Keyscan CA8WL-AL User manual


Copyright © 2015 Keyscan Inc. All rights reserved.
Information and specifications in this document are subject to change without notice.
Except for the benefit of installation and operation of the Keyscan access control system, no part of this
documentation may be reproduced or transmitted in any form or by any means without the expressed written
permission of Keyscan Inc.
Keyscan Inc. A Member of the Kaba Group
901 Burns Street East
Whitby, Ontario
Canada
L1N 0E6
Phone: 1-888-539-7226 (Toll Free Canada/USA)
Phone: 905-430-7226
Fax: 905-430-7275
Web Site: www.keyscan.ca
Keyscan technical support is available to dealers and installers Monday to Friday 9:00 A.M. to 6:30 P.M.
Eastern Time at the above listed telephone numbers or web address.


Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
4
Table of Contents
List of Figures ................................................................................................................................... 6
Foreword .......................................................................................................................................... 7
About This Guide ........................................................................................................................... 7
Electrical Precautions ..................................................................................................................... 7
Tools............................................................................................................................................ 7
Introduction to CA8WL-AL ................................................................................................................ 8
Mounting the CA8WL-AL ................................................................................................................. 10
Mounting Guidelines..................................................................................................................... 10
DIP Switch/Jumper Settings........................................................................................................... 14
S1.1 –S1.12 –System Configuration DIP Switches ......................................................................... 14
S2.9 & S2.10 System Software Mode DIP Switches .......................................................................... 18
J1 - Restore Default Settings/Clear Memory .................................................................................... 18
J6 - System Reset........................................................................................................................ 19
Communication ............................................................................................................................... 21
CA8WL-AL to Server/Workstation .................................................................................................. 21
CA8WL-AL to PIM400-485............................................................................................................. 21
Single Control Unit Communication Only......................................................................................... 21
Supported Number of Wireless Locks ............................................................................................. 21
Keyscan RS-232 Data Cable.......................................................................................................... 22
Power Connections ......................................................................................................................... 26
System Power-up ........................................................................................................................ 26
Test Points –Communication Terminals.......................................................................................... 29
Diagnostics ..................................................................................................................................... 30
Communication LEDs ................................................................................................................... 30
System Status LED ...................................................................................................................... 31
Program On-board Ethernet Module................................................................................................ 33
Before You Start Programming ...................................................................................................... 33
Configure CA8WL-AL for Reverse Network Communication ............................................................ 37
About Reverse Network Communication ......................................................................................... 37
Installation Coordination –Host & Remote Locations ........................................................................ 37
Before You Start .......................................................................................................................... 41
Set System Configuration DIP Switches .......................................................................................... 42
Set IP Address on Access Control Board.......................................................................................... 42
Program the CA8WL-AL On-board Ethernet Module .......................................................................... 44
CA8WL-AL Quick Reference............................................................................................................. 48

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
5
CA8WL-AL Specifications ................................................................................................................ 50
Warranty......................................................................................................................................... 51
Index .............................................................................................................................................. 52

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
6
List of Figures
Figure 1 –CA8WL-AL/PIM400-485/Schlage AD-400 Wireless Lock Overview................................................ 8
Figure 2 - Remove the Right Cover....................................................................................................... 11
Figure 3 –Mounting the CA8WL-AL ...................................................................................................... 12
Figure 4 - CA8WL-AL Mount - Side View................................................................................................ 13
Figure 5 –System Configuration DIP Switches S1.1 –S1.12 ................................................................... 16
Figure 6 - System Software Mode DIP Switches S2.9 & S2.10.................................................................. 18
Figure 7 –Restore Default Settings (Clear Memory) J1 Location .............................................................. 19
Figure 8 –Location of System Reset Jumper J6 ..................................................................................... 20
Figure 9 –RS-232 Data Cable Connections ........................................................................................... 22
Figure 10 –Communication - Serial ..................................................................................................... 23
Figure 11 –Communication - USB Adaptor/Serial .................................................................................. 24
Figure 12 - Communication –Network with PoE (Ethernet) ..................................................................... 25
Figure 13 –Power Supply Connections ................................................................................................. 28
Figure 14 –Control Board Communication Test Points ............................................................................ 29
Figure 15 –Communication Status LEDs............................................................................................... 31
Figure 16 - Location of System Status LED............................................................................................ 32
Figure 17 - Temporary Connection for Programming the Ethernet Module ................................................. 34
Figure 18 - Example of Internet/Intranet/WAN with Router or End Point External IP................................... 39
Figure 19 - LAN with no public exposure ............................................................................................... 40
Figure 20 –Location of S1.1 / S1.2 DIP Switches................................................................................... 42
Figure 21 –Temporary Programming Connection for Reverse Network ..................................................... 43
Figure 22 –CA8WL-AL Control Board ................................................................................................... 48

