Index
Safety information and explanation of symbols used......................3
Features of the KT63....................................................................5
Special Polarity Test Function. ........................................................... 6
Audible tones ...............................................................................7
Overview of the switches and LCD ..............................................8
Test lead inputs ............................................................................9
Continuity Test Function..............................................................10
Continuity Test Procedure................................................................ 10
Lead Nulling................................................................................... 10
Hands Free Continuity Testing.......................................................... 11
Insulation Test Function ..............................................................12
Insulation Test Procedure ................................................................ 12
Hands Free Insulation Testing .......................................................... 13
Loop Test functions ....................................................................14
High Current mode ......................................................................... 14
No Trip Mode ................................................................................. 14
PFC/PSC ....................................................................................... 15
Test lead configuration.................................................................... 15
Lead configuration for No-Trip testing............................................... 16
Lead configuration for High current 2-wire testing ............................. 16
Loop Test Procedures..................................................................... 17
No Trip Loop test (Zs) ..................................................................... 17
High current test (Ze)...................................................................... 18
Hands Free Loop testing................................................................. 18
RCD Test Function ......................................................................19
Ramp test...................................................................................... 20
Sinusoidal polarity (the 0° or 180° test)............................................ 20
RCD test procedure ........................................................................ 21
User selected test .......................................................................... 21
30mA Automatic test...................................................................... 22
Ramp test...................................................................................... 22
Specifications and tolerances .....................................................23
Continuity Test Range Accuracy....................................................... 23
Insulation Test Range Accuracy........................................................ 23
Insulation Output Voltage................................................................. 23
Loop Test Range Accuracy.............................................................. 23
RCD Test Range Accuracy............................................................... 24
Safety information and explanation of symbols used
Because the KT63 is a multi function tester used for testing both live and dead
circuits there are different safety issues that apply to the individual functions. Before
using your KT63 please read these instructions paying particular attention to the
general safety warnings below and those at the start of each section.
Before using the tester check the case and the test leads for damage.
If any damage is noticed the unit should be withdrawn from service and returned to
Kewtech for repair.
It is important for safety that only one set of leads can be fitted at a time. In the
unlikely event that the interlock cover is damaged the tester should be withdrawn
from service and returned to Kewtech for repair
Caution read this manual for safety information
The Continuity and Insulation functions are rated at 500V Category III
The Loop and RCD functions are rated at 300V Category IV
When installing batteries observe correct polarity do not mix old and new batteries
- Dispose of used batteries in accordance with local regulations – Never incinerate
batteries.
Do not use this tester in a manner other than that described in this booklet.
To clean the tester wipe with a damp cloth with a mild soap solution taking care
not to allow water ingress into the input terminals. Do not use solvents and do not
immerse. Allow the tester to fully dry before use.
The KT 63 is fuse protected against damage by accidental connection to an over-
voltage supply. The fuse is located inside the battery compartment and can be
accessed by removing the two small battery cover retaining screws on the back
of the case. Always ensure that test leads are disconnected before removing the
battery cover.