1
SCV Series UPS Quick Install Procedure
Please read all of the WARNINGS, CAUTIONS and the User’s Manual before attempting to install or service the UPS.
To download the SCV User’s Manual, please go to our web site at:
www.juicegoose/resources/manuals
WARNING: This UPS contains potentially hazardous voltages. Risk of Electrical shock. The internal batteries energize
hazardous live parts inside this UPS even when the AC input power is disconnected.
NOTE: Installing or Servicing of the UPS must be performed by Qualified Service Personnel ONLY. Juice Goose accepts no liabilities and is not
limited to: injury to the Service Personnel, or damages to; the UPS, or the connected equipment caused by the incorrect installation or servicing
of the UPS.
NOTE: These UPSs are shipped with the batteries disconnected. The batteries must be connected before putting these UPSs into service.
CAUTION: The battery system can present a risk of electrical shock. These batteries produce sufficient current to burn wire or tools very
rapidly, producing molten metal. Observe these precautions when installing or servicing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the battery
terminals.
6. Determine if the battery is inadvertently grounded. If the battery is, remove the
source of the grounding. Contact with any part of a grounded battery can result in
an electrical shock. The likelihood of such shock will be reduced if such grounds are
removed during installation and maintenance.
INSTALLATION
Be sure to read the installation placement and all the cautions before installing the UPS. These UPS are shipped with the internal batteries
disconnected. The batteries must be connected before putting these UPS into service. See the "Connecting the Batteries" procedure to connect
the batteries and then the "Rackmount Configuration" to install the UPS into the rack. USE CAUTION: The UPS is heavy. Use the appropriate
number of personnel when installing the UPS.
CAUTION! DO NOT USE THE MOUNTING BRACKETS TO LIFT THE UPS. The mounting brackets are ONLY for securing the UPS to the
rack.
CONNECTING THE BATTERIES
(QUALIFIED SERVICE PERSONNEL ONLY)
Please read all of the WARNINGS and CAUTIONS before attempting to connect the batteries.
WARNING: Use two or more people when installing the UPS, the UPS is extremely heavy.
1. Remove the UPS from the shipping box and place on a flat surface.
2. Grasp the battery door on the left-hand side, pull it outward and then set it aside (FIG. 1).
3. Press the spring-loaded latch on the battery retaining bracket on the left-hand side, pull it outward and then set it aside (FIG. 2)
4. Press down to unlock the battery connector holders (FIG. 3).
5. Verify proper polarity. Connect the battery connectors (red and black) together. Place the battery connectors in the battery connector
holder and then relock the battery connector holders (FIG. 3).
NOTE: Some sparking may occur this is normal.
6. Re-install the battery retaining bracket.
7. Re-install the battery door on the UPS.
8. Connecting the Batteries is complete. See the Rackmount Configuration.