KAZE APPLIANCES SE90TL2 User manual

WARNING
READ AND SAVE THESE INSTRUCTIONS
Installer: Leave this manual with the homeowner.
CAUTION
CLEANING & MAINTENANCE
OPERATION
PLAN THE INSTALLATION
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.
2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.
DO NOT MOUNT THIS PRODUCT IN A WALL.
3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off
power unit.
4. Please read specification label on product for further information and requirements.
For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit
with the dusting brush attachment.
The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noi-
ses, replace the motor with the exact service motor. The impeller should also be replaced.
The fan, light, and night light can be operated separately. Use a 3-function wall control. See “Connect Wiring” for details.
1. Do not use in a cooking area.
2. Two ways to connect ductwork to a factory-shipped unit.
ROOF CAP*
(with built-in
damper)
ROUND
DUCT* WALL CAP*
(with built-in
damper)
*Purchase
separately
POWER
CABLE*
INSULATION*
(Place around and
over Fan Housing.)
Seal gaps
around
Housing.
FAN
HOUSING
ROUND
ELBOW(S) *
Seal duct
joints with
tape.
Keep duct
runs short
MODEL: SE90TL2 SE110L2
VENTILATION FAN
a). Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
b). Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent
power from being switching on accidentally. When the service disconnecting means cannot be locked, securely fasten a
prominent warning device, such as a tag, to the service panel.
c). Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and
standards, including fire-rated construction codes and standards.
d). Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning
equipment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as
those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration
and Air Conditioning Engineers (ASHRAE), and the local code authorities.
e). When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
f). Ducted fans must always be vented to the outdoors.
g). Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch
circuit (ceiling installation only).
h). This unit must be grounded.
i). Not for Use in Kitchens.
j). To reduce risk of fire and to properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces within
walls or ceilings or into attics, crawl spaces, or garages
k). WARNING: To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State Speed Control
Device.
l). The fan must not be installed in a ceiling thermally insulated to a value greater R40.

Hold the housing so that it is in contact with the bottom of the joist. Attach
the housing with four (4) screws to the joist through the holes in each
mounting flange.
1. MOUNT HOUSING TO JOIST OR I-JOIST.
NAIL
DUCT
2. MOUNT WITH HANGER BARS
2a. Sliding hanger bars have been provided, which allow the housing to
be positioned accurately anywhere between the framing. The bars span
up to 24 in. and can be used on all types of framing: I-joist, standard joist,
and truss construction. Slide hanger bars onto housing and adjust as
needed to fit between framing.
2b. Extend the hanger bars to the width of the framing. Position the
ventilator with the hanger bar tabs wrapped around the bottom edge of
the framing, holding the ventilator in place.
Secure hanger bars to framing using one screw on each end of hanger bar.
Select a proper hole and secure the hanger bars together using flange
screws.
3. ATTACH DAMPER/DUCT CONNECTOR
Snap the damper/duct connector onto the fan housing. The connector
must be flush with the top of the housing, and the damper flap should
fall closed.
TYPES OF TYPICAL INSTALLATIONS
ASSEMBLY INSTRUCTIONS
1. Housing mounted to I-joists (Start at “ASSEMBLY INSTRUCTIONS 1”)
2. Housing mounted to joists (Start at “ASSEMBLY INSTRUCTIONS 1” )
3. Housing mounted to truss (Start at step “ASSEMBLY INSTRUCTIONS 2”)
SCREW
2
HANGER
BAR

