Soyal AR-321H User manual

SOYAL
ACCESS CONTROL SYSTEM
®AR-321-H /AR-721-H/ AR-331-H
AR-725-H / AR-757-H V221226
- 1 -
e x1
e x1
f x2
f x2
f x2
c x2
A.
A1.
A2. A3.
B.
E.
B.
C.
F.
C. H.G. D.
D.
b x2
a x2
c x2
d x2
CN1 CN2 CN4 CN5
CN1 CN2
CN4CN3
CN1 CN2
CN4CN3
CN5CN2 CN3 CN4CN1
Contents
AR-331-H: Touch-panel Metal Housing / AR-331-H-S: Metal Housing
AR-321-H: Touch-panel Metal Housing
AR-721-H
AR-725-H: Illuminated Touch-panel
AR-757-H
AR-725-H-M
AR-725-H
AR-725 (X)
1Product
1Product
1Product
1Product
1Products
1Products
1Products
5Optional
2Terminal Cables
2Terminal Cables
2Terminal Cables
2Terminal Cables
2Terminal Cables
2Terminal Cables
3Tools 4Accessories
3Tools
3Tools
3Tools
3Tools
3Tools
2Tools
4Water proof Strip
Parts Description
Button Head Pozidriv
Tapping Screw: M3x10
Security Torx Screw:
M3.5x15
Flat Head Cap Philips
Tapping Screw: 4x19.1
Button Head Pozidriv
Slotting Screw: 2.5x10
Flat Head Hex Socket
Screw: M3x8
Flat Head Cap Philips
Tapping Screw: 4x38
a.
e. f.
b. c. d.
Security Torx Screw: M3x10 Security Torx Wrenches
g. h.
※ Additional external relay must be purchased.
d x2
f x1
h x1
AR-331-H AR-331-H-S
CN1 CN2
CN3 CN4 CN5
or
WG keyboard
(Optional)
Water proof Strip
AR-721RB
Digital Relay
CN1 CN2 CN4CN3
V221226
- 2 -
4
2C.
1
c.
A.
B.
3
4
5
A. B. C.
6
A.
B.
D.
7
8
A.
C.
d.
F.
1A1.
F.
E.
2
4
5
e.
3
A3.
A1.
G.
1
2
3
e.
b. A2.
A1.+A3.
H.
4
5
5
a.
D.
4
41
2
3
2
3
4
5
16
Access Controller
Touch-panel Metal Housing / Illuminated Touch-panel
Installation
AR-321-H
AR-721-H
AR-725-H
AR-331-H / AR-331-H-S
AR-757-H
AR-725-H-M
AR-725-H
AR-725 (X)
Pull the cables from the square hole of the mounting plate.
Use a screwdriver to screw the mounting plate onto the wall.
Attach the water proof strip to the body, then connect the terminal cables to the body and attach the
body to the mounting plate.
Use the Allen key and screws (accessories supplied) to assemble the body onto the mounting plate.
Turn on the power, and LED will light and beep will sound.
Pull the cables from the square hole of the mounting plate.
Use a screwdriver to screw the base onto the wall.
Connect the terminal cables to the body and attach the body to the mounting plate.
Assemble the covers with the Allen key and screws (accessories supplied).
Turn on the power and LED will light and beep will sound.
Pull the cables from the square hole of the mounting plate.
Use a screwdriver to screw the base onto the wall.
Connect the terminal cables to the body and attach the body to the mounting plate.
Assemble the covers with the Allen key and screws (accessories supplied).
Turn on the power and LED will light and beep will sound.
Pull the cables from the square hole of the mounting plate.
Use a screwdriver to screw the base onto the wall.
Embed the water proof strip 3onto the frame side of the base.
Connect the terminal cables to the body and attach the body to the mounting plate.
Assemble the covers with the Allen key and screws (accessories supplied).
Turn on the power and LED will light and beep will sound.
Pull the cables from the square access hole of the mounting plate C.
Use a screwdriver to screw the metal plate Conto the wall.
Take o󰀨 the plastic mounting plate Bfrom the body A, and pull the cables
through the access hole of Cand B, then connect to the body A.
Assemble plate Bwith the body A, and embed the water proof strip D
onto the plastic side frame.
Assemble the body Aonto the mounting plate Cwith the Allen key and
screws (accessories supplied).
Turn on the power and LED will light and beep will sound.
Use a screwdriver to screw the base F onto the wall.
Attach the water proof gasket to the body A1, and pull the cables
from the square hole of the base F, and connect to the body A1.
Assemble the body A1 with the base F.
Screw A1 and F tight with the Allen key and screws (accessories
supplied).
Turn on the power and LED will light and beep will sound.
Put on G, and attach A1 onto the plastic plate A3, and screw it with
the Allen key and screws (accessories supplied).
Put the ring O on the metal frame, and put them together onto the
reader A1+A3, and screw them and buckle up the 4 buckles on the
back.
Embed the water proof strip Donto the frame side of the base.
Following by the install process of AR-725 (H-M)
Remove the rubber plug.
To cut tamper-resistant column and make it fit the appropriate
height for actual installation.
First, take o󰀨 the metal casing then screw the controller on the wall.
Second, put the metal casing back and lock it with security screw.
Finally, put the rubber plug into the hole.
Turn on the power, and LED will light and beep will sound.
SOYAL
ACCESS CONTROL SYSTEM
®AR-321-H /AR-721-H/ AR-331-H
AR-725-H / AR-757-H V221226
- 3 -
Installation(mm)
AR-321-H AR-331-H / AR-331-H-S
AR-721-H
AR-725-H / AR-725-H-M
AR-757-H
