Jung RTR231 User manual

Room thermostat (heating/cooling) 230 V
Room thermostat (heating/cooling) 230 V
Art. no.: RTR231
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the device or load. In
so doing, take all the circuit breakers into account, which support dangerous voltages to the
device and or load.
This manual is an integral part of the product, and must remain with the end customer.
2 Device components
Figure1: Device components
(1) Room temperature controller insert
(2) Cover frame
(3) Status LED
(4) Central plate
(5) Control knob
(6) Internal temperature sensor
(7) Adjustment rings temperature limit
During renovation work, the temperature sensor (6) must not become dirty or be painted
over.
3 Intended use
– Electronic room temperature controller for controlling electrothermal valve drives for
230 V~
– Control of the room temperature in closed rooms
– Mounting in appliance box with dimensions according to DIN 49073
4 Product characteristics
– Manually setting a comfort temperature
– Manually switching off the temperature control
– Input terminal for activation of ECO temperature via central clock
1 / 8
82404003 04.05.2022
J0082404003

Room thermostat (heating/cooling) 230 V
– Input terminal for activating the cooling mode via central control
– Internal temperature sensor
– Frost protection function
– Silent switching
– Temperature drop detection (adjusting to frost protection temperature when window is
opened)
– Controller output working method: pulse width modulation (PWM) or two-point switchable
– Adaptation to valve type (deenergised opened or deenergised closed, switchable)
– Offset adjustment (correction value for measured temperature)
– Valve protection function (once a week opening and closing of valve)
– Permanent LED operation possible
5 Functional description
ECO operation
In many areas of the building it makes sense for the temperature to be set to a lower ECO tem-
perature at certain times rather than to heat permanently to the comfort temperature. By con-
necting the input terminal Ø to 230 V, the temperature is reduced by 4 °C and the status LED
lights up green. This should be controlled by a central clock. In cooling mode, the wiring of the
input terminal Ø is ignored.
Cooling mode
Modern heat pump systems often also provide the option of cooling rooms. In cooling mode, it is
possible to change the cooling temperature using the control knob.
Switching between heating and cooling mode is done via the control knob or by wiring the input
terminal “C” with 230 V.
Temperature drop detection
In the event of a sharp drop in temperature, e.g. after opening a window, the system regulates
to the frost protection temperature of 5°C for a maximum of 30 minutes. Pressing or turning the
control knob cancels the operation.
Offset
This function allows the adjustment of the position of the control knob so that it corresponds to
the room temperature. Thus, the indication of the temperature via the control button is compar-
able in different rooms. An adaptation of up to +/- 3°C is possible.
Controller adaptation
Depending on the heating system, the control behaviour can be adjusted.
Pulse width modulated control (factory setting): Optimised for electrothermal valve drives (see
Technical data): The output is not permanently actuated, but for a time period (pulse width) that
depends on the difference between setpoint and actual temperature. This method brings the ac-
tual temperature gradually closer to the setpoint temperature.
Two-point control: The output remains switched on until the selected setpoint temperature has
been exceeded by 0.5 °C. The output will not be switched on again until the setpoint value is
undercut by 0.5 °C. Since most heating systems respond very slowly, this type of control can
entail temperature overshooting.
Setting the valve type
Depending on the electrothermal valve drive used, an adaptation to the valve type must be
made. There are valve drives where the valve is opened (deenergised opened) or closed (deen-
ergised closed, factory setting) when no supply voltage is applied.
2 / 8
82404003 04.05.2022
J0082404003

