Kidde Alarmline II Digital EN User manual

Page 1 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Page 1 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Alarmline II Digital EN Controller
Installation Instructions

Page 2 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Contents:
Important Guidelines – read before commencing installation Page 3
General Overview Page 4
Technical Specications Page 5
Installation Page 6
- Overview
- Connections Diagram
Operating Modes Page 7
- Wiring Diagram: Independent
- Wiring Diagram: Interlock
Useful Information Page 9
- Leader Cable
- Mounting Dimensions
- Static Discharge Cautionary
Commissioning Page 10
- Normal Operation
- Fault / Alarm Conditions
Testing and Verication Page 14
Two-wire RS-485 Modbus RTU/ASCII Communications Page 15
Resetting the AlarmLine II Digital EN Controller Page 16
Glossary Page 17

Page 3 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Important Guidelines
Please read this instruction leaet thoroughly before commencing installation.
Install the AlarmLine II Digital EN Controller accordingly to meet local and country
installation requirements.
The AlarmLine II Digital EN Controller must be installed in accordance with BS 5839-1:2017 (or
country equivalent) and IEC 60364 and authorities having jurisdiction.
Ensure the product is installed, commissioned and maintained by qualied professionals
according to good engineering practices and who have received sucient training on
the unit.
Only use Kidde AlarmLine II Digital EN Linear Heat Detection cable with the
AlarmLine II Digital EN Controller.
Test the Digital Linear Heat Detection cable before connecting it to the AlarmLine II Digital EN
Controller using a multimeter.
Ensure the end of line resistor (3.6kohm) is securely connected at the end each linear heat
detection cable.
If only one zone is required leave the end of line resistor (3.6kohm) connected across the
terminals of the unused zone.
Ensure any cable glands used are tightened to form a secure and moisture proof seal around
the detection cable and any other cable in or out of the unit.
Do not exceed the maximum operating voltage of the AlarmLine II Digital EN Controller (36Vdc).
Do not connect lengths of linear heat detection cable in ‘T’ connections or spurs.

Page 4 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
General Overview
AlarmLine II Digital EN Controller
The Kidde AlarmLine II Digital EN Controller is a dual zone module for
monitoring up to two zones of Kidde AlarmLine II Digital EN Linear Heat
Detection (LHD) Cable. If an overheat or re situation triggers either zone
of the Digital LHD cable the unit automatically calculates and displays the
distance along the cable, in feet and metres, to the alarm point. The two
zones can operate independently of each other, or in interlock mode and
a separate alarm and normally conducting fault output are provided for
each zone. The unit is intended to be installed between the Digital Linear
Heat Detection cable and a conventional or addressable re alarm
control panel. It has power, fault and alarm lights, as well as volt free
outputs for fault and alarm, corresponding to each zone. It may also be
connected to a industrial process control system using the two wire RS-
485 Modbus RTU/ASCII output.
Figure 1: Typical Installation of the AlarmLine II Digital EN Controller
AlarmLine II
Digital EN
LHD Cable
AlarmLine II
Digital EN
LHD Cable
AlarmLine II Digital
EN Controller

Page 5 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Technical Specications
Kidde Part Number: ADELCU-2
Kidde Part Description: AlarmLine II Digital EN Controller
UL Model Number: ADELCU-2
UL File Number: S36421
Revision: 1.9.2-EN
Approvals: EN54-28:2016
Enclosure:
...Dimensions H180mm x W120mm x D60.5mm (H7.1in x W4.72in x D2.38in)
...Rating NEMA 4, 4X (IP65)
...Finish Light Gray with clear lid
...Display 2 line, 16 character backlit display showing zone status
Power Requirements: All circuits power limited if powered from a power limited supply
Min. Nominal Max.
...Operating Voltage 12Vdc — 24Vdc — 36Vdc
Current Consumption:
...Normal Operation (standby) <15mA <7mA <5mA
...Alarm <40mA <23mA <15mA
Operating Temperature Range: -20°C – +50°C (-4°F – +122°F)
Terminal Blocks:
...Spacing 5mm Rising Clamp
...Rating 16A
...Wire Size 0.08mm2(28AWG) to 4mm2(11AWG)
Supervised Circuits: Power, Input Zone 1 & Input Zone 2
Inputs: Up to two Class B zones of Kidde AlarmLine II Digital EN
LHD Cable
...Max Zone Length 1000m (3,280ft)
...Min Zone Length 1m
...End of line resistor 3.6kohm (included)
...Short circuit current 0.5mA
...Max Zone Voltage 5V
Outputs:
...Communications Two wire RS-485 Modbus RTU/ASCII
...Sounder 2.4kHz 92dBa @ 10cm Buzzer
...Alarm 2x Form C volt-free relay contacts (resistive, common)
Max V 30Vac or 42.4Vdc
Max Current 2A
Max Switching Power 60W, 62.5VA
...Fault 2x Optoisolated phototransistor output (resistive, common)
Max V 35Vdc
Max Current 80mA
Max Power Dissipation 150mW

