jcm-tech M42 User manual

M42
User Manual

Table of contents
Important safety instructions 3
Safety instructions for installation 3
Safety instructions for the use 4
Use of the equipment 4
Introduction 5
General description 5
Detailed description 5
Indication LEDs 6
Installation 7
Connections 7
Configuration 9
Options selector 9
Starting up 10
Door Positioning 10
Programming 11
Maneuver programming with two motors with slow speed 11
Maneuver programming with two motors without slow speed 12
Maneuver programming with one motor with slow speed 12
Maneuver programming with one motor without slow speed 12
Maneuver programming with absolute encoder (just motor 1) 12
Troubleshooting 13
Indicator light for possible faults, LED ERROR 13
Notes 15
Technical Data 16
Regulatory Data 16
EU Declaration of conformity 16
jcmtechnologies
2

Important safety instructions
Safety instructions for installation
Disconnect the power supply whenever you proceed to the installation,
maintenanceor repair of theequipment.
•Before installing the panel, remove all unnecessary ropes or chains and disable any equipment such as locks that is not
necessary for the automatic operation.
•Before installing the panel, check that the door is in good mechanical condition, correctly balanced and that it opens and
closes correctly.
•Install the manual unlocking device at a height lower than 1.8m.
•Install any permanent control next to the door away from any moving part and at a minimum height of 1.5m.
•For permanently connected equipment, an easily accessible power disconnection device must be incorporated into the wiring. It
is recommended that this be of the emergency switch type.
•If the control panel is supplied without emergency stop button, this will be incorporated in the installation, connecting it to the
STOP terminal.
•For correct use of the security edge, this must never be activated when the door is fully closed. It is wise to install the ends of run
before activating the edge.
•This equipment can only be handled by a specialist fitter, by maintenance staff or by a suitably trained operator.
•To connect the power supply and motor wiring, 2.5 mm2 section terminals must be used.
•Use protective goggles when handling the equipment.
•Fuses must only be handled when the appliance is disconnected from the mains.
•The instructions for using this equipment must remain in the possession of the user.
•European door normative EN 12453 and EN 12445 specify the following minimum protection and door safety levels:
- for single-family dwellings, prevent the door from making contact with any object or limit the force of contact (e.g. safety
band), and in the case of automatic closing, it is necessary to complement this with a presence detector (e.g. photocell).
- for communal and public installations, prevent the door from making contact with any object or limit the force of contact (e.g.
safety band), and complement this with a presence detector (e.g. Photocell).
M42 control panel switches automatically to dead man mode when safety devices are active or
defective. Therefore, all controls work as “hold-to-run” controls.
WARNING: IN ACCORDANCE WITH THE EN 13241-1 AND EN 12453-1 STANDARD
CONCERNING PRESSURE MAINTAINED CONTROL DEVICES:
“The person operating the door must have a direct view of the doorway, must be near the door (5 meters maximum) during
movement of the door and should not find itself in a dangerous position”. Any adjustment of the radio range out of these
recommendations, undertakes the installer in terms of responsibility for injury or damage.
“Releasing of the pressure maintained control device should stop the door movement before it scrolls 5cml”.
jcmtechnologies
3

Safety instructions for the use
•Do not allow children to play with the door controls.
•Keep the remote controls out of the reach of children.
•Watch the door movement and keep people away until the door is fully open or closed.
•Precaution when operating the manual unlocking device, as the door may suddenly fall due to the bad condition of the springs
or door unbalance. Details on how to use the manual unlocking device must be provided by the manufacturer or the device
installer.
•Examine the installation frequently, especially the cables, springs and supports, to detect signs of wear, damage or unbalance.
Do not use the door if repair work or adjustments are required, as this may cause damage.
Use of the equipment
Designed for automation of garage doors, in accordance with the general description. Not guaranteed for other uses. The
manufacturer reserves the right to alter equipment specifications without prior notification.
jcmtechnologies
4