4. INSTALL ROUND DUCTWORK
Connect the round ductwork (not included) to the damper/duct connector,
and run the ductwork to a roof or wall cap (not included). Using tape (not
included), secure all the ductwork connections so that they are air tight.
Run 120 V AC house wiring to the location of the fan. Use only UL-approved connectors (not included) to attach the house wiring to the
wiring plate. Refer to the wiring diagram, and connect the wires as shown.
ASSEMBLY INSTRUCTIONS
CONNECT ELECTRICAL WIRING
INSTALL GRILLE
3
Install ceiling material to complete the ceiling construction.
Then, cut around the fan housing.
To attach the grille assembly to the fan housing, Insert the light plug from the
grille assembly into the wire panel. Pinch the grille springs on the sides of the
grille assembly, and position the grille into the housing with the grille springs
in the appropriate slots. Push the grille assembly towards the ceiling to secure.
UNIT
BLACK (BLK)
NIGHT
LIGHT
LIGHT
SWITCH BOX
FAN
120V AC LINE IN
GROUND (GRD)
RED
WHITE (WHT) BLUE (BLU)
FAN
RECEPTACLE
LIGHT
RECEPTACLE
WIRE
PANEL
The ducting from this fan to the outside of building has a strong effect on
the air flow, noise and energy use of the fan. Use the shortest, straightest
duct routing possible for best performance, and avoid installing the fan with
smaller ducts than recommended. Insulation around the ducts can reduce
energy loss and inhibit mold growth. Fans installed with existing
ducts may not achieve their rated air flow.

This warranty covers all defects in workmanship or materials for:
The mechanical and electrical parts contained in this product, for a period of 12 months, from the date of purchase. You
must keep and be able to provide your original sales receipt as proof of the date of purchase. This warranty is covered
the original retail purchaser of this product. The manufacturer will repair or replace, in your home, any mechanical or
electrical part which proves defective in normal household use for a period of 12 months.
THIS WARRANTY DOES NOT COVER:
• Damages from improper installation
• Damages from shipping
• Damages from misuse, abuse, accident, alteration, lack of proper care and maintenance
• Damages from service by persons other than an authorized dealer or service center.
• Labor, service, transportation and shipping charges for the removal of defective parts and for installation of a replacement
part, beyond the initial 12-month period.
This warranty does not extend to fluorescent lamp starters and tubes.
THIS LIMITED WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy provided in this warranty is exclusive and is granted in lieu of all other remedies. This warranty does not cover
incidental or consequential damages. Some states do not allow the exclusion of incidental or consequential damages, so
this limitation may not apply to you. Some states do not allow limitations on how long an implied warranty lasts, so this
limitation may not apply to you. This warranty gives you specific legal rights, and you may also have other rights, which
vary from state to state.
WARRANTY
SERVICE PARTS
* Blower Assembly includes part 6, 5, d, 4, c, b, a.
Replacement installation:
Remove the screw (part c), then take out the motor plate (part 4) from
the housing (part 9) by pushing down the rib in the plate while pulling
out on the side of the housing. Replace the broken parts.
4
WARNING: Before replacing, be sure to turn off power at power source.
4
5
d
e
a
1
2
3
b
c
6
8
7
9
10
10
11
PART PART NAME Qty.
1
2
3
4
5
6
7
8
9
10
11
a
b
c
d
e
Housing
Damper / Duct Connector
Wiring plate
Screw
Blower Wheel
Wire Panel / Harness Assembly
Motor
1
1
2
1
1
1
1
1
1
4
1
4
4
1
4
1
Isolator
Motor Plate
Washer
Nut, Hex Lock
Grille Assembly (includes part 1&3)
Lens
Grille Spring
Hanger Bar Kit
Screw
This manual suits for next models
1
Table of contents
Other KAZE APPLIANCES Fan manuals

KAZE APPLIANCES
KAZE APPLIANCES SE90T User manual

KAZE APPLIANCES
KAZE APPLIANCES SEP120 User manual

KAZE APPLIANCES
KAZE APPLIANCES SE90THL2 User manual

KAZE APPLIANCES
KAZE APPLIANCES SNP100H User manual

KAZE APPLIANCES
KAZE APPLIANCES SNP100 User manual

KAZE APPLIANCES
KAZE APPLIANCES SEP120H User manual

KAZE APPLIANCES
KAZE APPLIANCES SNP100HL9 User manual

KAZE APPLIANCES
KAZE APPLIANCES SEPD200L2 User manual

KAZE APPLIANCES
KAZE APPLIANCES SE90P User manual

KAZE APPLIANCES
KAZE APPLIANCES SE90PL2 Instruction Manual