Kessler-Ellis Products MINItrol Series Manual

MS287 INSTRUCTIONS
MINITROL WITH LINE FREQUENCY TIME BASE
Application:
This product special is especially useful for combined counter and
timer control functions. It has been used in applications such as
controlling the lubrication of a gear box in a drilling machine. The
gear box has to be lubricated for 5 seconds every 10 minutes. The
lubricating fluid needs to be changed after 75,000 lubrications.
This is easily accomplished using the MS287MC2A3.
The unit is programmed as follows:
Factor: factor of A = 3600, factor of B = 1.
Count: rst 0 (reset to 0), A sep B (A & B are separate counters), Hi
CPS (0-10KHz input speed).
Relay: A = 5.0 (duration of A relay is 5 seconds), B = 0.0 (duration
of B relay is latched till reset).
Presets: Preset A = 10, Preset B = 75,000
The relay on the machine which is energized when the machine is
running is connected between pin 10 (60Hz) and pin 5 (input A). A
simple solder jumper modification is made on the PC board to
make B a "batch" counter. Counter B will advance once for each
output of A. Relay A is connected to a solenoid valve which
controls the lubricating fluid. 115VAC/60Hz is connected to pins 11
& 12.
This system operates as follows:
When the machine is running, the relay on the machine is ener-
gized and the A counter starts to accumulate time. When the A
counter (timer) reaches 10 (preset A), the A counter resets, the A
Relay energizes and opens the solenoid valve for 5 seconds and
the B counter advances one. The system will run this cycle until
the B counter reaches 75,000. When the B counter reaches
75,000, the B Relay energizes and turns on a light to signal that the
fluid needs to be changed.
1- COMMON
2- N.O.(N.C./NPN)
3- COMMON
4- N.O.(N.C./NPN)
5- A INPUT
6- B INPUT
7- 12VDC OUT/+DC IN
8- -DC (GROUND)
9- RESET INPUT
10- 60Hz 15V OUT
11- A.C. INPUT
12- A.C. INPUT
RELAYS
A
B
COM.
N.O
N.C
Machine
Running Relay
LIGHT
To 115 VAC
To 115 VAC
MOV
Recommended
SOLENOID
VALVE
Description:
The MS287 is a special version of our Minitrol series counter/
ratemeter. The standard Minitrol is modified to bring a 60Hz
(50Hz) signal to pin 10 (AC powered units only). The user has the
option of connecting this signal to the A input, B input or both. By
entering the proper scaling factor, the user can scale the input to
read the desired time base. EXAMPLE: If the unit is powered with
115VAC @ 60Hz, The scaling factor for A can be set to yield
different time bases: i.e. 60 yields seconds, 360 yields minutes & 1/
10, 3600 yields minutes, etc. Input B can be scaled the same way
or used as a separate counter. With a little imagination, this
special can be used in many applications involving time/count
control. To order this special, add the prefix "MS287" to the
standard Minitrol part number, i.e. MS287MC2A3.
ORDERING NUMBER
EXAMPLE: MS287 MC2 A 3 1
SPECIAL
TYPE
MRT=6digits, counter / ratemeter
with presets and scaling.
MC2=6digits, counter only with
presets and scaling.
OPERATING VOLTAGE
A= 110 VAC ±15% or 11 to 15 VDC
B= 220 VAC ±15% or 11 to 15 VDC
C= 24 VAC ±15% or 11 to 15 VDC
COUNT INPUTS
3= Standard, 4-30 VDC Accepts simultaneous inputs.
OPTIONS
1= RS232 Communications
2= RS422 Communications
A= Analog Output (4-20/0-20 mA)
Accessories
Separate non keyboard panel order #34235
Separate keyboard panel - order #34237
KESSLER-ELLIS PRODUCTS 10 Industrial Way East, Eatontown NJ 07724
800-631-2165 • 732-935-1320 • Fax 732-935-9344 • http://www.kep.com 99367 7/3/97

MINItrol SERIES
INSTALLATION & OPERATING INSTRUCTIONS
99306 08/17/15
MODELS
MRT
MC2
MR2
KESSLER-ELLIS PRODUCTS
10 Industrial Way East
Eatontown, NJ 07724
800-631-2165 • 732-935-1320
Fax: 732-935-9344