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
7
Foreword
Keyscan systems are designed for use in various environments and applications. As such, observe stated
cable, power, ground, and environment specifications for reliable and safe operation of the equipment.
About This Guide
This guide reviews information that pertains to the installation of the Keyscan CA8WL-AL access control unit
and assumes the installer has knowledge of electrical, electronic, mechanical, network (TCP/IP) and computer
concepts, as well as having familiarity with access control systems and associated components.
Electrical Precautions
Be sure that all circuit breakers powering the system are switched off before commencing installation or
modifying wiring connections. Do not apply power before the installation is complete otherwise the equipment
may be damaged. Ensure all enclosures are connected to earth grounds for proper and safe system operation.
Tools
We recommend having the following tools on hand to install the access control system:
Digital Multi Meter
Wire Cutters
Needle Nose Pliers
Soldering Iron
Tape
Set of Screwdrivers
Drill & Drill Bits
Laptop Computer (optional)

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
8
Introduction to CA8WL-AL
The CA8WL-AL is designed to operate with a PIM400-485 which interfaces with Schlage AD-400 wireless locks.
The CA8WL-AL control unit supports a network (TCP/IP) connection or a direct serial connection (RS-232) to
the server/workstation with the Aurora communication service. If you are using a network connection with
either standard or reverse communication, you must program the CA8WL-AL’s on-board Ethernet module
using the NETCOM Program utility. Programming instructions are reviewed later in this guide.
Figure 1 –CA8WL-AL/PIM400-485/Schlage AD-400 Wireless Lock Overview
Important –Inputs, Outputs and Reader Terminals
As the CA8WL-AL is designed solely for use with a PIM400-485 and AD-400 wireless locks, all CA8WL-AL
inputs, outputs and reader terminals are disabled and do not function.
Software Requirements
The CA8WL-AL control unit is compatible with the following Keyscan software:
Aurora –version 1.0.8.0 or higher
If you are operating with a previous version of Keyscan Aurora software you can obtain the latest version at
www.keyscan.ca. The CA8WL-AL is not compatible with any previous generation of Keyscan software.
Powering the CA8WL-AL
The CA8WL-AL single door control unit can be powered from one of the following sources:
network switch with power over Ethernet (PoE) capabilities
mid-span PoE injector
+12V DC UL approved power supply
PIM400-485
CA8WL-AL
WIRELESS
maximum distance
200 horizontal ft. (61 m) with
typical building construction. Refer
to Allegion/Schlage documentation
for more information.
KI-00525E-12-14
Supports a maximum of 8 wireless locks per CA8WL-AL / PIM400-485.
Do not mount wireless lock and PIM400-485 on different floors.
RS485
CAT5 –1 twisted pair
maximum distance
4000 ft / 1219 m
12 3
45 6
78 9
0
*#
Wireless
Lock