Page 6 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Overview
The AlarmLine II Digital EN Controller allows accurate location of an alarm point along a length of Kidde AlarmLine II Digital EN Linear Heat Detection
(LHD) cable. It continuously monitors up to two zones of Digital LHD cable for a fault (open circuit) or an alarm (overheat or re condition). Because of the
wide range of applications that Digital LHD cable can be used for, it may not always be possible, or be too time consuming, to locate where along the cable
an alarm has occurred. Using the AlarmLine II Digital EN Controller, when an alarm occurs the distance to the overheat condition is immediately calculated
and displayed on the integrated display.
If a fault is detected, the corresponding fault output stops conducting, triggering a fault at the re alarm control panel. If an alarm is detected, the
corresponding alarm output changes state, triggering an alarm at the re alarm panel. The fault outputs also stop conducting on power loss to the unit or
microprocessor fault, triggering a fault at the re alarm control panel.
The two wire RS-485 Modbus RTU/ASCII output also outputs the current state of both zones. See the section “Modbus RTU/ASCII Communications” for
more detail.
There are two primary congurations of the AlarmLine II Digital EN Controller (see gure 1):
1) The Digital LHD cable can be connected directly to the AlarmLine II Digital EN Controller
2) The Digital LHD cable is connected to a length of leader cable which is connected to the AlarmLine II Digital EN Controller. In this scenario the
leader cable must be “calibrated out” during commissioning of the AlarmLine II Digital EN Controller.
Connections Diagram
Figure 3 shows the connections diagram for the AlarmLine II Digital EN Controller. The unit is provided with a 3.6kohm end of line resistor in each zone
input. If only one zone is required, leave the 3.6kohm resistor connected across the zone which is not in use. Otherwise the 3.6kohm resistor should be
connected at the end of the Digital Linear Heat Detection cable.
Figure 3: Wiring Diagram for the Kidde AlarmLine II Digital EN Controller
Installation

Page 7 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Operating Modes Wiring Diagram Independent
There are two operating modes for the AlarmLine II Digital EN Controller:
1. Independent – This is when the AlarmLine II Digital EN Controller is used as a two zone system. When a fault or overheat condition occurs on a Digital LHD
zone, the corresponding fault or alarm output respectively is triggered. The two zones operate independently and both sets of outputs should be connected
to a re alarm control panel. If the zone is not required leave the 3.6kohm resistor in the zone input terminals as supplied. In this mode, the two zones can
either contain identical rated temperature Digital LHD cables or two different rated temperature Digital LHD cables.
Zone 1: 250m
Zone 2: 120m
+
-
Power supply
250m
120m
- + NC NO
C
NC NO - +
C
Zone/Switch/
IO Module
+
-
+
-
Zone/Switch/
IO Module
Addressable
loop
Addressable
loop
+
-
RS-485
Modbus RTU
A A EOLEOL
Junction Box
Junction Box
Zone 1 Zone 2
AlarmLine II Digital EN
Controller
Alarmline II Digital EN Linear Heat Detection Cable Zones
Equivalent wiring
circuit for
zone/switch/IO
monitor module
Zone/Switch/
IO Module
Normally open
alarm contact
Normally closed
fault contact
EOL
Alarmline II Digital
EN Controller
Fault Output
Alarmline II Digital
EN Controller
Alarm Relay
The EOL and A resistor are usually provided with the fire alarm panel or zone/switch/IO module. For
more information please refer to the Fire alarm panel or addressable module installation instructions.
On each zone output group, the Fault '-' (negative terminal) and Alarm NO terminal are connected
by a soldered jumper on the Alarmline II Digital EN Controller PCB.
A
+
-
Alarmline II
Digital EN
EOL Unit