The information contained in this publication is derived in part from proprietary and patent data of the Kessler - Ellis Products
Company. This information has been prepared for the expressed purpose of assisting operating and maintenance personnel
in the efcient use of the instrument described herein. Publication of this information does not convey any rights to use
or reproduce it or to use for any purpose other than in connection with the installation, operation and maintenance of the
equipment described herein.
Copyright 1989, Kessler-Ellis Products Co.
Printed in USA. All Rights Reserved.
WARNING
This instrument contains electronic components that are susceptible to damage by static electricity. Proper handling* pro-
cedures must be observed during the removal, installation or handling of internal circuit boards or devices.
*Handling Procedure
1. Power to unit must be removed.
2. Personnel must be grounded, via wrist strap or other safe, suitable means, before any printed circuit board or other internal
device is installed, removed or adjusted.
3. Printed circuit boards must be transported in a conductive bag or other conductive container. Boards must not be removed
from the protective enclosure until the immediate time of installation. Removed boards must be placed immediately in a
protective container for transport, storage or return to factory.
Comments:
This instrument is not unique in its content of EDS (electrostatic discharge) sensitive components. Most modern electronic
designs contain components that utilize metal oxide technology (NMOS, CMOS, etc.). Experience has proven that even
small amounts of static electricity can damage or destroy these devices. Damaged components, even though they appear
to function properly, exhibit early failure.
ATTENTION
Cet instrument contient des composants électroniques qui sont susceptibles d'être endommagés par l'électricité statique.
Procédures de manipulation appropriées doivent être respectées lors de l'enlèvement, de l'installation ou de la manipulation
des cartes de circuits internes ou les périphériques.
Procédure de traitement
1. Mettez à l'unité doit être retiré.
2. Le personnel doit être mis à la terre, par l'intermédiaire de bracelet ou d'autres moyens appropriés, sûrs, avant toute carte
de circuit imprimé ou un autre dispositif interne est installé, enlevés ou ajustés.
3. Les circuits imprimés doivent être transportés dans un sac ou un autre récipient conducteur conductrice. Les conseils ne
doivent être retirés de l'enceinte de protection jusqu'à ce que le temps d'installation immédiate. Planches enlevées doivent
être placées immédiatement dans un conteneur de protection pour le transport, le stockage ou le retour à l'usine.
Commentaires:
Cet instrument est pas unique dans son contenu d'EDS (décharge électrostatique) des composants sensibles. La plupart
des conceptions modernes contiennent des composants électroniques qui utilisent la technologie de métal d'oxyde (NMOS,
CMOS, etc.). L'expérience a prouvé que même de petites quantités d'électricité statique peuvent endommager ou détruire ces
dispositifs. Les pièces endommagées, même si elles semblent fonctionner correctement, présentent une défaillance précoce.
Proprietary Notice

SPECIFICATIONS................................................................................................... 1
DECODING PART NUMBER .................................................................................. 2
HOW TO MOUNT THE UNIT .................................................................................. 3
WIRING MINITROL................................................................................................. 4
UP/DOWN CONTROL AND QUADRATURE INPUTS ............................................ 4
WHAT CAN YOU VIEW........................................................................................... 6
OUTPUT JUMPER SELECTIONS .......................................................................... 6
MILLIVOLT INPUT OPTION JUMPER SELECTIONS ............................................ 6
OPERATING FRONT PANEL.................................................................................. 7
PROGRAMMING FLOW CHART............................................................................ 7
PROGRAM CODES & DESCRIPTIONS................................................................. 8
MINITROL TERMINATIONS.................................................................................... 9
CALCULATING SCALE FACTORS......................................................................... 10
MINITROL PROGRAMMING PROCEDURE .......................................................... 11
SETTING SCALING FACTORS .............................................................................. 11
SETTING THE COUNTER...................................................................................... 12
SETTING THE RATE .............................................................................................. 13
SETTING THE LOCK CODE & LOCKING THE UNIT............................................. 14
SETTING THE RELAYS & PRESETS..................................................................... 15
OUTPUT WIRING ................................................................................................... 16
ANALOG OUTPUT OPTION................................................................................... 17
RS232/RS422 SERIAL COMMUNICATIONS.......................................................... 18
TROUBLESHOOTING GUIDE................................................................................ 21
WARRANTY
TABLE OF CONTENTS