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
9
Refer to page 26 for more about power connections and testing voltages.
Important
The CA8WL-AL operates as a Class 0 PoE Powered Device (PD). As such, the CA8WL-AL requires the
allocation of 15.4 Watts from the PoE switch or injector. Of the 15.4 Watts, the CA8WL-AL provides 680
mA at 12 volts –approximately 8 Watts –to power connected peripheral devices such as readers, door
strikes, PIR sensors, etc.
Selection of a PoE switch must be based on the power demand of all of the loads connected to the switch.
The PD Class (0-4) for each device connected to the switch must be known and the sum of all loads, for a
conservative and reliable design, should not exceed 75% of the total available power. As loads are
disconnected and others connected, the total power consumption must be re-assessed. Keyscan
recommends the use of low port count PoE switches, maximum 8 ports, to minimize the impact of a switch
failure on the access control system and, that all PoE switches be powered using a UPS.
Program On-board Ethernet Module
If the CA8WL-AL is connected on a network (TCP/IP) using Keyscan’s standard communication, the unit’s on-
board Ethernet module has to be programmed with an IP address. This procedure is required so the CA8WL-AL
can communicate with the Server/workstation that has Keyscan’s standard communication software.
The CA8WL-AL requires NETCOM Program Utility –version 6.0.18 or higher. Always use the latest NETCOM
Program Utility on the enclosed Keyscan CD when programming the on-board Ethernet module.
For a complete outline of requirements and procedures for programming the on-board Ethernet module for
standard communication, see page 33.
Configure the CA8WL-AL for Reverse Network Communication –License
Required
If the CA8WL-AL is connected on a network using Keyscan’s reverse network communication, the unit’s on-
board Ethernet module and the control board memory have to be programmed with IP addresses.
Generally, reverse network communication is used only in centrally managed access control applications.
A license must have been purchased –AUR-RNx –which includes encrypted reverse network communication
software.
If you have not purchased a license from Keyscan, do not configure the CA8WL-AL for reverse network
communication.
The CA8WL-AL requires NETCOM Program Utility –version 6.0.18 or higher. Always use the latest NETCOM
Program Utility on the enclosed Keyscan CD when programming the on-board Ethernet module.
For an outline of requirements and procedures on configuring the CA8WL-AL for reverse network
communication, see page 37.
PIM400-485/Schlage AD-400 Wireless Locks Documentation
Refer to the PIM400-485/Schlage AD-400 Wireless Locks documentation for mounting and programming
instructions. Keyscan recommends the PIM400-485 is mounted in proximity to the CA8WL-Al whenever
possible.

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
10
Mounting the CA8WL-AL
Locate the area where the CA8WL-AL and, if required, the power supply, are going to be mounted. Follow the
mounting diagrams on the succeeding pages. Keyscan recommends a vertical mount on a solid, smooth
surface. Do not mount the access control unit close to high-voltage equipment. Comply with all local and
regional codes. Record the serial number listed on the control board. The serial number is a required entry in
the Keyscan Client software. The CA8WL-AL includes a mounting template for drilling holes to mount the unit.
Mounting Guidelines
Unfasten the 2 knurled screw heads on the CA8WL-AL to remove the right-side cover as shown in Figure 2
Use the enclosed mounting template and drill 4 holes where indicated
Fasten the top 2 screws and the lower left screw until there is a gap of approximately 1/32” between each
of the screw heads and the mounting surface
Mount the CA8WL-AL so that the 3 keyway cutouts at the back of the enclosure are over the screw heads
as shown in Figure 3
Slide the enclosure down until the 3 screws are seated at the top of the keyway cutouts
If necessary, remove unit and adjust the screws to have the unit fit tight between the screw heads and
the mounting surface, then slide the enclosure down until the 3 screws are seated at the top of the
keyway cutouts
Fasten and tighten the 4th screw in the lower right hole
Leave the right cover off until you have connected the PIM400-485, applied power, and tested the
voltages

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
11
Figure 2 - Remove the Right Cover
CARD
BITS
10s1s
SYSTEM
STATUS COMMUNICATION
STATUS
TD 1 RD 1TD 2 RD 2
SYSTEM
INPUTS/
RS-485
(TB7)
SERVER
RS-232 (TB5)
ETHERNET
Left Cover - Do not remove.
SYSTEM STATUS LEGEND
GREEN –NORMAL
AMBER - SERVER COMMS FAULT
RED SOLID - RESET/FAULT
RED FLASHING - CLEARING MEMORY Removable Right Cover
Knurled Screw Head
Knurled Screw Head
KI-00524E-12-14
KEYSCAN
CA8WL