Page 8 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Operating Modes Wiring Diagram Interlock
2. Interlock – this mode is for applications which require a fail-safe guarantee that an alarm is only triggered when an overheat condition has been detected.
This mode may also be known as coincidence detection. In this case, the same rated temperature Digital LHD cable should be attached to both zones of the
AlarmLine II Digital EN Controller. The alarm output is only activated when both Digital LHD cables trigger an alarm due to an overheat condition. If one
Digital LHD cable zone input registers an alarm but the second does not, the alarm output will not be activated. This is to prevent an alarm if a mechanical or
other issue has triggered one Digital LHD cable and not an overheat condition.
• Only use Zone 1 fault and alarm outputs in Interlock mode.
• Two linear heat detection cables with the same temperature rating must be used and a
minimum of two linear heat detection cables must be installed in each protected space.
See the AlarmLine II Digital EN LHD Installation Instructions for the linear spacing specication.
Zone 1: 250m
Zone 2: 250m
+
-
Power supply
250m
- + NC NO
C
NC NO - +
C
+
-
Zone/Switch/
IO Module
Addressable
loop
+
-
RS-485
Modbus RTU
A
EOL
Junction Box
In interlock mode, the 2 zones of Digital LHD cable are intended
to be installed in close proximity to one another such that if a
fire or overheat condition occurs, both cables will activate.
Zone 1
Equivalent wiring
circuit for
zone/switch/IO
monitor module
Zone/Switch/
IO Module
Normally open
alarm contact
Normally closed
fault contact
EOL
Alarmline II Digital
EN Controller
Fault Output
Alarmline II Digital
EN Controller
Alarm Relay
The EOL and A resistor are usually provided with the fire alarm panel or zone/switch/IO module. For
more information please refer to the Fire alarm panel or addressable module installation instructions.
On each zone output group, the Fault '-' (negative terminal) and Alarm NO terminal are connected
by a soldered jumper on the Alarmline II Digital EN Controller PCB.
A
+
-
AlarmLine II Digital EN
Controller
Alarmline II Digital EN Linear Heat Detection Cable Zone
Alarmline II
Digital EN
EOL Unit

Page 9 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Leader Cable
In certain applications it may be desirable or necessary to use non-
sensing leader cable between the AlarmLine II Digital EN Controller
and the Digital LHD cable. For example, if the the AlarmLine II Digital
EN Controller is located some distance away from the area protected
by the Digital LHD cable. This may be required if the expected ambient
temperature range, or other environmental conditions, where the
Digital LHD cable is to be used is greater than the maximum ambient
temperature range for the AlarmLine II Digital EN Controller. (see steps 8,
9 and 10 in the Commissioning section on pages 10-11).
The maximum length of leader cable that can be used per zone is
dependent upon the leader cable diameter’. The following is a guideline
for typical cable sizes and maximum length:
Leader Cable Size Max Leader Cable Length
20AWG
(16x0.2mm or 0.8mm dia, copper) 1000m
Mounting Dimensions
The AlarmLine II Digital EN Controller is intended to be wall-mounted.
4 holes should be drilled according to the mounting dimensions given in
gure 2. The corresponding mounting holes on the AlarmLine II Digital
EN Controller can be found by removing the lid of the device. The
mounting holes are located adjacent to the lid screw positions. Suitable
screws for the type of wall the AlarmLine II Digital EN Controller is to be
mounted on will need to be provided for separately. The maximum screw
head diameter is 7mm and the maximum screw thread diameter is 4mm.
Static Discharge Cautionary
The following items are cautionary notes that will help prevent
equipment damage or malfunction caused by static discharge:
CAUTION
Static charges produce voltages high enough to damage electronic
components. Follow these precautions when installing, servicing, or
operating the AlarmLine II Digital EN Controller:
• Work in a static-free area.
• Discharge any static electricity you may have accumulated.
• Discharge static electricity by touching a known, securely
grounded object.
• Do not handle the printed circuit board (PCB) without proper
protection against static discharge.
In the event that the AlarmLine II Digital EN Controller malfunctions after
encountering a static discharge correct operation of the unit can be
restored by interrupting power to unit for a brief period (approximately
10 seconds). Setup information can be veried by following the steps in
the Commissioning section (page 10 onwards). In the event of the setup
information being corrupted the unit should be reset following the
Resetting the AlarmLine II Digital EN Controller procedure.
Figure 2: Mounting Dimensions for the Kidde AlarmLine II Digital
EN Controller
Useful Information