DESCRIPTION & SPECIFICATIONS
1
DESCRIPTION:
The MINITROL is a 6 digit totalizer / ratemeter with two level,
5 digit preset alarm control of total or rate. Inputs A & B have
separate scaling K-factors. The totalizer can be programmed
for “A” subtract “B”, “A” add “B” or A & B as separate totalizers,
with display and control of the “net” total and rate of "A". The
MINITROL is also available in 4 other versions. MC2: a two
preset totalizer with scaling, MR2: a high/low alarm ratemeter
with scaling; The “MC”: a totalizing counter only, and the “MR”:
a rate meter display only. If only one input is required, the unit
will display the total and rate from that one channel. The MINI-
TROL can accept up to 10,000 pulses per second. It has a 5
digit oating decimal scale factor allowing total readout in true
engineering units and rate per second, minute or hour.
Input “A” simultaneously drives a ratemeter which can be pro-
grammed to display the basic frequency (rate per second) or
factored to show rate per minute or rate per hour. Simply push
the “VIEW” button to see either total or rate without losing a
count. Two separate 5 A relay contacts can be set to operate
at either rate or total presets in a latch or auto-recycle mode
with output timing from 0.1 to 99.9 seconds.
Two control outputs can be assigned to either the totalizer or
ratemeter and can automatically recycle at the batch or stay
latched until reset.
Up to 99 units can communicate to a host computer on a single
RS232 or RS422 loop.
When two inputs are received (A & B), the unit can either add
or subtract the two inputs or display the two inputs as separate
totalizers.
SPECIFICATIONS:
DISPLAY
6 digit, 0.55" High LED
INPUT POWER:
110 VAC ± 15% or 12 to 15 VDC
220 VAC ± 15% or 12 to 15 VDC
24 VAC ± 15% or 12 to 15 VDC
CURRENT:
250 mA DC max. or 6.5 VA AC
OUTPUT POWER (AC powered units only)
+12 VDC @ 50 mA, unregulated -10 + 50%
TEMPERATURE:
Operating:
+32°F (0°C) to +130 F (+54°C)
Storage:
-40 F (-40°C) to +200°F (93°C)
MEMORY
EEPROM stores data for 10 years if power is lost.
INPUTS:
3: High Impedance DC pulse input 4-30 VDC (high), Open or
0-1 VDC (low),10 KΩ imp. 10 kHz max. speed. Accepts simul-
taneous inputs. May be used with KEP 711 series or 715-1
encoders or PD & D series sensors.
3M: Mag. Input, Input A only, accepts 30mV input (50 V max. P/P)
signals 10 KΩ imp. 5 kHz max. (Input B, 4-30V)
3MB: Mag. Input, Inputs A & B, accepts 30mV input (50 V max. P/P)
signals 10 KΩ imp. 5 kHz max.
5: 4-30 V Count pulses on Input A, 4-30 V Direction Control input
(level) on Input B. May be used with KEP 715-2 Encoder.
5M: 30 mV Count pulses on Input A (50 V max. P/P) 4-30 V Direc-
tion Control input (level) on Input B
9: Quadrature, accepts 4-30 V pulses with 90° phase shift for
direction detection. May be used with KEP 716 encoder.
9MB: Quadrature, accepts 30 mV (50 V max. P/P) pulses with 90°
phase shift for direction detection.
NOTE: The Mag. inputs have ltering as follows: up to 300hz
@30mV, 5KHz @ .25V to 50V max.
RESET:
Front Panel: Resets displayed value and control output
Remote: 4-30 VDC negative edge resets COUNTER "A"
and control output
K FACTOR/SCALING
In the standard unit a xed K-Factor is used to convert the input
pulses to engineering units. The 5 digit K-Factor dividers, with dec-
imal keyed into any position, allow easy direct entry of any K-Factor
from 0.0001 to 99999. Separate factors may be entered for the 2
separate input channels.
CONTROL OUTPUTS:
Relays:
2 each N.O. Relay; 5 Amps120/240 VAC or 28 VDC.
(N.C. relay contacts and NPN transistor output
available with solder jumpers. Transistor output is
internally pulled up to 10 VDC through relay coil, sinks
from 10 VDC to .5 V @ 100 mA)
Analog Output:
An optional 4-20mA (0-20mA) output is available for
the Minitrol series. The output can be programmed
to track rate or total. This feature is available by
adding sufx A to the part number. Connections are
via a 2 terminal pluggable screw connector.
Programming is accomplished by using the front panel
in conjunction with rear dip switches.
Accuracy: 50uA worst case.
Compliance Voltage: 3 to 30 VDC non inductive.

DECODING PART NUMBER
2
MINItrol (MRT, MC2, MR2)
Example: MRT A 3 1 A
Series:
MRT= 6 digits, counter / ratemeter
with presets and scaling.
MC2= 6 digits, counter only with
presets and scaling.
MR2= 5 digits, rate only with
presets and scaling.
Operating Voltage:
A= 110 VAC ± 15% or 12 to 15 VDC
B= 220 VAC ± 15% or 12 to 15 VDC
C= 24 VAC ± 15% or 12 to 15 VDC
Count Inputs:
3 = Standard, 4-30 VDC simultaneous inputs.
3M = Mag. Input, Input A only, 30mV input
(Input B, 4-30V)
3MB = Mag. Input, Inputs A & B, 30mV input
5 = 4-30 V pulses on Input A,
4-30 V Direction Control input on Input B.
5M = 30 mV pulses on Input A,
4-30 V Direction Control input on Input B
9 = Quadrature, accepts 4-30 V pulses
9MB = Quadrature, accepts 30 mV pulses (A & B)
Options (Multiple Options Available)
1= RS232 Communications
2= RS422 Communications
A= Analog Output (4-20/0-20 mA)
RS232/RS422SERIAL INTERFACE
If the serial interface option is supplied, up to 99 units can be linked
together. (The terminal addressing the unit must be capable of
driving all loads in the loop.) Unit status and new set points can be
communicated by serial communication. Mode changes, however,
must always be made on the front panel. Data is transmitted at
selected baud rates using standard seven bit ASCII characters and
parity with two additional bits of “Start” and “Stop” to make up the
standard ten bit character.
Data is received and transmitted over standard EIA RS232 or RS422
levels. Each 10 bit character is made up of a start bit, 7 bit ASCII
code, parity bit and stop bit. Unit number, baud rate and parity are
entered in the “Program Setting” set up mode and remain in memory
even if power is off.
Note that the input impedance of RS232 is 3K or 7K Ohm worst
case. The terminal addressing the unit must be capable of driving
all loads in the loop. RS422 input impedance is much higher and
there is usually no problem driving 25 units. Unit serial transmit line
remains in a high impedance “OFF” state until addressed.
PRESETS
Two control outputs are provided. To set relay values, press “menu”
button until “Relay” appears on the display, the A and B outputs can
be assigned to the ratemeter (high/low), one preset for rate and one
for total, or two presets (2 stage shut off) on the A and B counters. A
5 digit value can be entered for both presets and the decimal point
location is the same as the counter. The outputs can be set to ener-
gize from 0.1 to 99.9 seconds or latch (0.0). If a value other than 0.0
is entered, the counters will auto reset at the preset . In the A-B or
A+B versions, the relays will be assigned to either net total or A rate.
LOCKOUT
Unauthorized front panel changes can be prevented by entering a
user selected 5 digit code, in the “LOC” , . mode. The front panel
can be completely locked out or the presets can remain accessible.
RATEMETER
Accurate to 4 1/2 digits (±1 display digit). The rate meter can be
programmed to accept almost any number of pulses per unit of mea-
surement, sample from 2 to 24 seconds maximum, and auto-range
up to 5 digits of signicant information. In the “RPS” mode, the rate-
meter displays in units per second, and in the “scale” mode, units per
hour or per minute. The unit will display the rate of the A Input only.
COUNTER
The two 6-digit counters can count at 10Khz speed. Each can have
a 5-digit dividing scale factor. The counter advances on the positive
edge of each pulse. Count up or down modes available, as are
quadrature inputs from encoders for position or length measurement.
The unit can be programmed to view the net value of "A+B" or "A-B",
or A and B as separate counters.
SPECIFICATIONS
(continued)