158 mm
55 mm
30 mm
27.5 mm
19 mm 87 mm 22 mm
16.5 mm 27.5 mm
34 mm
14 mm
126 mm
83.5 mm
61 mm
91 mm 32 mm
78.5
15 14.730
59.7
21.5
25.5
110
84
30
14.315.9
60
17.6 82.5 24.2
89 25.7
32
29.99 .5
AR-725-H AR-725-H-M
22.5
111
77
42 30
30
41.5
33 mm
114 mm
78.5 mm
78 mm
57 mm
(Front View)
(Front View)
(Front View) (Front View)
(Front View)
(Front View)
(Side View)
(Side View)
(Side View) (Side View)
(Side View)
(Side View)
V221226
- 4 -
Access Controller
Touch-panel Metal Housing / Illuminated Touch-panel
LED
Cable : WG
LED
Wire Application
Wiegand
Beeper
Pin
1
2
3
4
5
Color
Thin Blue
Thin Green
Pink
Brown
Yellow
Description
Wiegand DAT:1 Input
Wiegand DAT:0 Input
Beeper Output 5V/100mA, Low
LED Green Output 5V/20mA, Max
LED Red Output 5V/20mA, Max
※After S/N: 0706-XXXXXX
Wire Application
Lock Relay
Common-COM-Point
Door Sensor
Exit Switch
Alarm Relay
Power
Pin
1
2
3
4
5
6
7
8
Pin
1
2
3
4
5
6
7
Color
Blue White
Purple White
White
Orange
Purple
Gray
Thick Red
Thick Black
Color
--
--
Thin Blue
Thin Green
Pink
Brown
Yellow
Description
(N.O.) DC24V1Amp
(N.C.) DC24V1Amp
(COM) DC24V1Amp
Negative Trigger Input
Negative Trigger Input
Low output; Max 12V/100mA (Open Collector)
DC Power 12V
DC Power 0V
Connector Table
Notice
The communication wires and power line should NOT be bound in the same conduit or tubing.
Don’t equip controller and lock with the same power supply. The power for controller may be unstable when the lock is activating, that may make
the controller malfunction.
The standard installation: Door relay and lock use the same power supply, and controller use independent power supply.
Use AWG 22-24 Shielded Twist Pair to avoid star wiring.
1.Tubing:
2.Wire selection:
3.Power supply:
CN1
CN2 CN4
CN3 CN5
CN1
CN2
CN4
CN3
CN5
CN4
CN2
CN1
CN5
CN3
CN1
CN2
CN4
CN3
CN5
125kHz
125kHz
125kHz
125kHz
125kHz
13.56MHz
13.56MHz
13.56MHz
13.56MHz
13.56MHz
CN1
CN2
CN4
CN5 CN3
CN1
CN3
CN2 CN5
CN4
CN4
CN1
CN5
CN2
CN3
Cable : Burglary (Optional)
Cable : Burglary / Security Relay (Apply to 757-H)
AR-321-H AR-331-H AR-721-H AR-725-H AR-757-H
AR-321-H AR-331-H AR-721-H AR-725-H AR-757-H
AR-321-H AR-331-H AR-721-H AR-725-H AR-757-H
AR-321-H AR-331-H AR-721-H AR-725-H AR-757-H
CN1
CN2
CN3
CN4
CN5
CN1
CN4
CN3
CN5
CN1
CN5
CN4
CN3
CN1
CN5
CN4
CN3
CN5
CN3
CN4
Wire Application
------
Wiegand Reader
Beeper
Description
Reserved
Reserved
Wiegand DAT:1 Input
Wiegand DAT:0 Input
Beeper Output 5V/100mA, Low
LED Green Output 5V/20mA, Max
LED Red Output 5V/20mA, Max
AR-321-H
AR-721-H
AR-331-H / AR-331-H-S
AR-725-H
AR-757-H
Cable : Power/Door/Alarm
Cable : RS-485
Cable : Tamper
CN1
(Apply to 331H)
(Apply to 321H/721H/725H/757H)
(Included)
Wire Application
Tamper Switch
Pin
1
2
3
Color
Red
Orange
Yellow
Description
N.C.
COM
N.O.
Wire Application
3-PIN Connector
Pin
1
2
3
Color
Black
White
Purple
Description
GND.
Duress
Arming/ Security trigger signal
Wire Application
Networking
Module
Pin
1
2
Color
Thick Green
Thick Blue
Description
RS-485(B-)
RS-485(A+)
Wire Application
Doorbell
Arming
Duress
LED indicator
Pin
1
2
3
4
Color
Brown White
Red White
Yellow White
Green White
Description
BE Output
AR Output/ Security trigger signal Output
DU Output/ TTL out
Hi input/ Green light brighten
SOYAL
ACCESS CONTROL SYSTEM
®AR-321-H /AR-721-H/ AR-331-H
AR-725-H / AR-757-H V221226
- 5 -
※ 1.Enable the security trigger signal: Please refer to the 34 ???
2.Disable "Exit by RTE Button". (Please refer to the
20 ??? of function default value.)
EXIT
12V
GND
12V
GND
12V
GND
N.O.
N.O.
COM
PB
12V
GND
WG 1
WG 0
BZ
GLED
RLED
12V
GND
WG 1
WG 0
BZ
GLED
RLED
GND
12V
12V
GND
N.C.
N.O.
COM
CTL
12V
Door Sensor
ALM
12V
GND
12V
GND
12V
GND
N.C.
12V
GND
EXIT
N.C.
N.O.
COM
CTL
12V
GND
PB
12V
GND
12V
GND
ARM AR-721RB
N.O.
12V
GND
EXIT
N.C.
COM
PB
12V
GND
N.O.
N.O.
COM
N.C.
V+
V-
(If both controller and
electric lock share one
same power supply, this
power supply is not used)
EXIT
E
12V
GND
12V
GND
12V
GND
N.O.
GND
N.O.
COM
PB
12V
GND
P.T.Exit
※ The above wiring diagram is used for two power supply conguration. If the controller and
the electric lock share one same power supply, please connect the V+ & V- of the electric
lock to the V+ and V- of the power supply of the controller.
AR-1207
Electric Bolt
Connect to Reader
Connect to Door Sensor
Connect to Electric Bolt Connect to Magnetic Lock
Connect to Electric Strike
Wiring Diagram
Electric Strike
Controller
Request To Exit
Request To Exit
Request To Exit
POWER
12VDC
POWER
12VDC
Controller
Reader
POWER
12VDC
Alarm
Controller
Door Sensor
Relay Output Module
POWER
12VDC
POWER
12VDC
Strengthen security with AR-721RB
Controller
POWER
12VDC
POWER
12VDC Request To Exit
Electric Bolt
Controller
Controller
POWER
12VDC
POWER
12VDC
POWER
12VDC
POWER
12VDC
Magnet Lock
V221226
- 6 -
B-
A+
B-
A+
B-
A+
Host
CH1
CH2
GND
12V
A+
B-
B-
A+
B-
A+
B-
A+
B-