Room thermostat (heating/cooling) 230 V
6 Operation
Brief overview
Function Control knob Status LED * LED colour
Change room temper-
ature
... turn right or left maximum 2
minutes
Red = heating mode
green = ECO heating mode
Blue = cooling mode
Orange = frost protection (10
seconds)
Display operating
mode
... press briefly 10 seconds. Red = heating mode
green = ECO heating mode
Blue = cooling mode
Orange = frost protection
* In permanent operation, the status LED lights up continuously during the active heating or
cooling phase, but with reduced brightness.
Increasing or reducing the room temperature
■ Turn the control knob to the right or left.
If the setpoint temperature is not reached, the LED lights up for a maximum of 2 minutes
in the colour of the current operating mode. The indication can also take place during the
entire heating/cooling process (see Activate/deactivate permanent LED operation).
In the middle position, the device regulates to approx. 20 °C setpoint temperature. The
room temperature reached depends on the installation location of the device and the am-
bient conditions. The lowest setpoint temperature is approx. 5 °C and the highest setpoint
temperature is approx. 30 °C
Indication of the current operating mode
■ Press the control knob briefly.
The LED lights up for 10 seconds in the colour of the current operating mode.
Red = heating mode, green = ECO heating mode, blue = cooling mode, orange = frost
protection.
Switching off the temperature control
■ Press the control knob for longer than 2 seconds until the LED lights up orange.
The device has switched to frost protection. The frost protection prevents the temperature
from falling below 5 °C.
Each time the control knob is turned, the LED lights up orange for 10 seconds.
■ To activate the temperature control, press the control knob again for more than
two seconds.
The device switches back to the previous operating mode. The LED lights up for
10 seconds.
Manual switching between heating and cooling mode
If 230 V is present at the input terminal C, manual switching to heating mode is not pos-
sible.
■ Press the control knob for longer than 4 seconds until the LED flashes red in active heat-
ing mode, flashes green in ECO heating mode or flashes blue in cooling mode.
■ Briefly press the control knob again to change the operating mode.
■ Press the control knob for longer than one second until the LED lights up continuously to
accept the displayed operating mode.
After 10 seconds without actuation, the displayed operating mode is automatically adop-
ted.
3 / 8
82404003 04.05.2022
J0082404003

Room thermostat (heating/cooling) 230 V
Calibrating the actual and setpoint temperature
To see which rotary switch position corresponds to the current temperature, proceed as follows.
■ Heating mode: Turn the rotary switch slowly anticlockwise when the heating phase is act-
ive (LED lights up red).
■ Cooling mode: Turn the rotary switch slowly clockwise when the cooling phase is active
(LED lights up blue).
When the current temperature is reached, the LED goes out.
Activate/deactivate permanent LED operation
The status LED lights up with reduced brightness during the active heating or cooling phase.
■ Press the control knob for longer than 10 seconds until the LED lights up or flashes in the
colour magenta.
LED lights up magenta = permanent operation is active
LED flashes magenta = permanent operation is inactive (default setting)
■ Press the control knob briefly to switch the mode.
■ Press the control knob for more than one second or wait 10 seconds to adopt the dis-
played mode.
7 Information for electrically skilled persons
Selecting a suitable installation location
– Recommended installation height: 1.50 m on interior walls
– Do not mount the device near sources of interference, such as ovens, refrigerators,
draughts (e.g. next to the door) or direct sunlight. This affects the temperature measure-
ment of the internal temperature sensor.
– Do not mount the device within shelf walls or behind curtains and similar covers
– Do not use the device in multiple combinations with heat-generating devices such as dim-
mers
DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
4 / 8
82404003 04.05.2022
J0082404003

Room thermostat (heating/cooling) 230 V
Connecting and fitting the device
Figure2: Connection example of the insert
Figure3: Clampable conductor cross-section
■ Connect electrothermal valve drive (10) to insert (1) according to connection diagram
(Figure 2). Observe the conductor cross-sections (Figure 3).
■ Optionally, connect the ECO operation input Ø via a switching contact of a central clock
(8).
If 230 V is applied to the input, the setpoint temperature is reduced by 4 °C, exclusively in
heating mode.
■ Optionally, connect the cooling input C via a switching contact of the heating system (9).
If 230 V is applied to input C, the cooling mode is active. If 230 V is switched off, the
device automatically switches to heating mode.
After each switchover, the LED lights up for 10 seconds in the colour of the current oper-
ating mode.
■ Fit device in appliance box; terminals must be at the bottom.
■ Fit the frame, central plate and control knob.
■ Switch on mains voltage.
The unit calibrates itself within the first 90 minutes. Control deviations are possible during
this period.
5 / 8
82404003 04.05.2022
J0082404003