HOW TO MOUNT THE UNIT
The unit is designed to be mounted with a gasket providing a water tight seal. Two mounting brackets are provided to secure
the unit to the panel. A panel less than .1" may distort if the clamps are screwed too tightly.
Slide the body of the unit through the rubber gasket. Insert the unit into the panel. As shown in "FIG. A", slide the brackets
up the groove to press against the back of the panel. Insert screws into rear of brackets and tighten them evenly and alter-
nately. Do not over tighten! A normal level of torque is required. Maximum torque should be 3" pounds.
This product is designed to be panel mounted and is NEMA 4 rated if proper mounting procedures are followed and the
required and supplied hardware is correctly used.
If the panel in which the unit is mounted is less than .125 of an inch thick, the possibility exists that there will be some exing.
Should this exing occur, the resulting deformation of the panel could cause a loss of the water tight seal. In case this should
occur, the use of silicone or other sealant would be recommended.
This product is designed to the NEMA 4 rated. However, the fact that we are unable to control either the location in which
the device is installed or the actual installation itself requires that the company's liability shall extend only to the repair or
replacement of a defective product.
We are prepared to offer additional assistance in those special situations where normal mounting methods do not seem to
satisfy the customers needs. This assistance may be obtained by calling the factory and asking for Application Engineering.
DIMENSIONS
FIG. A
3
3.622
(92)
1.772
(45)
4.437
(112.7)
2.625
(66.68)
0.587
(14.91)
4.245
(107.8)
BEZEL
GASKET
CUSTOMER PANEL
Panel Thickness 0.062" (1.5)
to 0.187" (4.7) max.
3.925
(99.7)

WIRING MINITROL
The rear terminal contains 12 screw terminals for connecting #14 to #28 gauge wire.
The unit is controlled by a microprocessor and, therefore, an electrically "noisy" environment could cause operating problems.
The input power line should not be common to power lines for motors, pumps, contactors, etc.
The unit is designed to be immune from line or RF voltage interference. In some environments voltage spikes of over 100
volts, even 1000 volts, can occur. When common to a power line driving motors voltage uctuations can be extreme and
rapid. Lines driving DC or AC solenoids, relays, or actuators can also cause problems.
Four sources of noise can occur:
1) AC power line noise - If the unit cannot be connected to a clean power source, an inductive load suppressing device
(MOV as GE # V130LA1 or Resistor Capacitor as Paktron # .2 uf/220 ohm @ 400V) can be installed. Although locating
the suppressor across the AC supply at the unit should help, best results are obtained by connecting the suppressor
across the leads of the "load" at the device causing the spike.
2) Input line noise -The noise is carried on the input and D.C. ground lines. Make sure the input wires are never run into
the unit in a bundle with power input lines. Also, keep these input lines isolated from inductive lines from devices
drawing heavy loads. If there is a possibility of electrical noise, we recommend using shielded cable, with the shield
being hooked to the D.C. ground terminal on the instrument, and to "earth" at one point in the circuit, preferably at the
D.C. ground terminal of the unit.
3) Output lines - The unit has two relay outputs. When these outputs are used to run external relays or solenoids, spikes
can be generated upon activation. This noise can spread through the instrument causing operating problems. If the
source is a D.C. operated device, a general purpose diode (IN4004) placed across the solenoid prevents electrical
noise spikes. Connect the cathode (banded side) to the more positive side of the coil. If the source is an A.C. operated
device, use a MOV or Resistor Capacitor across the coil.
4) 12 VDC output supply - Noise can be generated on the 12 VDC output supply if it is used to drive inductive loads or if
the current draw exceeds 50 mA. Insure that all inductive loads have a diode (such as IN4004) across the coil and that
the current does not exceed 50 mA.
UP/DOWN CONTROL AND QUADRATURE INPUTS
QUADRATURE INPUT:
When programming the counter section for quadrature input, you must set the unit for A net B and A sub B (see step 2 in
programming section). This insures proper operation. The rate can only be viewed in one direction. If the unit is a ratemeter
only (MR2), connect only one of the quadrature channels to Input A (pin 5).
UP/DOWN CONTROL:
When using the up/down control option, Input A (pin 5) is the count input and Input B (pin 6) is the up/down control (direction)
input. The counter must be set for A net B and A sub B (see step 2 in programming section).
When the direction input is high (4-30VDC) the count inputs will count up, when the direction input is low (open or less than
1VDC) the count inputs will count down. The direction input must precede the count input by 1 msec when the unit is set
for low CPS and 1 usec when set for high CPS.
4