A+
B-
A+
Node 1
Node 9
Node 8
Node 16
Plug AR-331-H into CN2 connector on the mainboard
Refer to command list and start to operate AR-331-H.
21
34
5
6
72
1
2
345
3
CN5CN2
CN3 CN1
1
3
8
7
6
2
1
AR-331-H External WG keyboard AR-331-H Front Panel & Indicator
※If you want to program system on AR-331-H directly, please order WG
keyboard then install it according to the following pattern.
4
6
LED A LED B
Best Reading
Area
LED A Descrption
Blue Arming / Blue LED
Input (Active High)
Yellow Yellow LED Input
(Active High)
LED B Descrption
Green Power-on/Stand-by
/OK
Red Error/Alarm
Plug in AR-331-H
While power on the device,hands o󰀨 panel for
10 sec. to make sure a successful activation.
Traditional Electronic Door Lock wiring diagram
adopted with controller power supply
Traditional Electronic Door Lock wiring diagram
adopted with interphone power supply
EL
AC
PT
N.O.
COM
PB
V+
V-(GND)
N.C.
N.O.
COM
CTL
V+
EL
AC
PT
N.O.
COM
PB
V+
V-(GND)
N.C.
N.O.
COM
CTL
V+
※ This wiring diagram function is required to setup Door Relay Time in 1 sec, please refer to 02 TTT command.
Access Controller
Touch-panel Metal Housing / Illuminated Touch-panel
AR-716E
Controller
Controller
Controller
Controller
Controller
Converter
Node ID 001
Node ID 254
POWER
12VDC
Connect to Networking
Wiring Diagram
POWER
DC12~24V
POWER
DC12~24V
POWER
AC18V
AR-821RB AR-821RB
Controller
Traditional
Electronic
Door Lock
Traditional
Electronic
Door Lock
Controller
(Controller power supply) (Controller power supply) (Interphone power supply)
SOYAL
ACCESS CONTROL SYSTEM
®AR-321-H /AR-721-H/ AR-331-H
AR-725-H / AR-757-H V221226
- 7 -
M4 / M6 / M8
※ M6: the user capacity can be 65535 because it only reads 5-digits CARD CODE, while in M4/M8 it reads both SITE CODE and CARD CODE(10 digits).
65,535
Mode
Networking/
Standalone
Standalone
Networking/
Standalone
Networking/
Standalone
User
Capacity Access Mode
M4
M6
M8
(Default
Value)
Yes
No
Yes
Yes
No
Yes
Yes
No
Yes
Yes
No
Yes
32
No
32
11
No
11
No
Auto-show
Duty time
Event log
Capacity
120
Holidays
Duress
Function
Time
Zone
Lift
Control
Anti-pass-
back
1.Card only
2.Card and PIN
(4-digit PIN)+
3.User Address (5-digit)
+ PIN
(4-digit Private PIN)
+
1.Card only
(using 17* command to set Arming PWD as 0000)
2.Card and PIN
(4-digit public PIN)+
3.Card or PIN
(4-digit public PIN)
1.Card only
2.Card and PIN
(4-digit Private PIN)
+
3.Card or PIN
(4-digit Private PIN)
1,024
3,000
{721-H/757-H}
{321-H/331-H/
725-H}
1,024
3,000
1,200 721-H
1,500
321-H/331-H/
725 (H)
3,000 757-H
{721-H/757-H}
{321-H/331-H/
725-H}
1,200 721-H
1,500
321-H/331-H/
725 (H)
3,000 757-H
AR-721RB
N.C.
N.O.
COM
CTL
12V
GND
PB
WG Reader
POWER
12VDC
PB / Egress
Alarm
12V+
12V+
12V+ 12V+
V-
V-
V- V-
or
Magnet LockElectric BoltAlarmElectric StrikeDoor Contact
Lock
Connect to PC
or
Multi-Door
Controller
Push Button
EXIT
WG Door D.O.
Connect to
PC for FW
upgrade
BZ
WG 0
WG 1
R-LED
G-LED
CN2
LA+
LB-
21
Door O.C.(N.O.)
Door O.C.(N.C.)
COM
Door Sensor
PB
Alarm
12V+
V-
CN1 CN5
CN3
3456
7
AR-331H AR-331K/U
Connect to PC or Multi-Door Controller
Converter
USB-RS485
TCP/IP-RS485
RS232-RS485
Multi-Door
Controller CH1Host CH2
LA+ LB- LA+ LB- LA+ LB-
AR-331H
345 6 78
12
Arming O/P or
G-LED
BZ
WG 0
WG 1
R-LED
CN2
Set 2
Set 1
X
12V+
V-
CN1
CN3 34 52
4123
1
765
LA+
13.56MHZ Only
LB-
21
CN4 1
2
1
23 1
2
3
Door.D.O (N.O)
34 128
Duress O/P
GND
COM
N.C.
N.O.
CN5 1
2
3
COM
N.C.
N.O.
AR-331-H Connector Table
Adding and Deleting Tag
M4/M8
Enter program mode → 00 NNN [Node ID: 001~254; if the access controller is connected to AR-716E, its Node ID will be 001~016.]
Enter program mode → 04 N [N=4/6/8]
Change the Node ID of Controller
C.Set up M4/M6/M8
Master Code modication
Enter program mode → 09 PPPPPPRRRRRR [Input the 6-digit new master code twice.]
[e.g.] Set the Master code to be 876112, input 123456 → 09 876112876112
Enter the program mode
Input 123456 or PPPPPP
[e.g.] The Default Value= 123456, if the Master Code is already changed= 876112, input 876112 → program mode entered
Exit the program mode
Input
Master Code modication / Change the Node ID of Controller
Enter / Exit Program Mode
※ Conrm the access mode by assessing the beep sounds while entering the Program Mode(M4-4 beeps/M6-6 beeps/M8-8 beeps)
※ Default Card UID Length is 4 (Could not change by command and only be able to change by customized rmware)
Add New Tags
Add by Presenting Tags (apply to Single Tag or a Batch of Tags)
※Important Notice:
Please remember the last user address being added to make
sure the old user data is not being over written with the new card in the future.
(Note : The modication of controller mode between M4/M8(networking) and M6(standalone) will reset the data, user data will be required to rebuild.)
Tag Information
(125kHz) ※ For Mifare tags, the separator between Site Code & Card Code is comma ",".