Page 10 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
1. After wiring the unit up (see wiring diagram) power up the device.
Device will show screen including software revision number.
2. If the unit is being setup for the rst time the following options will
be shown. If the unit has previously been installed the display will
automatically cycle through the options, showing the stored settings.
3. After the initial title screen the next screen will show a menu (see
right) with three options: Load Congs, New Congs and Self Test. On a
previously congured device, after 10s of no button press the device will
automatically proceed to loading saved congs.
4. If “Load Congs” is selected or no button has been pressed after 10s
on a previously congured device, the screen will show “Loading Saved
Congs”. The previously saved parameters will then be displayed.
5. Select the operating mode. (see “Operating modes” (pages 7-8)
for more detail.
Independent: the two zones operate independently of each
other (default).
Interlock: Both fault outputs activate when a fault occurs on either zone
1 or zone 2. Both alarm outputs activate only when both Digital LHD
zones trigger an alarm.
6. Select the relevant operating programme for Zone 1 based on the
table below:
7. Select the relevant operating programme for Zone 2 based on the table
below:
8. If leader cable is connected between the Digital LHD cable and the
AlarmLine II Digital EN Controller and/or the LHD cable is installed in a
hazardous area and IS barriers are being used, the voltage drop to the
start of the LHD cable must be measured by the AlarmLine II Digital EN
Controller in order to ensure correct operation and accurate distance
location. In order to do this, with the leader cable and/or IS barriers and
LHD cable connected to the AlarmLine II Digital EN Controller, short out
the connection at the start of the LHD cable. Select “Yes” and press Set to
continue.
Commissioning
MAIN MENU
LOAD CONFIGS
LOADING SAVED
C O N F I G S ...
Z1 Cable Type:
T078-V10-A045
Z2 Cable Type:
T078-V10-A045
Operating Mode:
INDEPENDENT
Alarm (or activation)
temperature
Cable Set-Up
T078-V10-A045 T088-V10-A065
78°C (EN78) 3
88°C (EN88) 3
Alarm (or activation)
temperature
Cable Set-Up
T078-V10-A045 T088-V10-A065
78°C (EN78) 3
88°C (EN88) 3
In this example, the rst option has been chosen
for an alarm temperature of 78°C
In this example, the rst option has been chosen
for an alarm temperature of 78°C
Zone 1 ldr cable
Yes
KIDDE ADELCU-2
SW REV 1.6

Page 11 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Commissioning (Cont.)
9. If “Yes” was selected in step 8, the AlarmLine II Digital EN Controller will
then ask if the zone is ready to be calibrated. Ensure that the connection
between the leader cable and/or the IS barriers and the start of the
Digital LHD cable is securely shorted out between the two cores. When
this is done, press the “Set” button to continue.
10. The AlarmLine II Digital EN Controller will display the voltage drop
across the leader cable. If necessary, press “Select” to perform the
calibration measurement again. The AlarmLine II Digital EN Controller will
display the updated voltage drop in mV (milli-volts). The displayed value
should be equal to approximately the loop resistance in ohms from the
AlarmLine II Digital EN Controller, with the short in place, divided by 8.
Once the voltage drop has been conrmed correct, press “Set” to continue.
Now remove the short at the start of the LHD cable.
11. If the Linear Heat Detection cable is connected directly to the
AlarmLine II Digital EN Controller then select No and press the Set button
to continue.
12. Select whether you would like the alarm outputs for both zones to
be latching. If set to Yes, then if an alarm is triggered the unit will either
require the power supply to be interrupted (min. 2s) or the Set button
to be pressed to reset to normal once the alarm conditioned has
been cleared.
13. Select whether the Modbus output should be enabled. If this is not
enabled then proceed to step 17.
14. Select required Modbus type, either RTU or ASCII.
15. Set the Modbus address for this device (1-247).
16. Cycle through the possible Baud Rates for the Modbus RTU/ASCII
output. (2400, 4800, 9600, 19200, 38400, 57600, 115200).
17. Select the number of data bits for the Modbus RTU/ASCII output.
(7 or 8)
18. Select the number of stop bits for the Modbus RTU/ASCII output.
(1 or 2).
19. Select the parity for the Modbus RTU/ASCII output.
(even/odd/none).
Modbus TYPE
RTU
Modbus address
1
Latching outputs
No
Modbus output on
yes
R ea dy to
ca lib r ate?
Zone 2 cal:
109 mV
ZONE 2 ldr cable
no
BAUD RATE
2400
DATA BITs
7
Stop BITs
1
PariTY
Even