Room thermostat (heating/cooling) 230 V
7.1 Commissioning
Setting the control mode and valve type
Default setting:
– Pulse width modulated control (PWM)
– Valve type deenergised closed (NC)
This setting can be used with most heating systems without adaptation.
Changing the settings
■ Press the control knob for longer than 20 seconds.
The LED flashes green for PWM control and green/blue for 2-point control.
■ Press the control knob briefly: The control behaviour is changed.
■ Press the control knob for longer than one second: The control behaviour is saved.
Adapting the valve type.
The LED flashes red for valve type “deenergised closed” (NC) and red/blue for valve type
“deenergised opened” (NO).
■ Press the control knob briefly: The valve type is changed.
■ Press the control knob for longer than one second: The valve type is saved.
The setting mode is exited automatically.
After approx. 2 minutes without any operation the menu is exited without saving.
Setting the temperature limits
The room temperature controller has a setting range of 5 ... 30 °C. The adjustment rings on the
central plate can be used to limit the temperature setting range.
Figure4: Setting the temperature limit (before/after)
■ Pull the control knob off the central plate so that the adjustment rings are visible
(Figure 4).
Pulling off is done by hand or with a suitable tool, e.g. vacuum lifting tool or key cap puller.
6 / 8
82404003 04.05.2022
J0082404003

Room thermostat (heating/cooling) 230 V
■ Turn the large blue adjustment ring clockwise to the desired minimum temperature. Each
notch corresponds to a change of about 1°C.
■ Turn the small red adjustment ring anticlockwise to the desired maximum temperature.
The respective adjustment ring can only be turned in one direction. To return to the ori-
ginal setting, continue turning to the respective position.
■ Replace the control knob, observing the coding (Fig. 4, bottom) of the control knob and
rotary axle.
Setting the offset
This function allows the adjustment of the position of the control knob so that it corresponds to
the room temperature. Thus, the indication of the temperature via the control button is compar-
able in different rooms. An adaptation of up to +/- 3°C is possible.
This setting is only possible if the lower temperature limit has not been raised by the blue
setting ring (see Setting the temperature limits).
Precondition: The desired setpoint temperature has been reached in the room.
■ Turn the control knob to 5 °C (left stop) and press twice in quick succession (double-
click).
The LED flashes quickly, alternately red and green.
■ Turn the control knob to the desired position for the current room temperature and press it
for longer than one second.
The control knob position is saved and the LED lights up green for 5 seconds.
If the LED flashes red for 5 seconds, the change was greater than +/- 3 °C and the adapt-
ation is discarded.
8 Technical data
Rated voltage AC 230 V ~
Mains frequency 50 / 60 Hz
Standby power max. 0.5 W
Connected load 20 W
Connection: Thermal valve drive 230 V, art. no. TSA230NCWW
Number valve drive 1 ... 10
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Cable length inputs max. 100 m
Controller class (EU 811/2013) IV
Contribution to energy efficiency 2%
9 Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.
7 / 8
82404003 04.05.2022
J0082404003

Room thermostat (heating/cooling) 230 V
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle
GERMANY
Telefon: +49 2355 806-0
Telefax: +49 2355 806-204
www.jung.de
8 / 8
82404003 04.05.2022
J0082404003
Table of contents
Other Jung Thermostat manuals
Popular Thermostat manuals by other brands

Kemo
Kemo M169A Connection Example

AMX
AMX ViewStat Operation/reference guide

Larson Electronics
Larson Electronics EXP-TSTAT-125.250-60.250F-0.25-V1-15L instruction manual

NOVASTAT
NOVASTAT EL QUATTRO RT-ELQ Installation

OJ Electronics
OJ Electronics OCD6-1999 instructions

Peco
Peco T180 Technical specifications

LATICRETE
LATICRETE STRATA-HEAT TDS 408 troubleshooting guide

Z-Wave
Z-Wave CT100 Operation guide

ThermoLife
ThermoLife 84 Series instructions

Lux Products
Lux Products Smart Temp TX9100U Installation and operating instructions

tado°
tado° Smart Thermostat installation guide

Vtronix
Vtronix TF85L –10011 installation manual