SITE CODE
CARD CODE
SITE CODE
CARD CODE
V221226
- 8 -
Access Controller
Touch-panel Metal Housing / Illuminated Touch-panel
Delete All Tags
Input 123456 (or Master Code) → 29 29
Delete Single Tag or a Batch of Tags (by Card Code)
Input 123456 (or Master Code) → 10 SSSSS EEEEE
[e.g.] Delete by Card Code: 00058
Enter program mode → 10 00058 00058
[e.g.] Delete by Card Code: 00058~00063
Enter program mode → 10 00058 00063
9
9
9
Delete Tags
Add New Tags
Delete Tags
M6
Add Single Tag(by Card Code) ※Card Code should not be repeated
Add a Batch of Tags(by Card Code) ※Card Code should not be repeated
※by Card Code in Sequence
Input 123456 (or Master Code) → 11 SSSSS EEEEE → OK
Input 123456 (or Master Code) → 11 SSSSS EEEEE → OK
[e.g.] Add one card with Card Code 61632
Enter program mode → 11 61632 61632 → OK
[e.g.] Add a batch of user with sequential Card Number of user address 12058
until 12559 (total 500 tags)
Enter program mode → 11 12058 12599 → OK
Add a Single Tag (by Presenting the Tag) :
Delete Tag (by Presenting the Tag) :
[e.g.] Add single tag
:
Enter program mode → 22 1
→ Present the tag to Access Controller → OK
[e.g.] Delet single tag
:
Enter program mode → 22 0 → Present the tag to Access Controller → OK
Input 123456 (or Master Code) → 22 0
Add a Batch of Tags (by Presenting the Tags):
Input 123456 (or Master Code) → 22 1
Input 123456 (or Master Code) → 22 1
[e.g.] There are 20 tags to add:
Enter program mode → 22 1
→Present 20 tags one by one →OK
Suspend Single Tag or a Batch of Tags (by Card Code in Sequence)
Input 123456 (or Master Code) → 10 SSSSS EEEEE
[e.g.] Suspend by Card Code: 00058
Enter program mode → 10 00058 00058
Suspend Tags
[e.g.] Suspend by Card Code: 00058~00063
Enter program mode → 10 00058 00063
[Add single tag] Add a new tag for selected user address 100:
Enter program mode → 19 00100 00001 → Present the tag → Successfully added tag of user 100
[Add 2 additional tags] Add new tags to the following user address 101-102:
Enter program mode → 19 00101 00001 → Present (User 101) card → Present (User 102) card
→ Successfully added tags of user 101-102
[Add 10 additional tags] Add new tags to the following user address 103-112
Enter program mode → 19 00103 00001 → Present (User 103) card → Present (User 104) card → Present (...) card
→Present (User 111) card →Present (User 112) card →Successfully added tags of user 103-112
The default value of access function of M6 is Card and PIN, it will have 3 beeps for hinting you input PIN
number after card presentation. Access function modication please refer the table below:
17 ???? 15 0000 ????=4-digit PIN(0001~9999 ; default value=1234)
????=4-digit PIN(0001~9999 ; default value=4321)
17 0000 15 0000
17 0000 15 ????
Card and PIN
Card only
Card or PIN
Access Mode Command Description
Tag Information
(125kHz) ※ For Mifare tags, the separator between Site Code & Card Code is comma ",".
SITE CODE
CARD CODE
※M6 Mode only assess Card Number
SITE CODE
CARD CODE
[Add 50 consecutive tags] Add 50 new tags with consecutive card number following user address 00050-00150:
Enter program mode → 19 00050 001001 →Successfully added tags of user 50-150
Add Non-consecutive Tags:
Add Consecutive Tags:
SOYAL
ACCESS CONTROL SYSTEM
®AR-321-H /AR-721-H/ AR-331-H
AR-725-H / AR-757-H V221226
- 9 -
Operation process
[e.g.] The anti-pass-back function of User Address 00154 has been enabled. After presenting the card to get in, the user doesn’t present the card to
leave. When s/he tries to present the card to get in again, since the in-in sequence violates the anti-pass-back rule, s/he will be rejected. To solve this
problem, you can reset it as follows. Enter program mode → 26 00154 00154 2 → Reset
Enable/Disable auto-open time zone
Enter program mode → 20 004 [004= enable Auto-Open Time Zone; 000= disable Auto-Open Time Zone]
Enable/Disable auto open door without presenting one valid card and Automatically release door lock when auto open time is up
Enter program mode → 24 001 [001=enable auto-open door without presenting one valid card
;
000=disable auto-open door without presenting
one valid card]
[e.g.] Enable the anti-pass-back function of User Address from 00152 to 00684: 26 00152 00684 0
Enable card
Enter program mode → 26 SSSSS EEEEE N
[SSSSS= Starting User Address; EEEEE= Ending User Address; N=0(control)/ 1(Not control)/ 2(reset)]
Enable controller
Enter program mode → 20 ??? [128= Anti-pass-back(0=Disable; 1=Enable)/ 064=Entrance/Exit(0=Exit; 1=Entrance).]
Enter program mode → 20 128 (Please refer to function default value for details.)
[e.g.] Enable Anti-pass-back, and set to Exit door= (128 x 1) + (064 x 0) = 128
N: 2 sets of auto-open zone (N=0=1st set; N=1=2nd set)
HHMMhhmm=Staring time to ending time (e.g. 08301200=08:30 to 12:00)
