
3. Connect the supply voltage of
24VDC/150mA.
Refer to the rating plate for the supply voltage
for your device. A message will appear on the
display after the supply voltage has been con-
nected. If no display appears, check whether
the supply voltage is within the nominal volt-
age range.
4. Connect the device to your local network. Use
a standard RJ45 patch cable to do so (see also
„4.1 Display and connection assignments“ on
page 12).
ATTENTION
Material damage due to disregard of the instal-
lation instructions!
Disregard of the installation instructions can
damage or destroy your device.
·Observe the information on the mounting orien-
tation in the sections “Mounting” and “Technical
Data”.
·Provide adequate air circulation in your installa-
tion environment and, as needed, cooling when
the temperatures are high!
CAUTION
Material damage due to disregard of the con-
nection conditions or impermissible overvoltag-
es
Disregard of the connection instructions or ex-
ceeding the permissible voltage range can dam-
age or destroy your device. Before connecting
the device to the supply voltage, please note:
• The voltage value must correspond to the
specifications on the rating plate! Observe
limit values as described in the user manual!
• In the building installation, secure the supply
voltage with a UL/IEC listed line circuit break-
er/fuse!
• Place the isolation device within easy reach of
the user, close to the device, and label it for
the respective device.
Gnd IO2 IO3 IO4 +24IO1
Supply voltage, 24 VDC

16
www.janitza.de
Procont®-LMC-008-IO
6. Connection
ATTENTION
Material damage due to security vulnerabili-
ties in programs, IT networks and protocols.
Security vulnerabilities can lead to data misuse
and faults and even the standstill of your IT infra-
structure.
To protect your IT system, network, data com-
munications and measurement devices:
· Inform your network administrator and/or IT
representative.
· Always keep the meter firmware up to date and
protect the communication to the meter with
an external firewall. Close unused ports.
· Take protective measures against viruses and
cyber attacks from the Internet, e.g. through
firewall solutions, security updates and virus
protection programs.
· Eliminate security vulnerabilities and update or
renew existing protection for your IT infrastruc-
ture.
ATTENTION
Material damage due to incorrect network
settings.
Incorrect network settings can cause faults
intheIT network!
· Consult your network administrator for
thecorrect network settings for your device.
The connection to a Procont®-LMC /LMC-Lite is
made via RS-485 or TCP/IP (interface optional).
The Procont®-LMC-008-IO expansion module
serves as a server in this constellation.
6.1 Connecting the expansion module via a
network

17
www.janitza.de Procont®-LMC-008-IO
6.2 Connecting to the master
For the connection to the load management
device (master module), the station number and
the assignment of the outputs to the load groups
must be set. The station number is consecutive in
a bus, starting with 1 at the master module (LMC/
LMC-Lite).
A connection via TCP/IP (optionally available) also
requires the input of the IP address of the master
module. The expansion module must be in the
same subnet as the master module. Fig. "TCP/IP Connection".
1.
Patch cable
LMC(-Lite) PC
Switch/Router
LMC-008-IO
2. LMC(-Lite) LMC-008-IO
Patch cable
Patch cable

18
www.janitza.de
Procont®-LMC-008-IO
7. Instantaneous values on the display
Symbol Display Function
10:45:00
OK
10:45:00
OK
Time and status
Alarme (Alarms):
Alles OK (All OK)
Alarme (Alarms):
Alles OK (All OK)
Pending alarms; alarms that have already
been acknowledged but are still active are
also displayed here.
PD:1.5m
Tarif (Tariff): HT
PD:1.5m
Tarif (Tariff): HT
Current period duration and tariff
10:45:00
18/10/10
10:45:00
18/10/10
Time and date
IO-01: I
22.0kW
IO-01: I
22.0kW
Type and current values of the inputs/outputs
IP-Adr. (IP addr.)
IP-Adr. (IP addr.)
Display of the currently set IP address
AZS-M-XP
Mx:50kW
AZS-M-XP
Mx:50kW
Type of the Procont®-LMC-008-IO and the
maximum connected load
BUS-G: 0
E-Mob: 0
BUS-G: 0
E-Mob: 0
Number of licensed bus devices and
e-charging stations
V: x18.0g SNr (Serial
number):1000
V: x18.0g SNr (Serial
number):1000
Version and serial number of the Procont®-
LMC-008-IO
MAC:0050
C271E25A
MAC:0050
C271E25A
MAC address that is set. Do not change!
SD card:
7.39GB
SD card:
7.39GB
SD card size
In each of the displays, it is possible to switch to the
basic menu by pressing the joystick to the left for at
least 1 second and to the operating menu by press-
ing the joystick to the right for at least 1 second.

19
www.janitza.de Procont®-LMC-008-IO
8. System settings
10:45:00
HZ: 50
10:45:00
HZ: 50
Auswahl
(Selection):
System
Auswahl
(Selection):
System
Spr/Lng:
German
Spr/Lng:
German
Spr/Lng:
German
Spr/Lng:
German
T-Sper
(Key lock):N
HG
(back-light):Aut.
T-Sper
(Key lock):N
HG
(back-light):Aut.
Grundb
(Home
screen):1
Grundb
(Home
screen):1
Spr/Lng:
German
Spr/Lng:
German
Sprache/Lan.
(Spr./Language): Set language (German/English)
Datum / Uhrzeit
(Date / Time) Set date and time
T-Sper (Key lock): N = Not allowed,
If you want to change and save a parameter despite the message "Not
allowed",
proceed as follows:
·Input the parameter
·This message is shown on the display: "Not allowed"
·Press and hold the joystick upwards for the duration of
the message
·The parameter has been saved
HG (backlight, BL): Backlight On
Off, Aut = Automatic
Grundb (Home screen, Hm scrn): Home screen instantaneous values
Uhrzeitsynchr
(Clock sync): Synchronize time with synchronization pulse
1 s
1 s

20
www.janitza.de
Procont®-LMC-008-IO
9. Alarms on the display
States of the alarms.
Pending alarms can be acknowledged using
"ENT" (Enter). To do so, press the joystick to the
right for 1.5 seconds.
1.5 sec
If the alarm is still displayed after acknowledging
and the fault is no longer present, switch off the
controller for 5 minutes. After switching on, the
alarm will no longer be displayed.
Alarme (Alarms):
Alles OK (All OK)
Alarme (Alarms):
Alles OK (All OK)
Pending alarms; alarms that have already been
acknowledged but are still active are also dis-
played here.
Alarm Error
Ext.Bus Bus failure of a bus device
Not-Aus
(Emergency stop)
Emergency stop alarm. Emergency stop curve exceeded.
TCP-Mod. TCP module alarm. The TCP module had an internal error. Please acknowledge.
MAN-Sch.
(Manual switch)
Consumer manual switch active. This alarm is displayed when one or more toggle
switches have been pressed to "ON".
Watchdog A watchdog alarm was triggered due to an internal program cycle error. A restart
was performed.
File-Al
File error alarm. One or more files on the SD memory card are corrupt.
Daten-Al (Data Al) Data from Procont®master station not received
SNTP-Uhr
(SNTP clock)
Connection to SNTP time server failed
UST-Al
(substation alarm)
Substation alarm. Connection to one or more substationsfailed
Table of contents