Commisioning
When co issioning the first ti e, start values
are loaded into the device. Then it requires to
enter the nu ber of steps. In this case, the
screen on the right side will be displayed. The
nu ber of step is set-up to the required value
by the direction keys and “Apply” is selected. In
case “Okay” key is pressed, saves the change.
Or, in case no key is pressed, when the ti e is
over on the screen, it switches to the section
in which the current transfor er ratio is
inserted by taking 12 steps in the e ory.
1 2 3 4 5 6 7 8 9 10 11 12
nter number of step
seconds
20
12
Apply▲ + ▼ - ◄
1 2 3 4 5 6 7 8 9 10 11 12
nter number of step
seconds
20
18
CancelOkay xit
Save
Changes?
12345678910 11 12
nter current transformer Value
seconds
30
00500 / 5A
Apply▲ + ▼ - ◄
1 2 3 4 5 6 7 8 9 10 11 12
Insert current transformer Value
seconds
20
CancelOkay Back
00500 / 5A
Save
Changes?
The line on which the blue bar locates, is set-
up to the required value by using the direction
keys and switch to the next side by pressing
the left direction key. Inserting the co plete
pri ary value, “Apply” key is pressed. In case
of pressing “Okay” key, the change is saved.
1 2 3 4 5 6 7 8 9 10 11 12
searching for current
transformer direction ... 5
Main MenuPlease wait
R S T ????????
Switch on loads
For all phases
1 2 3 4 5 6 7 8 9 10 11 12
Seaeching for current
transformer directions...
Main Menu
Current Flow dir. not Detected
- Make sure all
phases have loads
- Check voltage and
current inputs
!
The device auto atically switches to the
internalization of current polarity direction
ode. In this case, it is required to draw
enough current fro each phase. If enough
current can not be drawn fro any phase, the
device warns as “current flow direction not
detected” and shows the phase or phases
which are not internalized by ??? arks. When
the current polarity direction are internalized,
the device switches to the auto atic capacitor
power internalization ode.
P.S.: There is no need to press on the ain
screen key nor ally.
1 2 3 4 5 6 7 8 9 10 11 12
Main MenuPlease wait
Rdetected
R
1 Step : Number of Steps
2 Step : Current Transformer Ratio
3 Step : Determine of Current Transformer Directions
1 2 3 4 5 6 7 8 9 10 11 12
Kvar
Make internalizeMain Screen
R S
Detecting step powers... 10:00
Please close the variable loads in the system.
S1 -1.0
Device tries to identify capacitor powers, by
activating and then re oving the steps in
sequence. It is reco ended the closure of
variable loads in the syste to ensure instant
internalization during this process. If required,
the user presses the “Make the steps
internalize” key and can ake the syste
internalize by hi self. The auto atic
internalization is put on hold in the eanti e.
The step is not internalized auto atically as
long as the user is in the “Make the steps
internalize” enu.
P.S.1: There is no need to press on the ain
screen key nor ally.
P.S.2: Despite of the variable loads are
disabled, the connections of the device should
be checked again in case any power of the
steps and their connections are not intenalized
for a long ti e.
4 Step : Learning of step powers
When all the steps are internalized, the ain
screen page co es up and the device starts
operating in auto atic ode.
5 Step (Main Screen)
searching for current
transformer directions ... 5
R S T ????????
S T
T
S2 -2.5