Introduction
General description
Single-phase control panel with 2 motors with soft stop for residential and community use. Control by JCM, Elektromaten
or Kostal digital absolute encoder (motor 1 only) or by limit switches.
Detailed description
1- RECEIVER 12- 12/24VDC / TEST OUTPUT
Motion STICK receiver connector 2 outputs
12Vac/dc range: 11,4V to 12,6V
24Vac/dc range: 23,9V to 27,3V
2- MOTOR POWER 13- ELECTROLOCK
Electrolock 12Vdc output
3- EXPANSION CARD 14- FREE VOLTAGE OUTPUTS
TL-CARD-V / RSEC3 Connector Voltage-free outputs (voltage-free relay contacts, sup-
ply them at 110-230Vac or 12 / 24Vac / dc as desired)
4- DOOR POSITION BUTTONS 15- MOTOR 2 CONNECTION
Position open and close door for each motor Connection for motor 2
5- ALTERNATIVE BUTTON 16- MOTOR 1 CONNECTION
Start maneuver Connection for motor 1
6- PROGRAMMING BUTTON 17- POWER SUPPLY
(Maximum time: 6 min) 110V - 230Vac
50Hz - 60Hz
7- OPTION SELECTORS 18- EMERGENCY
(see"Connections") Emergency button connection
8- REMOTE CONNECTOR 19- FUSE
Connection for VERSUS-PROG programmer 6A/250V delayed
9- INPUTS 20- GARAGE LIGHT
Connection for inputs, limit switches or safety contacts
/ safety edges
Garage light output
10- INPUTS 21- EMERGENCY STOP
Encoder input Emergency stop input
11- INPUTS 22- 12/24Vdc SELECTOR
Connection for inputs, limit switches or safety contacts
/ safety edges
12Vdc or 24Vdc selector
jcmtechnologies
5

Indication LEDs
LED ON GREEN Led indicates control panel power supply
LED PROG RED Led indicates programming activation
LEDs INPUTS RED Leds indicate input activation
LEDs OUTPUTS GREEN Leds indicate output activation
LEDs MOTOR YELLOW Leds indicate activation of the motor movement button and direction
If Leds flash, they indicate slow speed
LED ERROR RED Led indicates errors (see "Troubleshooting")
jcmtechnologies
6

Installation
Install the control panel vertically on the wall at a height of 1.5m and following the assembly instructions.
Connections
POWERSUPPLYANDMOTORCONNECTIONS OUTPUTS
INPUTS
jcmtechnologies
7

PHOTOCELLCONNECTIONWITHAUTOTEST
ABSOLUTEENCODERCONNECTION
jcmtechnologies
8

Configuration
Options selector
By default all selectors leave the factory set to OFF.
OFF OPTIONSSELECTOR ON
Do not closes automatically 1- AUTOCLOSE Closes automatically
Normal speed in all the manoeuvre 2- SLOW SPEED Slow speed available at the end of
the manoeuvre
Enables the operation by end limit
switches 3- ABSENCODER/LIMITSW Enables the operation by ABS
encoder
Normal opening 4- REVERSE STRIKE Performs a reverse strike 2s before
opening the door
The safety contact performs its
formal function 5- CLOSE BY CSEG
The safety contact operates as a
close button once the vehicle has
passed
One motor (M1) operating 6- TWO MOTORS MODE Both motors operating (M1 and M2)
OFF OPTIONSSELECTOR ON
Start button performs an stop at
opening 7- NO REVERSE AT OPEN Start button opens until total open-
ing
The electrolock is activated 2s
before opening the door + 1s during
the opening
8- ELECTROLOCK The elctrolock is disabled
Test safety contact in opening dis-
abled 9- TEST CSEG OPEN Test safety contact in opening
enabled
Test safety contact in closing dis-
abled 10- TEST CSEG CLOSE Test safety contact in closing
enabled
Adds 3s after inversion in closing 11- ELECTROMEC/HYDR Do not adds time after inversion in
closing
Pushbutton in IN7 performs a start
button 12- OPEN/START Pushbutton in IN7 performs an
open button
jcmtechnologies
9

