Jiangsu GoodWe Power Supply Technologu Co. SS series User manual

User Manual
GOODWE SS SERIES

Table of Contents
1 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 01
2 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 02
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
3.1 Mounting Instruction . . . . . . . . . . . . . . . . . . . . . . . . . 04
3.2 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 04
3.3 Equipment Installation . . . . . . . . . . . . . . . . . . . . . . . . 06
3.4 Electrical Connection . . . . . . . . . . . . . . . . . . . . . . . . . 09
3.5 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4 System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.1 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.2 Indicator Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.3 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.4 Error Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 Technical Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
GW1500-SS GW2000-SS GW3000-SS . . . . . . . . . . . . . . 33
GW4000-SS GW4600-SS . . . . . . . . . . . . . . . . . . . . . . . . 36
6 Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.1 Warranty Period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.2 Warranty Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.3 Warranty Conditions . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.4 Scope of Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
8 Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

- 1 -
1 Symbols Caution! - Failure to observe a warning
indicated in this manual may result in minor or
moderate injury.
Danger of high voltage and electric shock!
Danger of hot surface!
Product should not be disposed as normal
household waste.
This side up- The package must always be
transported, handled and stored in such a way
that the arrows always point upwards.
Components of the product can be recycled.
Fragile-The package/product should be
handled carefully and never be tipped over or
slung.
Stack limitation-6 or 7 units of identical
packages that may be stacked in maximum.
Keep dry –The package/product must be
protected from excessive humidity and must
accordingly be stored under cover.
CE Mark
Residual voltage exists in the inverter; the
inverter cannot be maintained within 5
minutes until the capacitor is fully discharged.

- 2 -
2 Safety
SS series inverter of Jiangsu GoodWe Power Supply Technology
Co.,Ltd. ( hereinafter referred to as GoodWe ) strictly conforms to
related safety rules in design and test. As electric and electronic
equipment, Safety Regulation shall be followed during installation
and maintenance. Improper operation may bring severe damage to
the operator, the third party and other properties.
The installation and maintenance of the inverters must be
performed by qualified personnel only in compliance with
national and local standards and regulations.
Before installation and maintenance, DC input and AC output of
the inverter should be cut off beforehand and the inverter cannot
be touched within 10 minutes after power cut-off in case of
electric shock.
Partial temperature of the inverter may exceed 60℃during

- 3 -
operation, please do not touch in case of scalding.
All electric installation should conform to local electric standard
and permission has to be obtained from local power supply
department before synchronization by qualified personnel.
Children must be kept away from inverters.
Please do not open the front cover of inverter. Apart from wiring
terminal, touching or changing components without
authorization may cause damage to people and inverters.
GoodWe may deny the obligation of warranty service
accordingly.
Static electricity may damage electronic components and proper
measures shall be adopted to avoid static electricity.
The output voltage of proposed PV array should be lower than
the inverter maximum rated input voltage; otherwise, GoodWe
will not undertake any obligations and warranty services.

- 4 -
3 Installation
3.1 Mounting Instruction
A In order to achieve optimal performance, the ambient
temperature should be lower than 45 °C .
B For the convenience of checking the LCD display and
possible maintenance activities, please install the inverter at
eye level.
C Inverters should NOT be installed near inflammable and
explosive items. Any electro-magnetic equipment should be
kept away from installation site.
D Product label and warning symbol shall be clear to read after
installation.
3.2 Unpacking
When you receive GoodWe inverter, please check if there is any
visible external damage on the inverter or any accessories. Please
also check if there is anything missing according to the list below.
Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Wall-mounted bracket . . . . . . . . . . . . . . . . . . . . . . . . . 1
Lock Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Positive DC Plug (GW1500-SS) . . . . . . . . . . . . . . . . . . 1
Negative DC Plug (GW1500-SS). . . . . . . . . . . . . . . . . 1
Positive DC Plug (GW2000-SS / GW3000-SS). . . . . . . 2
Negative DC Plug (GW2000-SS / GW3000-SS) . . . . . . 2

- 5 -
Positive DC Plug (GW4000-SS / GW4600-SS). . . . . . . 3
Negative DC Plug (GW4000-SS / GW4600-SS). . . . . . 3
Unlock Tool for DC Plug . . . . . . . . . . . . . . . . . . . . . . . 1
AC Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
USB Data Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Expansion Bolt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Flat Head Screw for Lock Plate and RS485 Cover. . . . . . 5
User Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Warranty Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Wall-mounted Bracket Positive DC Plug Negative DC Plug Unlock Tool for DC Plug
AC Plug USB Data Cable Expansion Bolt Lock Plate
Flat Head Screw User Manual Warranty Card PV inverter

- 6 -
3.3 Equipment Installation
3.3.1 Selecting the installation position
Installation position should be selected based on the following
aspects:
The installation method and mounting location must be suitable
for the inverter's weight and dimensions.
Mount on a solid surface.
Select a well ventilated place sheltered from direct sun radiation.
Install vertically or tilted backward by max 15°. The device
cannot be installed with a sideways tilt. The connection area
must point downwards.
Figure 3.3.1-1

- 7 -
In consideration of heat dissipation and convenient
dismantlement, the minimum clearances around the inverter
should be no less than the following value:
Upward . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300mm
Downward . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500mm
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300mm
Both sides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200mm
Figure 3.3.1-2
3.3.2 Mounting Procedure
AUse the wall-mounted bracket as a template and drill 7 holes
on the wall, 10 mm in diameter and 80 mm deep.