1111111H = 7 days of a week (Sun/Mon/Tue/Wed/Thu/Fri/Sat) + Holiday (H= 0: disable; 1: enable); Holidays can be set via 701Client software.
Set up auto-open time zone
Enter program mode → 0 8 N HHMM hhmm 1111111H
[e.g.] To set the second time zone as 9:30 AM to 4:20 PM, Monday, Wednesday and Friday: 08 1 09301620 01010100 → Done
Usually, anti-pass-back is commonly applied to parking areas in order to prevent from multi-entry with one card at a time, or to locations that
need entry and exit control.
Door will remain open after ashing one valid card. There are 2 time zones supported when Standalone, and 63 time zones when connected to AR-716-E.
Please refer to paragraph Compound Command Function List below to ensure command 20 ??? / 24 ??? will not reset the functions
that already had been changed.
Enter program mode → 28 064 [064= Double Door Control]
Controller with a reader to perform the "Double Door Control".
Double Door Control (M4/M8)
Anti-pass-back (M4/M8)
Auto Open Access (uncontrolled) Time Zone – Automatically Release Door Lock
M4/M8: Private PIN
Card or PIN: Enter program mode → 12 UUUUU ???? [e.g. User Address: 00001 and pass code: 1234, input 12 00001 1234 ]
Card and PIN: Enter program mode → 13 UUUUU ???? [e.g. User Address: 00001 and pass code: 1234, input 13 00001 1234 ]
M6: Public PIN
Card or PIN: Enter program mode → 15 ???? [Input 4-digit PIN, default value: 4321; PPPP=0000:
cancel the function of simply inputting PIN to get access
]
Card and PIN: Enter program mode → 17 ???? [Input 4-digit PIN, default value: 1234; PPPP=0000: access mode will be "Card Only"]
Set up the password
Delete All Tags:
Input 123456 (or Master Code) → 29 29
Delete Tags (by Card Code) :
Input 123456 (or Master Code) → 10 SSSSS EEEEE → OK
[e.g.] Delete a tag with card code 62362
Enter program mode → 10 62362 62362 → OK
9
9
V221226
- 10 -
1.Normal Opening
2.Abnormal Opening
Enable: Enter program mode → After door open : The normal procedure to open door → Input 4-digit arming PWD →
Disable: Enter program mode → Do not open the door
: →Input 4-digit arming PWD → Present a valid card
Enable/Disable Arming status (for M4/M8):
More Details:
SOYAL Security Related Function
Arming Setting and Alarm Trigger Procedure :
※ [The normal procedure to open door] can refer to [Access Mode].
※ Read the [Command List-Arming /Duress Function Setting] below to modify arming PWD.
※ M6 is Standalone Mode, the mode is without Arming /Duress Function.
Enter Programming Mode
Without Enter Programming Mode (Standby Mode): Enter Arming Code (
default value of arming PWD is: 1234
)
Arming ModeDisarming Mode
Triggering󶁖Alarm󶁖
Condition:
Triggering󶁖Alarm
󶁖Condition:
VS abnormal󶁖door󶁖
position
door󶁖open󶁖too
long
door󶁖is󶁖forced
openg
door󶁖is󶁖forced
openg
Door Relay TMArming Delay TMEnable Arming Alarm Relay TMDoor Close TM Alarm Delay TM
Enable
Arming Status
Alarm Trigger
Door open
Green Led Flash Quickly Red Led Flash Quickly
Alarm trigger
Green Led Flash
Standby Mode
(Arming is not enable)
Enable
Arming Status Alarm Trigger
Green Led Flash Quickly Red Led Flash Quickly
Green Led Flash
Arming Delay TMEnable Arming
Standby Mode
(Arming is not enable)
Alarm Relay TM
Alarm Delay TM
Alarm trigger
Access Controller
Touch-panel Metal Housing / Illuminated Touch-panel
H. Lift control
Enable
Enter program mode → 24 002 [002= enable lift control]
[e.g.] User Address NO. 168, only to the 6th and the 20th oor:
Enter program mode → 21 00168 0 00100000
→ 21 00168 2 00001000
Multi oors
Enter program mode → 21 UUUUU S FFFFFFFF
[UUUUU=User Address S: 4 sets of lift control (Input: 0~3) FFFFFFFF:
8 oors setting (F=0: Disable, F=1: Enable)
Single oor
[e.g.] User Address NO. 45, allowed to access the 24th oor: 27 00045 24
Enter program mode → 27 UUUUU FF
UUUU=User Address FF=Floor number (01~32 oor)
Connect with AR-401-IO-0016R to control access oors of users.
In the security management of access control system, the controller or reader status is divided into Standby Mode or Disarming Mode and Arming
Mode. The conditions for triggering the alarm in these two modes is di󰀨erent, as shown in the following comparison:
Set Floor/ Stop
F
8
16
24
32
0
1
2
3
F
6
14
22
30
F
7
15
23
31
F
5
13
21
29
F
4
12
20
28
F
3
11
19
27
F
2
10
18
26
F
1
9
17
25
Please refer to below oor chart
I. Setting Up the Arming
Alarm conditions:
1. Door is forced open
Application:
1. Door open too long: Door is open longer than door relay time plus door close time.
2. Force open (Opened without a valid user card): Access by force or illegal procedure.
3. Door position abnormal: Arming is enabled and the power is suddenly o󰀨 then on.
SOYAL
ACCESS CONTROL SYSTEM
®AR-321-H /AR-721-H/ AR-331-H
AR-725-H / AR-757-H V221226
- 11 -
AR-321-H / AR-331-H / AR-721-H / AR-725-H
Function Selection Value Application
※Default Value