Starting up
Door Positioning
1PRESS PROGBUTTON 2PRESS MOTOR2 CLOSETO
CLOSEIN DM 3DOOR 2 CLOSES 4PRESS MOTOR1 CLOSETO
CLOSEIN DM
5DOOR 1 CLOSES 6PRESS PROGBUTTON 7LED TURNS OFF 8END DOOR POSITIONING
Considerations:
In step 2, if MOTOR2 CLOSEis pressed and the door opens, reverse the motor 2 wires, and return to step 1.
In step 4, if MOTOR1 CLOSEis pressed and the door opens, reverse the motor 1 wires, and return to step 1.
jcmtechnologies
10

Programming
Maneuver programming with two motors with slow speed
To program the door maneuver is necessary to use the PROG button to start programming and the START button to per-
form each step in the sequence.
1DOORS CLOSED 2SET OPTIONS 2&6 AT ON 3PRESS WHITE PROG
UNTIL LED ON 4PRESS BLACK START
BUTTON
5DOOR 1 OPENS ¤6PRESS START BUTTON ¤7DOOR 2 OPENS 8PRESS START BUTTON
*9DOOR 1 OPENS SLOW
SPEED *¤10PRESS START BUTTON *¤11DOOR 2 OPENS SLOW
SPEED *12PRESS START BUTTON
13DOOR 1 STOPS (OPENED) ¤14PRESS START BUTTON ¤15DOOR 2 STOPS
(OPENED) 16AUTOCLOSETIME
¤17PRESS START BUTTON ¤18DOOR 2 CLOSES 19PRESS START BUTTON 20DOOR 1 CLOSES
jcmtechnologies
11

*¤21PRESS START BUTTON *¤22DOOR 2 CLOSES SLOW
SPEED *23PRESS START BUTTON *24DOOR 1 CLOSES SLOW
SPEED
¤25PRESS START BUTTON ¤26DOOR 2 STOPS
(CLOSED) 27PRESS START BUTTON 28DOOR 1 STOPS (CLOSED)
29LED TURNS OFF 30END PROGRAMMING
Maneuver programming with two motors without slow speed
In step 2, set only the 6 option at ON.
Followthe above sequence without performing the steps marked with'*'.
Maneuver programming with one motor with slow speed
In step 2, set only the 2 option at ON.
Followthe above sequence without performing the steps marked with '¤'.
Maneuver programming with one motor without slow speed
In step 2, set options 2 and 6 at OFF.
Followthe above sequence without performing the steps marked with '* and/or ¤'.
Maneuver programming with absolute encoder (just motor 1)
In options selector, set option 3 at ON.
Followthe sequence of steps explained in previous points to program the door maneuver for a leaf.
The control panel will save the encoder position instead of storing time.
jcmtechnologies
12

Troubleshooting
Indicator light for possible faults, LED ERROR
ERROR LED ERROR INDICATION SOLUTION
Er 02 INTERNAL ERROR 10 slow flashes
2 quick flashes Internal error Consult the technical ser-
vice
Er 09 PROG TIME MAX 10 slow flashes
9 quick flashes
Programming time max-
imum
Program a maneuver
below the maximum
allowed time
Er 12 S.EDGE.CL
ERROR
1 slow flashes
2 quick flashes Closing safety edge error
Verify the security edge
band connections when
closing
Er 13 S.EDGE.OP
ERROR
1 slow flashes
3 quick flashes Opening safety edge error
Verify the security edge
band connections when
opening
Er 19 TEST.CL ERROR 1 slow flashes
9 quick flashes Closing auto test error
Verify that the security
device connected to the
security connection when
closing is in good con-
ditions and correctly
installed
Er 20 TEST.OP ERROR 2 slow flashes
10 quick flashes Opening auto test error
Verify that the security
device connected to the
security connection when
opening is in good con-
ditions and correctly
installed
Er 21 RSENS NC WHEN
PROG
2 slow flashes
1 quick flashes
Control panel pro-
grammed without RSENS
connected
Connect the RSEC card
and program the control
panel again
Er 22 RSENS NOT
FOUND
2 slow flashes
2 quick flashes
Control panel pro-
grammed with RSENS
connected and now it is
not connected
Program the control panel
again without RSEC or
connect the RSEC again
that was programmed to
the control panel pre-
viously
Er 23 RSENS PROG
ERROR
2 slow flashes
3 quick flashes
RSENS programming
error, are R and T paired?
Program the transmitter
RSENS to the RSEC
receiver card
Er 26 STOP 2 slow flashes
6 quick flashes
Control panel stopped by
an STOP
Verify that the STOP input
has been activated
Er 29 DOOR LOCKED
RSENS
2 slow flashes
9 quick flashes Closed door latch
Open the door's latch
before the opening man
oeuvre
jcmtechnologies
13