CONNECTING AC / DC POWER
NOTE: Connect power only after other connections are nished. Do not touch the live AC power terminals! The unit has
been designed with an isolated AC input. Thus, polarity is not a concern for the AC input. The chassis is plastic, therefore
earth ground is not used. For D.C. operation, connect + 12V to pin 7 and - D.C. to pin 8.
CONNECTING SENSOR INPUTS
These diagrams show how to hook typical input sensors to the unit. The unit supplies an unregulated 12 Volt (50mA)
output to power these sensors (Pin 7).
A valid pulse is one which makes a transition from the off-state (0 to 1V) to the on-state (4 to 30V): a positive going edge.
The input impedance is 10K Ohms to ground. The unit can be programmed from the front panel for slow switch closure
inputs up to 40Hz (select "Lo CPS"), or solid state switches (select "hi CPS") up to 9.99KHz. No rear terminal jumpers are
required. Use PNP (sourcing) type pulsers.
TYPICAL SENSOR HOOKUP TYPICAL QUADRATURE HOOKUP
When the unit has the quadrature input, the counter must
be set at:
A net B, A sub B (for "set to preset", A add B) and the
scaling factors for A & B must be of equal value.
D08N
1 COMMON
2 N.O. (N.C./NPN)
3 COMMON
4 N.O. (N.C./NPN)
5 A INPUT
6 B INPUT
7 12 V OUTPUT/ + DC INPUT
8 - DC (GROUND)
9 RESET INPUT
10 NOT USED
11 AC INPUT
12 AC INPUT
D12P
COUNT
POWER
GROUND
COUNT
GROUND
POWER
A
RELAYS
B
*
* PULLUP RESISTANCE
4.7K TYPICAL
1 COMMON
2 N.O. (N.C./NPN)
3 COMMON
4 N.O. (N.C./NPN)
5 A INPUT
6 B INPUT (90° out of phase)
7 12 V OUTPUT/ + DC INPUT
8 - DC (GROUND)
9 RESET INPUT
10 NOT USED
11 AC INPUT
12 AC INPUT
A
RELAYS
B
716 12VDC 100PPR 300RPM A1
+12 VDC
GROUND
5

WHAT CAN YOU VIEW?
6
1) "A sub B" - If you have selected the "A sub B" mode, pressing "view" shows:
A) The net result of subtracting input B from input A. Pulses on input B will subtract (count down). Pulses on input A
will add (count up) if "reset to 0" is selected, if "set to preset" is selected, input A will subtract (count down).
B) The rate of input A.
2) "A add B" - If you have selected "A add B" mode, pressing "view" shows:
A) The net result of adding "A" and "B" inputs. Pulses on input B will add (count up). Pulses on input A will add
(count up) if "reset to 0" is selected, if "set to preset" is selected input A will subtract (count down).
B) The rate of input A.
3) "A sep B" - If you have selected " A sep B" mode, pressing "view" shows:
A) The total counts of input A. If "reset to 0" is selected A counts up, if "set to preset" is selected A will count down.
B) The rate of input A.
C)* The total counts of input B. B will always count up.
NOTE: In "A sep B" mode, B can be used in 3 ways:
1) As a separate totalizing counter
2)** As a Batch Total Counter for input A
3)** As a Grand Total Counter for input A
NOTE:
* All decimal points are inverted when "B total" is being displayed.
** See below on how to modify for Batch Count and "B" as a Grand Total Counter.
MILLIVOLT INPUT OPTION
JUMPER SELECTIONS
OUTPUT JUMPER SELECTIONS
FUNCTION
"A" RELAY
N.C. OUTPUT
"B" RELAY
N.C. OUTPUT
"A" PRESET
TRANSISTOR (NPN)
"B" PRESET
TRANSISTOR (NPN)
"B" AS BATCH
COUNTER
"B" AS GRAND
TOTAL COUNTER
MODIFICATION
CUT JUMPER
AT "A" "B" TO "2"
CUT JUMPER
AT "D" "E" TO "4"
CUT JUMPER
AT "A" "C" TO "2"
CUT JUMPER
AT "D" "F" TO "4"
SELECT JUMPER
"A SEP B" "H" TO "G"
SELECT CONNECT
"A SEP B" PULSES TO
"A" & "B"
BOTTOM VIEW AT TERMINAL
DE
G
H
20192
12 11 10 9 8 7 6 5 4 3 2 1
L
4
AB
2
FC
JUMPER SELECTIONS
J4
J5
J6
J3
J1
J2
CR1
R3
C8R7R5
R4
U1
CR2
REV
20229
CR6
CR3
U3
P1
R10 R6
C6
C7
CR4
CR5
C4
R2
R1
C3
C5
U2 U4
U6
U5
R8
R9
C1
C2
C9
B
If the unit has the millivolt input bd.# 20229, A & B inputs can be
separately solder jumper programmed to accept either a low millivolt
or 4-30 V input. Each unit shipped is programmed according to part
number. If solder jumpers are made, the part number should be
modied to reect the changes made
C=CLOSE, O=OPEN
4-30V INPUT Millivolt INPUT
Input A J1-O, J2-C, J3-O J1-C, J2-O, J3-C
InputB J4-O, J5-C, J6-O J4-C, J5-O, J6-C
*
*
* The unit must be removed from the case to access jumpers C & F, all
other jumpers can be accessed by removing the plastic extender.
NOTE: All three pads at jumpers 2 and 4 are connected.