Page 12 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Zone 1: OK
Zone 2: OK
{Zone 1: OK
{Zone 2: OK
LED Illustration
Either of the display screens above and a single ashing Power light (green colour) should be visible
when AlarmLine II Digital EN Controller is in normal operation.
Independent mode
Interlock mode
Normal Operation
20. Once the unit has been commissioned, the display will show the zone
status. In normal operation, the display unit in independent mode will
show:
Zone 1: OK
Zone 2: OK
The display unit in interlock mode will show:
{Zone 1: OK
{Zone 2: OK
This indicates the two zones of LHD cable are linked and an alarm is only
transmitted if both zones are triggered.

Page 13 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Zone 1: OK
Zone 2: I/F FAULT
Zone 1: FAULT
Zone 2: OK
{Zone 1: 300M
{Zone 2: OK
{Zone 1: 300M
{Zone 2: 301M
Fault/Alarm Conditions
LED Illustration
21. If an alarm condition occurs the AlarmLine II Digital EN Controller
automatically calculates the distance along the cable to the trigger point
and rst displays this value in metres.
22. The display alternates showing the distance along the cable to the
trigger point in metres and in feet.
23. The unit monitors for relay faults. If an alarm condition occurs but the
relay does not switch state (due to a coil failure for example) the device
will go into relay fault and show the screen to the right, depending upon
which zone is in fault
24. The unit monitors for interference faults when the input may be
changing between alarm, ok and fault conditions, for example, too rapidly.
In this case an I/F fault is displayed on the corresponding zone. Check all
cable teminations are securely fastened and for other sources of noise.
25. The unit monitors for cable faults (i.e. an open circuit). An open circuit
will be displayed as fault (as per zone 1 shown right).
26. In interlock mode, the alarm outputs are only activated when both
LHD cables are triggered. If one cable triggers but not the other the
display will show the distance to the alarm on the triggered zone and the
corresponding alarm LED will ash slowly.
27. In interlock mode, if both cables go into an alarm, the alarm outputs
will be activated and the display will show the distance to the alarm for
each zone. The zone 1 and zone 2 alarm LEDs will light continuously.
Zone 1: RLY FLT
Zone 2: OK
Zone 1: 1751 ft
Zone 2: OK
Zone 1: 534 m
Zone 2: OK

Page 14 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Testing & Verication
1. If self test mode is selected the device will rst load the saved congs
then proceed to cycle through normal operation, alarm and fault.
This is to allow the installer/maintenance engineer verify that the unit
is connected to an external system correctly. The screen will ash “SELF
TEST/MODE” every few seconds.
2. In self test mode the device cycles between normal operation, alarm
and fault every approx. 8 seconds. In normal operation the display will
show ok. The alarm relays will be off and the fault output normally
conducting (on).
3. In self test mode and alarm condition the display will show alarm.
The alarm relays will be on. After approx. 8 seconds the unit will go into
fault condition.
4. In self test mode and fault condition the display will show fault.
The fault outputs will stop conducting (off). After approx. 8 seconds the
unit will return to normal condition. To exit self test mode, press and hold
both SET and SELECT buttons for 10s or more until the device resets.
Zone 1: OK
Zone 2: OK
{Zone 1: OK
{Zone 2: OK
Zone 1: ALM
Zone 2: ALM
{Zone 1: ALM
{Zone 2: ALM
Zone 1: FAULT
Zone 2: FAULT
{Zone 1: FAULT
{Zone 2: FAULT
SELF TEST
MODE
LED Illustration
Independent mode
Independent mode
Independent mode
Interlock mode
Interlock mode
Interlock mode

Page 15 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Two-wire RS-485 Modbus RTU/ASCII Communications
The Kidde AlarmLine II Digital EN Controller includes a two wire RS-485 Modbus output which can be
enabled to output the status of each zone of Digital Linear Heat Detection cable. The AlarmLine II Digital EN
Controller Modbus output supports the Modbus RTU/ASCII protocol and the following functions:
• Function code 4 (Read Input Registers)
The request for reading the input registers should be constructed in the following manner:
• Address of rst register to be read (16-bit)
• Number of registers to read (16-bit)
The AlarmLine II Digital EN Controller will respond in the following manner:
• Number of bytes of register values to be read (8-bit)
• Register values (16-bits per register)
The AlarmLine II Digital EN Controller stores the information for each zone of the Digital LHD cable in the
following format:
Register Description Possible Values
0 Zone 1 status -1 or 65535=fault on zone
0=zone ok
1-32767=distance in metres to trigger point
1 Zone 2 status -1 or 65535=fault on zone
0=zone ok
1-32767=distance in metres to trigger point
2 Zone 1 cable type 1 = T078-V10-A045 (EN78), 2 = T088-V10-A065 (EN88)
3 Zone 2 cable type 1 = T078-V10-A045 (EN78), 2 = T088-V10-A065 (EN88)
If the start address plus the requested number of registers exceed 4, the AlarmLine II Digital EN Controller
will return an ILLEGAL DATA ADDRESS error.
If the request contains a function code other than those supported the AlarmLine II Digital EN Controller will
return an ILLEGAL FUNCTION error.