Er 30 RBAND NOT
FOUND
3 slow flashes
10 quick flashes
Control panel pro-
grammed with RBAND
connected and now it is
not connected
Program the control panel
again without using
RBAND or connect the
RBAND that was con-
nected to the control panel
previously
Er 31 RBAND NC WHEN
PROG
3 slow flashes
1 quick flashes
Control panel not pro-
grammed with RBAND
connected
Connect the RBAND card
and program the control
panel again
Er 32 FC NOT LEARNT 3 slow flashes
2 quick flashes
End of course learning
error
Verify the intern motor limit
switches
Er 33 ERROR SYNC
RSENS
3 slow flashes
3 quick flashes
Synchronization error
between the receiver and
the transmitter
Program the transmitter
RSENS to the RSEC
receiver card
Er 36 RSENS RADIO
ERROR
3 slow flashes
6 quick flashes
Detection through open-
ing current
Verify the batteries of the
RSENS emitter id they are
charged, verify the radio
signal with the Check func-
tion
Er 39 CTROL PANEL
BLOCKED
3 slow flashes
9 quick flashes
Control panel cannot
enter programming
because it is blocked.
Enter the password with
V-DPLAY or VERSUS-
PROG for unlocking the
control panel.
jcmtechnologies
14

Notes
jcmtechnologies
15

Technical Data
Parameter Value
Power supply 110Vac - 230Vac ; 50Hz / 56Hz
Maximum motor power 1,2kW for each motor
Maximum motor intensity 6A for each motor
Optional cards RSEC3, TL-CARD-V
Receiver card connector Motion STICK
Voltage-free outputs Garage light and flash
12Vdc/1A output Electrolock
24Vac / 24Vdc / 24Vdc TEST outputs Accessories power supply / Photocells test (shared 2A)
ENCODER connector Connector for absolute encoder
Operating temperature -20ºC --- +55ºC
Watertighness IP54
Size 285x225x92mm
Regulatory Data
EU Declaration of conformity
JCM TECHNOLOGIES, S.A. declares that the product M42 complies with the relevant fundamental requirements of the
Machine Directive 2006/42/EC as well as with the Directives 2014/30/EU on electromagnetic compatibility and
2014/35/EU regarding low voltage whenever its usage is foreseen; and with the 2011/65/EU RoHS Directive.
See website https://www.jcm-tech.com/declarations/
JCM TECHNOLOGIES, SA
C/COSTA D'EN PARATGE, 6B
08500 VIC (BARCELONA)
SPAIN
jcmtechnologies
16
UM_3201602_M42_EN_Rev00
Table of contents
Other jcm-tech Control Panel manuals
Popular Control Panel manuals by other brands

Swegon
Swegon CASA Smart Sensor Installation

Honeywell
Honeywell Symphony Frequently asked questions

Victron energy
Victron energy Skylla-i Control GX manual

Beckhoff
Beckhoff CP29xx-0000 Series Installation and operating instructions

RCS
RCS UPM-421 operating instructions

SLEIPNER MOTOR AS
SLEIPNER MOTOR AS 8700 installation guide