PROGRAMMING FLOWCHART
NOTE: Several programming selections will not appear with MC2 and MR2 units.
PRGM
Press this key to step through menu choices.
ENTER
RST
Press this key to enter displayed value
Start Here
654321
LOCK PRE A PRE BVIEW PRGM
ENTER
Press to "reset"
in operating
mode.Press to
"enter" in
programming
mode.
Press to enter
lock code for
panel lock.
Press to
view or
change
preset A.
Press to
view or
change
preset B.
Press to alternately
view A rate & net
total or A rate,
A total & B total.
Press to cycle
through PROGRAM
choices. Press to
toggle between
choices in program
mode.
OPERATING THE FRONT PANEL
RST
7
PRGM
FACToR
RUN MODE
DP F A
#####
DP F B
#####
ENTER
ENTER
ENTER
ENTER
ENTER
PRGM
Hi
CPS
Lo
CPS
PRGM
RUN MODE
ENTER
RATE METER
(MR2) ONLY
CouNT
ENTER
RST
0
SET
PR
PRGM
ENTER
DPLoC
ENTER
A
NET
B
A
SEP
B
PRGM
ENTER
ENTER
A
ADD
B
A
SuB
B
PRGM
Hi
CPS
Lo
CPS
PRGM
ENTER
RUN MODE
ENTER
RATE
ENTER
SCALE RPS
PRGM
Z3600 Z60
PRGM
ENTER
ENTER
ENTER
RUN MODE
NoR ##
ENTER
FiguR#
ENTER
DLY #
ENTER
LoC
ENTER
LC
PRg
LC
ALL
PRGM
ENTER
CoDE
#####
RUN MODE
ENTER
RELAY
ENTER
A
ToT
A
RATE
PRGM
A ##.#
ENTER
ENTER ENTER
B
ToT
B
RATE
PRGM
B ##.#
ENTER
ENTER ENTER
RUN MODE
PRGM PRGM PRGM

The following is a list of abbreviations as they appear on the display and front panel of the unit.
ABBREVIATION DESCRIPTION
FACTOR SCALING FACTOR - For A and B Inputs. Each input has a separate 5 digit dividing scale factor.
DP F A DECIMAL POINT FOR FACTOR A - Enter location of decimal point for scaling Factor A by pressing the
button under the digit where the decimal is desired.
DP F B DECIMAL POINT FOR FACTOR B - Enter location of decimal point for scaling Factor B by pressing the
button under the digit where the decimal is desired.
COUNT PORTION OF MENU FOR SETTING COUNTER VARIABLES
RST 0 RESET TO 0 - Counter will reset to 0. Input A will count up from 0. Input B will subtract (count down) in A
Sub B mode. Input B will add (count up) in A Add B mode.
SET PR SET TO PRESET - Counter will reset to preset A. Input A will count down from preset A. Input B will count
up (add) in "A add B" mode and input B will count down (subtract) in "A sub B" mode.
DP LOC DECIMAL POINT LOCATION - Enter desired location of decimal by pushing the button under the digit where
the decimal is desired. Changing the decimal will change the decimal location in the A & B counters as well
as the rate display.
A NET B NET RESULT OF ADDING OR SUBTRACTING A & B INPUTS
A SEP B A & B INPUTS ARE SEPARATE - A & B are not added or subtracted.
A SUB B A SUBTRACT B - The number of scaled pulses from Input B are subtracted from the number of scaled pulses
from Input A. (-99999 TO 999999)
A ADD B A ADD B - The number of scaled pulses from the A Input are added to the number of scaled pulses from the
B Input.
HI CPS HIGH COUNTS PER SECOND - This sets the unit for high count speeds (0-9.99KHz)
LO CPS LOW COUNTS PER SECOND – This sets the unit for contact debounce ltering (0-40Hz)
RATE PORTION OF MENU FOR SETTING RATE VARIABLES
RPS RATE PER SECOND - The display will read in rate per second.
SCALE SCALING - Allows unit to display rate per minute or rate per hour.
Z 60 DIVIDE K FACTOR BY 60 - This sets the unit for rate per minute; equal to 60 times rate per second.
Z 3600 DIVIDE K FACTOR BY 3600 - This sets the unit for rate per hour; equal to 3600 times rate per second.
NOR## NORMALIZING FACTOR - Normalizes (averages) the data being received. Higher settings provide more
normalizing (averaging) for a more stable display. Derived from the equation:
(Old Data x "NOR" + New Data)
("NOR" + 1)
FIGUR ## SIGNIFICANT FIGURE - This sets the amount (1-5) of meaningful gures the unit will display. (RATE DIS
PLAY ONLY). FOR EXAMPLE: If "2" is set as the gure, a rate of 273.45 will be displayed as 270.
DLY## DELAY FACTOR - The amount of time (02 to 24 sec.) the unit will "look" for valid data, before the display
defaults to zero. (RATE DISPLAY ONLY)
8