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
12
Figure 3 –Mounting the CA8WL-AL
KI-00527E-12-14
CARD
BITS
10s1s
SYSTEM
STATUS COMMUNICATION
STATUS
TD 1 RD 1TD 2 RD 2
SYSTEM
INPUTS/
RS-485
(TB7)
SERVER
RS-232 (TB5)
ETHERNET
Front View
Keyway
Cutout
Keyway
Cutout Keyway
Cutout
Left Cover
(Do not remove.)
x3 for Keyway
Cutouts x1
Knock-outs - 7/8"
(2.2225 cm)
Knock-out
Knock-out
Knock-out
Knock-out
KEYSCAN
CA8WL
KEYSCAN INC.
CA150B
Rev. B
CA8WL-AL PC1156

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
13
Figure 4 - CA8WL-AL Mount - Side View
SideView
Mounting Surface
CA8WL-AL Enclosure
Keyway
Cutout
Keyway
Cutout
1/32"
Mounting Surface
CA8WL-AL Enclosure
Keyway
Cutout
Keyway
Cutout
1
Lineup bottom part
of keyway cutouts
withscrew heads
and place enclosure
against mounting
surface.
2
Slide enclosure
downuntil the 3
screws are seated
at thetop ofthe
keyway cutouts.
KI-00528E-12-14

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
14
DIP Switch/Jumper Settings
The CA8WL-AL has DIP switches and jumpers that activate or alter specific board functions to meet installation
requirements.
System configuration DIP switches S1.1 to S1.12 –page 14
System software mode DIP switches S2.9 –S2.10 –page 18
Restore factory defaults jumper J1 (Clear memory) –page 18
System reset jumper J6 –page 19
Depending on the installation, some switches may require activation in order to enable the desired settings.
After you have installed and connected the control board with a power source, be sure to reset the factory
defaults by clearing memory. This procedure is reviewed later in this section.
S1.1 –S1.12 –System Configuration DIP Switches
The following outlines the functions that system configuration DIP switches S1.1 to S1.12 regulate. Refer to
Table 1 –System Configuration DIP Switch S1 Settings on page 16 for function activation and DIP switch
settings.
S1.1 - Communication Mode
Keyscan CA8WL-AL control boards support serial, network and reverse network communication modes. Serial
and network communication use standard polling in which communication is initiated at the communication
manager server. Reverse network communication differs from standard polling in that communication is
initiated at the control unit. Do not set the S1.1 switch for reverse network communication unless a RN license
was purchased from Keyscan.
S1.2 - Communication Bit Rate Selection
The communication bit rate selection regulates the number of bits per second the control board processes. The
control board may be set on one of its configurable bit rates. Ensure that the Keyscan Client software baud
rate setting matches the control board’s bit rate when using a serial connection. If using the on-board Ethernet
module, ensure the module is programmed with the corresponding control board bit rate.
S1.3 - P3 Card Lockout
The Client’s P3 cardholder lockout mode can be overridden when the S1.3 DIP switched to the on position,
which allows a valid credential access on a single presentation.
S1.4 - Alternate Panel Serial Number
Each Keyscan control board is programmed with a factory-assigned serial number for identification and
communication with the Keyscan software.
In the event a duplicate serial number is detected during ACU setup in the Client software, you will be
prompted by the Client application to reset the control board with an alternate serial number. However, unless
you are prompted in the Client software, always use the factory-assigned serial number.