※0: Disable
※
0: Alarm Output
※0: Disable
0: None
※0: Disable
Networking/Standalone
Networking/Standalone
Networking/Standalone
Networking/Standalone
Networking/Standalone
001
002
032
064
128
1: Enable
1: Lift Control
1: Enable
※ 1: Yes
1: Enable
Add value 032 means to activate, deduct value of 032 means to disactivate the function of swipe any tags to release door open
◎
Auto Open without Presenting in Auto-open Time Zone
Alarm Output/ Lift Control
◎Enable swipe any tags to release door open
Stop Alarm by pressing RTE Button or Closing the Door
Doorbell
24 ???
Compound Command Function List
AR-321-H / AR-331-H / AR-721-H / AR-725-H / AR-757-H
Function Selection Value Application
※Default Value
Time Attendance
Auto Relock
Auto Open
Exit by RTE Button
Master Controller of Network
Entrance/Exit
Anti-pass-back
※0: Yes
※0: Disable
※0: Disable
0: Disable
※0: Slave
※0: Exit
※0: Disable
Networking
Networking/Standalone
Networking/Standalone
Networking/Standalone
Networking
Networking
Networking
001
002
004
016
032
064
128
1: No
1: Enable
1: Enable
※1: Enable
1: Mater
1:
Entrance
1: Enable
Function Selection Value Application
※Default Value
Double Door Control
Force Open Alarm Output
※0: Disable
※0: Disable
Networking/Standalone
Networking/Standalone
064
128
1: Enable
1: Enable
Select the desired function, Weighted Value = Selection Index (0 or 1) x Value.
[e.g.] ??? (total weighted value of all functions): Enable "Auto Open" + "Exit by RTE Button" + "Anti-pass-back"
=1*004 + 1*016 + 1*128=148; As a result of that, the command will be 20 148 .
Function Selection Value Application
※Default Value
Enable the RF after door sensor closed to GND
Invalid card to activate alarm relay
Turn o󰀨 all sounds of beeper
Mute the sounds of egress button (RTE)
Reserved
Keep beeing while arming is enabled
Door relay connected to AR-721RB (suited to models without relay built-in)
Arm relay connected to AR-721RB (suited to models with relay built-in)
※0: Deactivate
※0: Deactivate
※0: Deactivate
※0: Deactivate
※0: Deactivate
※0: Deactivate
※0: Deactivate
※0: Deactivate
Networking/Standalone
Networking/Standalone
Networking/Standalone
Networking/Standalone
Networking/Standalone
Networking/Standalone
Networking/Standalone
Networking/Standalone
001
002
003
004
016
032
064
128
1: Activate
1: Activate
1: Activate
1: Activate
1: Activate
1: Activate
1: Activate
1: Activate
Weighted Value Manual :
"Selection" of the function that you need is either
have 0 or 1 value.
Substract the "Value" of each Option with Selection.
Function = [0(deactive)*Value] ; [1(activate)*Value]
Add up all of the Function per Compound Command
(20 , 24 ,etc)
Step 1:
Select the "Function" that you need for each
Compound Command category (20 , 24 , etc)
Step 2:
Step 3: Step 4:
20 ???
28 ???
34 ???
V221226
- 12 -
Factory Reset
Reset User Data Reset User Data &Controller Parameter
(incl. Master Code)
Reset User Data &Controller Parameter
(incl. Master Code) & Reset Parameter Setting- SOR
Enter program mode →29 29
→ Exit the programming mode
Enter program mode →29 20
→ Exit the programming mode
Enter program mode →29 21
→ Exit the programming mode
AR-757-H
Function Selection Value Application
Auto Open without Presenting in Auto-open Time Zone
Lift Control/ Duress Function
Stop Alarm by pressing RTE Button or Closing the Door
※0: Disable
※0: Duress
0: None
Networking/Standalone
Networking/Standalone
Networking/Standalone
1: Enable
1:Lift Control
※1: Yes
※Default Value
001
002
064
24 ???
Command List
Function
Enter program mode
Master code setting
Suspend tag
Delete tag
Add a batch of sequential cards by
inputting card number (M6)
Recover the suspended cards(M4/M8)
Card number modication(M4/M8)
Add card by presenting(M4/M8)
Add/Delete tag by presenting(M6)
Delete all tags
Enable/Disable Door open for any Tag
Mifare tag / card format (Optional)
(M4/M8)
Administrator Card setting
(M4/M8)
Enable the security trigger signal
( with AR-721RB)
Control mode setting
Card or PIN (M4/M8)
Modify the PIN with user address, change
the pass mode into Card or PIN
Card and PIN (M4/M8)
Modify the PIN with user address, change
the pass mode into Card and PIN
Command
PPPPPP
09 PPPPPPRRRRRR
10 SSSSS EEEEE
10 SSSSS EEEEE
11 SSSSS EEEEE
11 SSSSS EEEEE
16 UUUUU SSSSSCCCCC
19 UUUUU QQQQQ
22 N
29 29
0
01 N
07 SSSSS EEEEE
34 ???
04 N
12 UUUUU ????
13 UUUUU ????
Description
PPPPPP=Master Code, default value=123456
PPPPPP=6-digit new master code
RRRRRR=Reconrm the new master code
=Suspend =Delete;
SSSSS=Starting User Address
;
EEEEE=Ending User Address
SSSSS=Starting card number
EEEEE=Ending card number
SSSSS=Starting card number ;
EEEEE=Ending card number
UUUUU= User Address; SSSSS=5-digit site code;
CCCCC= 5-digit card code
UUUUU=User Address; QQQQQ=Card quantity
(00001:
for adding a single card or a batch of random