LOC LOCK - This portion of the menu allows you to:
1) lock the program (presets are still accessible)
2) lock all (presets and program are locked).
LC PRG LOCK PROGRAM - This will lock the program and allow the presets to be changed when the unit is in the
lock mode.
LC ALL LOCK ALL - This will lock the program and the presets when the unit is in the locked mode. The presets can
be viewed, but not changed.
CODE LOCK CODE - This message (code) will ash on display for approximately 3 seconds. It will be followed by a
5 digit number (xxxxx). The number you enter here will be the code to lock and unlock the unit.
RELAY RELAY - This portion of the menu allows you to set your relay operation variables.
A TOT RELAY A FOR TOTALIZER - When this is selected relay A will activate when the net total has reached
Preset A ("A NET B" Mode ). Relay A will activate when the total of input A reaches preset A ("A SEP B"
Mode).
A RATE RELAY A FOR RATE - When this is selected relay A will activate when the Rate of input A equals or exceeds
preset A when in "A NET B" or "A SEP B" mode. The relay will drop out when the rate of A falls below preset
A.
A##.# RELAY A DURATION - This message will appear when "A TOT" is selected. It is the duration which the
relay will remain energized (00.1 to 99.9 sec). If 00.0 is selected, the relay will latch until reset. When the
duration is not at 00.0, the unit will autorecycle.
B TOT RELAY B FOR TOTALIZER - When this is selected relay B will activate when the net total has reached preset
B ("A NET B" Mode). Relay B will activate when the total of input B has reached preset B ("A SEP B" Mode).
B RATE RELAY B FOR RATE - When this is selected relay B will activate when the rate of input A equals or exceeds
preset B when in "A NET B" or "A SEP B" mode. The relay will drop out when the rate of A falls below preset
B.
B##.# RELAY B DURATION - Follow same procedure as A ##.#.
MINITROL TERMINATIONS
1 2 3 4
REAR VIEW
1 2 3 4 5 6 7 8 9 10 11 12
13 14
Analog Out Setup SwitchesSerial Port
ON
1- COMMON
2- N.O.(N.C./NPN)
3- COMMON
4- N.O.(N.C./NPN)
5- A INPUT
6- B INPUT
7- 12VDC OUT/+DC IN
8- -DC (GROUND)
9- RESET INPUT
10- NOT USED
11- A.C. INPUT
12- A.C. INPUT
SYALER
A
B
13- V+
14- I SINK
GOLANA
TUPTUO
ON
CAL.
0-20mA
COUNT
SET
OFF
RUN
4-20mA
RATE
RUN
4321
NO
HCTIWS
9

CALCULATING SCALE FACTORS
There are two separate dividing scale factors, one for input "A" and one for input "B". The factor to enter is the number of
pulses per the desired unit of measurement. The factor ranges from 0.0001 to 99999. The factor is the same for rate and
count on input "A". Because the "units per second", "minute", or "hour" are eld programmable from the keypad, scale factor
calculations for the ratemeter are easy. Here are some examples:
SCALING FACTOR EXAMPLES:
BATCHING: You want to count the number of batches (10 boxes each) being loaded onto a pallet.
Solution - Dial in a scale factor of 10.
UNIT COUNTING: You pick up a notch on a paper roll (1 pulse per shaft revolution). Each revolution equals 3 feet. To
nd the number of pulses per foot, simply divide "1 pulse" by "3 feet" (1÷ 3 = .3333).
Solution - One foot equals 0.3333 pulses, enter this as the scale factor and the display will read in feet.
RATE: The shaft of a motor has a ywheel with 10 spokes. The KEP DO series prox switch is mounted to
sense 10 pulses per revolution. RPM of the shaft is the desired readout.
Solution: Enter a Factor of 10 and for every 10 pulses, "1" will appear on the display. Set rate per
second, minute or hour as desired.
A conveyor carrying bottles must be controlled for bottle speed. For each revolution of the front roller, three bottles
travel by. Thus, one revolution equals 3 bottles. A wheel with seven spokes is mounted on the roller. The user
can't sense bottles because they are traveling through a washer, so a sensor is placed at the roller, sensing seven
pulse per revolution of the shaft, which equals 3 bottles per revolution.
To calculate the scale factor (7 ppr ÷ 3 bottles) = 2.3333 scale divider. Set rate per second, minute or hour as
desired.
A ow meter is generating 52.6 pulses per gallon. The desired readout is in liters. Since there are 3.785 liters per
gallon, divide 52.6 by 3.785 to nd the number of pulses per liter (52.6 ÷ 3.785 = 13.897).
Enter 13.789 as the scale factor so the display will read in liters.
An aluminum sheeting plant has a cut to length application to customer specication. A ten pulse per revolution
encoder with a 12" wheel is used to sense. The travel of aluminum sheets is in inches. Thus, after 10 pulses, you
want 12 to appear on the display. Thus, 10 ÷ 12 = .8333. Enter .8333 as your scale factor.
10