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
15
S1.5 - Reader LED Mode
This DIP switch is not applicable.
S1.6 - Unassigned
Reserved for future use.
S1.7 - Temporary Card Countdown
The Client software has a card usage countdown function when credentials are issued on a temporary basis. To
employ this function in the Client software, the temporary card countdown DIP switch must be enabled on the
CA8WL-AL control board.
S1.8 –N/A
This DIP switch is not applicable.
S1.9 - Clear Memory Enable
The S1.9 DIP switch must be on to enable the J1 Clear Memory jumper for restoring the factory defaults.
S1.10 & S1.11 - Communication Terminal Activation
DIP switches S1.10 and S1.11 activate the RS-232 terminal for direct serial communication or network
communication with the internal, on-board Ethernet module for run mode or program mode.
S1.12 - Flash Program Memory Upgrade
Currently, this function is unavailable.

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
16
Figure 5 –System Configuration DIP Switches S1.1 –S1.12
Table 1 –System Configuration DIP Switch S1 Settings
S1 Switch #
Setting
Function
Notes
S1.1
0 = Off
1 = On
Communication Mode
0
Serial Communication –standard polling
Also see S1.10 & S1.11 in the table.
0
Network Communication –standard polling
As above.
1
Reverse Network Communication
Requires a license from Keyscan.
S1.2
Communication Bit Rate
0
115,200 bit/s
1
57,600 bit/s
S1.3
P3 Card Lockout
0
Enabled
1
Disabled
S1.4
Alternate Panel Serial # Selection
0
Factory-assigned serial #
Only set DIP switch for alternate serial
number if prompted in the Client
software when adding a panel.
1
Adds 1000 to factory-assigned serial #
DOOR RTE AUX1 AUX2
-
+
-
+
-
+
-
+
READER 1 READER 2
C1
(BEEP)
LED
D1
WHITE
D0
GREEN
PWR
RED
GND
BLK
C1
(BEEP)
LED
D1
WHITE
D0
GREEN
PWR
RED
GND
BLK
J6
J4 J1
RDR
RST. CLR
MEM.
SYS.
RST.
Location of System
Configuration DIP Switches
S1.1 to S1.12
Cut view with right
cover removed.
KI-00341E-02-14
RDR/SUPV. CONFIG.SYSTEM CONFIG.
ON
678910
2345
1
678910
2345
111 12
ON
S1
S2
Switch Off
Off = 0
Switch On
On = 1
Switch Settings

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
17
S1 Switch #
Setting
Function
Notes
S1.5
Reader LED Mode
0
n/a
1
n/a
S1.6
Unassigned
0
n/a
1
n/a
S1.7
Temporary Card Countdown
0
Disabled
If credentials are issued on a
temporary basis, the temporary card
countdown function must be enabled.
1
Enabled
S1.8
N/A
0
n/a
1
n/a
S1.9
Clear Memory Enable
0
Disabled
Note –clear memory enable S1.9
activates the Clear Memory jumper J1
to reload factory defaults.
1
Enabled
S1.10 & S1.11
0=Off 1=On
Communication Terminal Block
Activation
S1.10
S1.11
0
0
Enables RS-232 serial TB5 terminal block
For direct serial communication
0
1
Future use
1
0
Enables Ethernet operation mode
For network communication
1
1
Enables Ethernet program mode
For programming the Ethernet module
S1.12
Flash Program Memory Upgrade
0
n/a
1
n/a