numbering cards)
N=0(Delete tag); N=1(Add tag)
After enabling Door Open For Any Tag, all cards in
same frequency as controller can pass directly.
N:0=ISO14443A
;
1=ISO14443B
2=ISO15693
;
3=I Code1
;
4=I Code2
PS.1. Please select the transmission standard rst.
2. Ensure both reader and card using the same
transmission standard.
SSSSS-EEEEE=00000-00255
(Administrator Card can enter the program mode
after present the card and press in 3 seconds,
also can exit program mode by present the card.)
Change the "Arming" to the security trigger signal,
when controller is connected with AR-721RB.
Please refer to Compound Command Function
List for details.
N=4: M4; N=6: M6; N=8: M8
Pass by Card or PIN;
UUUUU=User Address;????=4-digit PIN
(0001~9999); 0000=Set as card only
Pass by Card and PIN;
UUUUU=User Address;
????=4-digit PIN (0000~9999)
9
9
(07 Starting User Address Ending User Address )
Master
Code
Setting
Card
Setting
Commands
Additional
Card Function
Setting
Access Mode
Setting
Access Controller
Touch-panel Metal Housing / Illuminated Touch-panel
※If forgotten the current Master Code, Reset through software tools is required. Please refer to the FAQ for more detail:
How to change or reset di󰀨erent kinds of Controller Settings, including Master Code, Parameter Setting and User Data?
SOYAL
ACCESS CONTROL SYSTEM
®AR-321-H /AR-721-H/ AR-331-H
AR-725-H / AR-757-H V221226
- 13 -
Command List
Function
Card or PIN(M6)
Set up the mutual PIN in Card or PIN mode
Card and PIN(M6)
Set up the mutual PIN in Card and PIN mode
Setting duress PWD(M4/M8)
Setting arming PWD(M4/M8)
Node ID setting (Connected to 716E)(M4/M8)
Node ID setting (Connected to the PC directly
without 716E) (M4/M8)
Door Relay Time setting
Alarm Relay Time setting
Arming Delay Time setting
Alarm Delay Time setting
Arming Pulse Time setting
Door Close Time
Controller time clock setting
Same tag reading interval time
Command
15 ????
17 ????
15 ????
17 ????
00 NNN
00 NNN VVV nnn
02 TTT
03 TTT
05 TTT
06 TTT
14 TTT
18 TTT
25 YYMMDDHHmmss
31 TTTT
Description
????=4-digit PIN(0001~9999 ; default value=4321)
????=4-digit PIN(0001~9999 ; default value=1234)
0000= Set as card only
????=4-digit PIN(0001~9999 ; default value=4321)
※The Duress Code 0000 means that disable
Duress Function and the default value is set as
0000 already.
????=4-digit PIN(0001~9999 ; default value=1234)
NNN=Node ID of Access Controller (range:
001~016)
NNN=Node ID of Access Controller
(range: 001~254)
VVV=Virtual 716E Node ID, nnn=Door number
(range:001~254)
TTT=Door relay time 000= Output continuously
001~600=1~600 sec.
601~609=0.1~0.9 sec.
TTT=Alarm relay time 000= Output continuously
001~600=1~600 sec.
TTT=the bu󰀨er time before entering arming mode
001~600=1~600 sec.
TTT=the bu󰀨er time before the alarm is activated
001~600=1~600 sec.
TTT=Arming output time; 000=output continuously
001~250=0.1~2.5 sec.
TTT=Door Close Time: 001~600=1~600 sec.;
default value: 15 sec.
YYMMDDHHmmss=Year/ Month/ Day/ Hour/ Min./
Sec.
TTTT=10~6000 (Base on 10ms, range from 10 to
6000; default value: 1 sec.
:
0100)
Access Mode
Setting
Arming /Duress
Function
Setting
(M4/M8 applicable
, but not M6)
Node ID
Setting
Time /Delay
Setting
Please refer to Compound Command Function List
for details.
N= 0 (1st time zone) / 1 (2nd time zone)
HHMM= Starting time; hhmm= ending time
(i.e.: 08301600=08:30 to 16:00)
7123456H= 7 days of week (Sun/Mon/Tue/Wed/
Thu/Fri/Sat)+ Holiday(H= 0: disable; 1: enable);
Holidays can be set by 701Client software.
SSSSS=Starting User Address;
EEEEE=Ending User Address;
N=0: Enable; N=1: Disable; N=2: Reset
After enabling keypad lock function, press any
button will only has two beeps and no reaction.
Disable the keypad lock function will bring controller
keypad function back to normal. (only Keypad
Controllers have this function ex. AR-721-H; Touch
Keypad Controllers do not have this function ex.
AR-725-H)
UUUUU=User Address, S=4 sets of lift control (0~3);
FFFFFFFF=8 assigned oor(F=0: Disable, 1: Enable)
NNN=site number,
TTT= relay time: 000~600=1~600 sec.
UUUUU=User Address; FF=Floor (01~32 oor)
20 ???
24 ???
28 ???
08 N HHMMhhmm 7123456H
26 SSSSS EEEEE N
(simultaneously)
24 002
21 UUUUU S FFFFFFFF
23 NNN TTT
27 UUUUU FF
Controller
Additional
Function
Setting
Lift
Control
Setting
Exit
Program
Mode
Reader additional setting
Controller parameter setting
Double Door Control / Force Open Alarm
Auto-open time zone setting
Anti-pass-back (Enable user)
Enable/Disable keypad lock
Controller parameter setting
Lift control setting: multi-oor(M4/M8)
AR-401RO16 Lift Relay Activated TM
(M4/M8)
Lift control setting: single oor
(M4/M8)
Exit program mode
Exit program mode and enter arming
mode(M4/M8)
※More Details:Introduction of New Function Commands for Enterprise E Controller and Home H Controller