Page 16 of 17 Revision 1.1 Aug 2020
Document No. AlarmLine II Digital EN Controller Installation Instructions
Resetting the AlarmLine II Digital EN Controller
WARNING: This procedure will erase ALL stored settings and reset the Kidde AlarmLine II Digital
EN Controller back to its factory default state. The cable types, leader cable calibration, latching
output selection and Modbus setup will all require selecting after this procedure.
To reset the AlarmLine II Digital EN Controller back to the factory state, when the unit is powered up and in
normal operation (see step 20 in the Commissioning procedure), press and hold the SET and SELECT buttons
for a minimum of 10 seconds continuously. While the SET and SELECT buttons are held down the power LED
will ash quickly to conrm this procedure is about to take place. After approximately 10 seconds, the unit
will restart and return to step 1 in the Commissioning procedure. The settings are only erased if the menu
option “New Congs” is selected.
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY
QUALIFIED PROFESSIONALS. UTC FIRE & SECURITY CANNOT PROVIDE
ANY ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS PRODUCTS,
INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED RESELLER”, IS
PROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and product safety
information, please check https://resecurityproducts.com/policy/
product-warning/ or scan the QR code:
Product warnings and disclaimers

Glossary
Alarm condition – A re or overheat around the Digital LHD cable which activates the cable and triggers the
AlarmLine II Digital EN Controller.
Cable glands – Used to form a dust-proof and weatherproof seal around a cable entering the AlarmLine II
Digital EN Controller.
Digital linear heat detection cable – a sensing cable comprised of a pair of twisted low resistance
conductors that fuse together at a specic temperature and induce an alarm on a re panel or
interface module.
End of line resistor – A component which allows a residual current ow through a circuit to monitor the
integrity of the circuit. In the event of a break in the circuit, current will stop owing completely and a
trouble or fault signal will be triggered.
Fault condition – A break in one or both cores of the Digital LHD cable or a malfunction of the AlarmLine II
Digital EN Controller.
Independent mode – The mode on the AlarmLine II Digital EN Controller where both zones operate
separately. Each zone can trigger a fault or alarm, or be in the normal state, regardless of the state of the
other zone.
Interlock mode – The mode on the AlarmLine II Digital EN Controller where the alarm relay outputs will only
activate when both Digital LHD cables go into alarm. If one cable triggers but not the other, the alarm
relay outputs will not be triggered.
Junction box – A secure, dust-proof and weatherproof enclosure to protect a join between two lengths of
Digital LHD cable or a length of Digital LHD cable and leader cable.
Leader cable – A non-temperature sensing cable which transmits the signals between two components in
the system, e.g. the AlarmLine II Digital EN Controller and the Digital LHD cable. Does not provide re
detection and may be re-rated to continue functioning even in a re condition.
Two-wire RS-485 Modbus RTU/ASCII Communications – An industry standard, signalling protocol used to
communicate information between components in a system, for example a SCADA system or PLC. Often
used to provide more information to be communicated than simple open or closed status communicated
by a relay output.
Zone – a single circuit of AlarmLine II linear heat detection cable connected across either a AlarmLine II
Digital EN Controller or a re panel and an end of line resistor.
Table of contents
Other Kidde Controllers manuals
Popular Controllers manuals by other brands

Meilhaus Electronic
Meilhaus Electronic USB-GT Series manual

GREER Company
GREER Company MicroGuard MG510 Installation, Calibration and Troubleshooting Manual

SPECS
SPECS CCX 70 user manual

EFI
EFI E-45A Installation and service guide

Kenwood
Kenwood KCA-R10 instruction manual

Voicebird
Voicebird Voicebird Mini user guide