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
18
S2.9 & S2.10 System Software Mode DIP Switches
DIP switches S2.9 and S2.10 select the Keyscan software application.
The CA8WL-AL control unit must be set on Aurora as outlined in Table 2.
Important
After the control board has been in operation, if the system software mode DIP switches are altered, you
must perform a clear memory on the control board. Procedures are outlined on page 18 .
The system mode jumpers do not require modifications for a version upgrade.
Figure 6 - System Software Mode DIP Switches S2.9 & S2.10
Table 2 –System Software Mode DIP Switch Settings
S2 Switch #
Settings
Keyscan Software
Version
S2.9 & S2.10
Off=0 / On=1
System Software Mode
S2.9
S2.10
0
0
n/a
0
1
n/a
1
0
Future use
1
1
Aurora
1.0.8.0 or higher
J1 - Restore Default Settings/Clear Memory
Jumper J1 is used to restore the control board’s factory default settings. You must restore the factory default
settings whenever one or more of the following procedures are undertaken on the CA8WL-AL control board:
AUX2
-
+
READER 1 READER 2
C1
(BEEP)
LED
D1
WHITE
D0
GREEN
PWR
RED
GND
BLK
C1
(BEEP)
LED
D1
WHITE
D0
GREEN
PWR
RED
GND
BLK
J6
J4 J1
RDR
RST. CLR
MEM.
SYS.
RST.
Location of System
Software Mode DIP
Switches S2.9 to S2.10
Cut view with right cover
removed.
KI-00343E-02-14
RDR/SUPV. CONFIG.SYSTEM CONFIG.
ON
678910
2345
1
678910
2345
111 12
ON
S1
S2
Switch Off
Off = 0
Switch On
On = 1
Switch Settings

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
19
when a control board has been newly installed
when the CA8WL-AL has had a flash memory upgrade
when system software mode DIP switches S2.9 / S2.10 have been changed
when temporary card countdown DIP switch S1.7 has been changed
Procedure
To restore the factory default settings, ensure the control board has power, enable DIP switch S1.9, short
J1 momentarily, and then disable DIP switch S1.9.
After placing the jumper on J1, the system status LED begins flashing red and the control board’s piezo
emits a cycle of 2 short beeps followed by a pause. This occurs for approximately 2 minutes while the
factory default settings are loaded and the database information is erased from the on-board memory. Do
not make any changes to the control board, such as altering jumpers or powering down the board, while
the factory defaults are being restored or you will have to repeat the procedure. After the system status
LED has stopped flashing, the factory default settings have been restored and the Keyscan database has
been cleared from the on-board memory. After you have restored the factory defaults, perform an upload
from a PC with a Keyscan Client software module so the Keyscan database is transferred to the control
board’s on-board memory.
If this is a new installation, enter the site information in the Keyscan Client software and then upload the
Keyscan database information to the control board(s). Until you perform an upload from a Keyscan Client, the
access control unit(s) will not function.
Figure 7 –Restore Default Settings (Clear Memory) J1 Location
J6 - System Reset
Excluding the changes outlined under Restore Default Settings on the preceding page, whenever you have
changed the DIP switches or altered jumpers on the CA8WL-AL control board while it is powered, perform a
system reset by momentarily placing a jumper on J6.
AUX2
-
+
READER 1 READER 2
C1
(BEEP)
LED
D1
WHITE
D0
GREEN
PWR
RED
GND
BLK
C1
(BEEP)
LED
D1
WHITE
D0
GREEN
PWR
RED
GND
BLK
J6
J4 J1
RDR
RST. CLR
MEM.
SYS.
RST.
Location of Clear Memory Jumper J1
Cut view with right
cover removed.
KI-00349E-02-14
RDR/SUPV. CONFIG.SYSTEM CONFIG.
ON
678910
2345
1
678910
2345
111 12
ON
S1
S2
Jumper Off
Off = 0
Jumper On
On = 1
Jumper Settings
Enable Clear Memory
DIP Switch S1.9 = ON

Keyscan Inc. A Member of the Kaba Group –CA8WL-AL Rev. B Installation Guide (07.15)
20
Figure 8 –Location of System Reset Jumper J6
AUX2
-
+
READER 1 READER 2
C1
(BEEP)
LED
D1
WHITE
D0
GREEN
PWR
RED
GND
BLK
C1
(BEEP)
LED
D1
WHITE
D0
GREEN
PWR
RED
GND
BLK
J6
J4 J1
RDR
RST. CLR
MEM.
SYS.
RST.
Location of System
Reset Jumper J6
Cut view with right
cover removed.
RDR/SUPV. CONFIG.SYSTEM CONFIG.
ON
678910
2345
1
678910
2345
111 12
ON
S1
S2
Jumper Off
Off = 0
Jumper On
On = 1
Jumper Settings
KI-00517E-02-14
Table of contents