REMARKS
This section of the menu is used to set
up the scaling factors for inputs A & B.
This sets the decimal for factorA. Press
the arrow key under the digit where
the decimal is desired. To clear the
decimal, press the arrow key furthest
to the right (PRGM) .
This is the scaling factor for input A.
To change, press the arrow key under
the digit(s) to change. Press ENTER
to enter the displayed value.
This section will only appear in the
RATE only version. Press the PRGM
key to choose HIGH CPS (0-9.99KHz)
or LOW CPS (0-40Hz). Press the EN-
TER key to enter the displayed choice.
This sets the decimal for factor B. Press
the arrow key under the digit where
the decimal is desired. To clear the
decimal, press the arrow key furthest
to the right (PRGM) .
This is the scaling factor for input B.
To change, press the arrow key under
the digit(s) to change. Press ENTER
to enter the displayed value.
DISPLAY
factor
dp f a
#####
hi cps
or
lo cps
dp f b
#####
PRESS
PROGRAMMING
THIS SECTION
WILL ONLY
APPEAR IN THE
RATE METER
ONLY VERSION
11
SETTING
SCALING
FACTORS
STEP
1

PRESS DISPLAY REMARKS
This section of the menu sets up the
counter information.
Press the PRGM key to choose RST 0
(reset to 0, count up) or SET PR (set to
preset, count down), press the ENTER
key to enter the displayed choice.
This sets the decimal location for the
A & B counters. Press the arrow key
under the desired digit location. To
clear the decimal, press the arrow key
furthest to the right. Press the ENTER
key to enter the displayed location.
Press the program key to choose A
NET B (add or subtractA & B) orA SEP
B (view A & B as separate counters).
Press the ENTER key to enter the
displayed choice.
This section will only appear if A NET
B was selected. Choose A SUB B (A
subtract B) or A ADD B. Press the EN-
TER key to enter the displayed choice.
Press the PRGM key to choose HIGH
CPS (0-9.99KHz) or LOW CPS (0-
40Hz). Press the ENTER key to enter
the displayed choice.
factor
count
rst 0
or
set pr
dp loc
a net b
or
a sep b
a sub b
or
a add b
hi cps
or
lo cps
12
SETTING
THE
COUNTER
STEP
2

STEP
3
REMARKSPRESS DISPLAY
This section of the menu is used to set up
the rate information.
Press the PRGM key to choose RPS (rate
per second) or SCALE (RPM, RPH). Press
ENTER to enter displayed choice.
Press PRGM to choose ÷60 (RPM) or
÷3600 (RPH). Press ENTER to enter dis-
played choice.
This sets the normalizing (averaging) factor.
Press the arrow keys under the desired
digits to change. Press ENTER to enter
displayed value.
This sets the number of signicant gures
to be displayed. Press the arrow key under
the digit to change. Press ENTER to enter
displayed value.
This sets the delay time (2 to 24 sec.) that
the unit will "look" for valid input data before
the display falls to 0. Press the arrow key
under the digits to change. Press ENTER
to enter displayed value.
factor
count
rate
rps
or
scale
z 60
or
z 3600
nor ##
figur #
dly #.#
13
SETTING
THE RATE

DISPLAY REMARKS
factor
count
rate
loc
LC PG
or
LC ALL
CoDE
Flashes
followed by:
#####
CoDE
Flashes
followed by:
0
LoC
or
uN LoC
This section of the menu is used to set up the
lockout type and code.
LC PG = Locks program but presets and re-
set are accessible.
LC ALL= Locks entire keypad.
Press the PRGM button to toggle between
choices; Press ENTER to enter displayed
choice.
After CODE ashes the display will show the
existing lock code. To change the code press
the key under each digit to be changed. Press
ENTER to enter displayed value.
Key in the lock code (see programming step
4) by pressing the keys under the digits to be
changed. Press the ENTER key to enter the
displayed code.
After the code is entered the unit will display
LOC (unit is locked) or UN LOC (unit is un-
locked). This message will be displayed for
approximately 3 seconds before the unit re-
turns to the run mode.
SETTING
THE
LOCK
STATUS
PRESS
14
SETTING
LOCK
STEP
4

REMARKS
DISPLAYPRESS
STEP
5
SETTING
THE
RELAYS
This section sets up the relay information.
Press the PRGM key to choose A TOT (A
assigned to total) or A RATE (A assigned to
rate). Press enter when the desired choice is
displayed.
This is the duration (.1 to 99.9 sec) that relay
A will remain energized. If 00.0 is selected,
the relay will latch until reset
Press the PRGM key to choose B TOT (B
assigned to total) or B RATE (B assigned to
rate). Press enter when the desired choice is
displayed.
This is the duration (.1 to 99.9 sec) that relay
B will remain energized. If 00.0 is selected,
the relay will latch until reset
PRE A = Preset A (Final Preset); The set point
at which output A will trigger. If the displayed
value is not the desired preset, press the
key(s) under the digit to be changed.
PRE B = Preset B (Prewarn); The set point
at which output B will trigger. If the displayed
value is not the desired preset, press the
key(s) under the digit to be changed.
factor
count
rate
loc
relay
a tot
or
a rate
A ##.#
b tot
or
b rate
b ##.#
PRE A
Followed by
last PRE A
entered
PRE B
Followed by
last PRE A
entered
SETTING
THE
PRESETS
15
This manual suits for next models
5
Table of contents
Other Kessler-Ellis Products Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

AEMC instruments
AEMC instruments 6536 user manual

ALICE
ALICE NGU Series user manual

GHM-Messtechnik
GHM-Messtechnik GREISINGER GTF 111-Ex Series operating manual

Maynuo Electronic
Maynuo Electronic M97 series user guide

Allestec
Allestec EDISON ONGUARD 1604 System operation manual

Koeng
Koeng KEG-500 Operation manual