Other manuals for AR-321H

1

This manual suits for next models

4

Other Soyal IP Access Controllers manuals

Soyal AR-331-E User manual

Soyal

Soyal AR-331-E User manual

Soyal AR-837-EA-T User manual

Soyal

Soyal AR-837-EA-T User manual

Soyal AR-721H User manual

Soyal

Soyal AR-721H User manual

Soyal AR-888U User manual

Soyal

Soyal AR-888U User manual

Soyal AR-881-EF9DO User manual

Soyal

Soyal AR-881-EF9DO User manual

Soyal AR-837-EA User manual

Soyal

Soyal AR-837-EA User manual

Soyal AR-727iV3 User manual

Soyal

Soyal AR-727iV3 User manual

Soyal AR-721K User manual

Soyal

Soyal AR-721K User manual

Soyal AR-829E User manual

Soyal

Soyal AR-829E User manual

Soyal AR-363-E User manual

Soyal

Soyal AR-363-E User manual

Soyal AR-723 H User manual

Soyal

Soyal AR-723 H User manual

Soyal AR-721KP User manual

Soyal

Soyal AR-721KP User manual

Soyal AR-837-E User manual

Soyal

Soyal AR-837-E User manual

Soyal AR-327 User manual

Soyal

Soyal AR-327 User manual

Soyal AR-721K User manual

Soyal

Soyal AR-721K User manual

Soyal AR-327-E User manual

Soyal

Soyal AR-327-E User manual

Soyal AR-101-H User manual

Soyal

Soyal AR-101-H User manual

Soyal AR-888H User manual

Soyal

Soyal AR-888H User manual

Soyal AR-837-EL User manual

Soyal

Soyal AR-837-EL User manual

Soyal AR-331-E User manual

Soyal

Soyal AR-331-E User manual

Soyal AR-327-E User manual

Soyal

Soyal AR-327-E User manual

Soyal AR-888-PBI-S User manual

Soyal

Soyal AR-888-PBI-S User manual

Soyal AR-327-E User manual

Soyal

Soyal AR-327-E User manual

Soyal AR-888-PBI User manual

Soyal

Soyal AR-888-PBI User manual

Popular IP Access Controllers manuals by other brands

CEM Systems emerald TS100 Quick start installation guide

CEM Systems

CEM Systems emerald TS100 Quick start installation guide

ZKTeco C3 Pro quick start guide

ZKTeco

ZKTeco C3 Pro quick start guide

Richelieu SAFE-O-TRONIC access 6330084330 manual

Richelieu

Richelieu SAFE-O-TRONIC access 6330084330 manual

Radionics Easikey 1000 Plus Installation and programming manual

Radionics

Radionics Easikey 1000 Plus Installation and programming manual

Roger MCX2D installation manual

Roger

Roger MCX2D installation manual

Paxton Ins-30156 PROXIMITY P Series quick start guide

Paxton

Paxton Ins-30156 PROXIMITY P Series quick start guide

ZKTeco F19 installation guide

ZKTeco

ZKTeco F19 installation guide

Pamex Kapture KA-WR1S User Manual & Implementation Guide

Pamex

Pamex Kapture KA-WR1S User Manual & Implementation Guide

Videx B100-SA v2 Installer manual

Videx

Videx B100-SA v2 Installer manual

EverFocus EBC890 Specifications

EverFocus

EverFocus EBC890 Specifications

ZKTeco Aurora T1 quick start guide

ZKTeco

ZKTeco Aurora T1 quick start guide

Datavan Facelook X1 user manual

Datavan

Datavan Facelook X1 user manual

IDTECK Star FINGER006 Quick installation guide

IDTECK

IDTECK Star FINGER006 Quick installation guide

Kimaldi Kreta3 Installation and programming manual

Kimaldi

Kimaldi Kreta3 Installation and programming manual

Häfele WT 210 BLE operating instructions

Häfele

Häfele WT 210 BLE operating instructions

Panasonic BMET200 - IRIS RECOGNITION Brochure & specs

Panasonic

Panasonic BMET200 - IRIS RECOGNITION Brochure & specs

ACTi R21CF-31 installation guide