- 8 -
Figure 3.3.2-1
BFix the wall mounting bracket on the wall with the expansion
bolts in accessory bag.
CCarry the inverter by holding the groove on the heat sink.
Figure 3.3.2-2
DPlace the inverter on the wall-mounted bracket (as illustrated
below).

- 9 -
Figure 3.3.2-3 Figure 3.3.2-4
Figure 3.3.2-5
E Insert lock plate into two holes in the heat-sink, then fix the
inverter with a padlock and screw M3x8
Figure 3.3.2-6
3.4 Electrical Connection
The inverter is compatible with RCD and RCM.

- 10 -
The DC component may produce electricity; as a result, a residual
current operated protective (RCD) or monitoring device (RCM)
will be used for protection in case of direct or indirect contact, only
Type B RCD/RCM is allowed to be connected to the supply side of
the product.
3.4.1 Connection to grid (AC side Connection)
ACheck the grid (utility) voltage and frequency at the
connection point of the inverter. It should be 230VAC (or
220VAC), 50/60Hz, and single phase.
BDisconnect the breaker or fuse between PV-Inverter and utility.
CConnect the inverter to the grid as follows:
Switch off the AC Breaker.
Disassemble female connector of the AC wire connector
and connectAC wires to connection socket as indicated.
Figure 3.4.1-1
Insert Line wire to Pin 1, Neutral wire to Pin 2 and Ground
wire to Pin

- 11 -
Figure 3.4.1-2
After fastening all screws, reassemble the female
connector of theAC wire connector.
Connect the female connector of the AC wire connector to
the Male connector on the inverter.
DSpecifications of the AC wires:
Figure 3.4.1-3
Depiction
Size
A External diameter of the wire
12mm-25mm
B Sectional area of conducting materials
Max.6mm2
C Length of bare wire
Approx.10mm

- 12 -
E AC output connection diagram
Figure 3.4.1-4
3.4.2 DC side connection
AMake sure the maximum open circuit voltage (Voc) of each PV
string does not exceed the inverter input voltage Vmax under
any condition.
BUse Multi-contact connectors for PV array terminals.
CConnect the positive and negative terminals of the PV panel to
corresponding terminals on the Inverter. The DC terminal on
each Inverter can bear 20ADC current.

- 13 -
Female side connector (PV+) Male side connector (PV-)
both types of connectors must be equipped in pair strictly
according to above graphs

- 14 -
Figure 3.4.2-1 Separated by Ring tool
Before connecting the PV panels, please ensure the plug
connectors have the correct polarity. Incorrect polarity
connection could permanently damage the unit.

- 15 -
Checks short-circuit current of the PV string. The total short-
circuit current of the PV string cannot exceed the inverter’s
maximum DC current.
High voltage exists when the PV panel is exposed to the sun.
Please secure the terminal connection, and do NOT touch any
exposed components in case of electric shock.
3.4.3 RS485 Communication
RS485 interface is used for multipoint communication. EzLogger
can monitor and communicate with 50 inverters at the same time.
But the maximum length of the cable should not exceed 1000 m.
All the inverters, which communicate through one cable, should
use provided RS485 interface (a piece of 10# cable is recommend
to be connected for waterproofing without RS485 cable
connection). The typical inverter connection graph through RS485
is shown below.
Figure 3.4.3-1

- 16 -
The graph below shows the monitoring system connection, in
which inverters’ multipoint communication can be realized
through RS485 interface. The software “EzExplorer” used in PC
end can realize real-time monitoring of 16 EzLoggers at the same
time.
Figure 3.4.3-2
Pins of RS485 of GoodWe SS series:

- 17 -
AConnection procedure:
a. Screw off the RS485 cover;
b. Remove the screw cap of the cable gland;
c. Remove one-hole sealing ring;
d. Put RS485 cable through the components in this order:
screw cap, one-hole sealing ring, gland body;
e. Compress the crystal head and insert it into corresponding
interface;
f. Fasten the waterproof of RS485 Cover;
g. Fasten the screw cap of the cable gland.
Figure 3.4.3-3

- 18 -
BRS485 cable is composed by eight wires with different colors.
Chop the envelope outside to expose the eight wires, then
straighten the end of every wire, and put them in order.
Figure 3.4.3-4
CThe connection between crystal connectors and RS485 wires
must be corresponding with each other, as shown in the table
below.
Figure 3.4.3-5
DPlug the eight wires into corresponding slots of the crystal
connector, and then fix them up using special tool below.
Table of contents
Other Jiangsu GoodWe Power Supply Technologu Co. Inverter manuals
Popular Inverter manuals by other brands

Autarco
Autarco UX Series Installation and operation manual

Huawei
Huawei SUN2000-100KTL user manual

Sensata
Sensata Magnum Energy CSW3012-X owner's manual

Tycon Power Systems
Tycon Power Systems RemotePro RPST-2424 Quick install guide

Trace Engineering
Trace Engineering TS - manual

Rayleigh Instruments
Rayleigh Instruments RI-ENERGYFLOW-MODULAR Series user manual